© Siemens AG 2006. All rights reserved.
3AK
Vacuum circuit-breaker module
3AK1 and 3AK3
OPERATING INSTRUCTIONS
Order no.: 9229 9923 176 0B
Ordering location: IC LMV LP PO P C41
AG 09.2013 en
29229 9923 176 0B
2013-09-09
For your safety
Signal terms and defini-
tions Hazards are classified in accordan ce with ISO 3864-2 using the following keywords:
DANGER, WARNING or CAUTION, where there is a risk of personal injury
NOTE, where there is a risk of material damage.
Hazards are classified and indicated in the operating instructions and on the vacuum
circuit-breaker module as follows:
Qualified personnel are, for the purposes of this manual or the warning notices on the vacuum circuit-
breaker module, persons who are familiar with the transport, storage, placement,
assembly, commissioning, operation and maintenance of the product and have the
qualifications corresponding to their activity, such as:
training and authorization to energise, de-energise, clear, earth and tag circuits
and equipment in accordance with established safety practices.
training in the proper care and use of protective equipment in accordance with
established safety practices;
training in providing first aid.
Product liability
DANGER
signal word used to indicate an imminently hazardous situation which,
if not avoided, will result in death or serious injury.
WARNING
signal word used to indicate a potentially hazardous situation which,
if not avoided, could result in death or serious injury.
CAUTION
signal word used to indicate a potentially hazardous situation which,
if not avoided, could result in minor or moderate injury.
Note
indicates a potentially damaging situation.
If the damaging situation is not avoided, the product or something in its vicinity
may sustain damage.
Note
Product liability claims are upheld only if the replacement of the purchased spare
parts is performed by personnel that have been trained and certified by Sie-
mens.
9229 9923 176 0B 3
2013-09-09
Table of contents
For your safety .................................................................................................................................................. 2
Transport, storage and packing ................................................................................................................. 5
Transport ......... ................ ............. ................. ................ ................ ................ ...................................................... 5
Unpacking ........................................................................................................................................................... 6
Reusing the transport unit ................................................................................................................................... 8
Storage ............................................................................................................................................................... 9
General information ...................................................................................................................................... 11
Range of application ............................................................................................................................ ... ...... .... 11
Standards ............... ................ ............. ................ ................ ................ ................ ............................. .... ... ... ... .... 12
Design approval as per X-Ray Ordinance .............................................................................................. ... ... .... 12
Scope of delivery ................................................................................................................................. ... .......... 12
Description ....................................................................................................................................................... 13
Design ........................................................................................................................................ ... ... .... ... ... ... .... 13
Locking devices ...................................................................................................................................... ... ... .... 25
Rating plate ............... ........................................................................................................... ... ... ... ... .... ............. 27
Technical data ...................................................................................................................................... ... ... ... .... 27
Ambient conditions ........................................................................................................................... .... ...... ... .... 28
Installation altitudes ...................................................................................................................... ... .... ............. 28
Switching times ................................................................................................................................ .... ............. 29
Circuit diagrams ......................................................................................................................... ... ... ....... ... ... .... 30
Mounting .............. ............................. ............................. ............................. ...................................... .... ... ... ... .... 35
Attachment in the switching cubicle ................................................................................................. .... ............. 35
Coding ................. ................ ............. ................ ................ ................ ................ ............................. ... .... ... .......... 36
Earthing ............... ................... ................ ................... .................... ................... ................................ .... ... ... ....... 37
Fitting the vacuum circuit-breaker module .......... ... ... .... ... ... ... ........................................................................... 38
Moving the vacuum circuit-breaker module into operating position .................................................................. 40
Electrical connection of the prime conduc tor ...... ... ........................................................................................... 41
Operation .......................................................................................................................................... .... ............. 43
Commissioning ....................................................................................................................................... ... ... .... 43
First closing operation ............................................................................................................................. ... ... .... 44
Closing ....................................................................................................................................... ... ... .... ............. 45
Opening ........................................................................................................................................... .... ... ... ... .... 45
Maintenance .............................................................................................................................................. ... .... 47
Maintenance and servicing ..................................................................................................................... .......... 47
Vacuum interrupter service life . ........................................................................................................................ 50
Accessories and spare parts ............................................................................................................ .... ... ... ... .... 50
Manufacturer's product liability ............ ... ... ....................................................................................... .... ... ... ... .... 51
Disposal ........................................................................................................................................... .... ... ... ....... 51
Service ....................................................................................................................................... ... ... .... ............. 51
Index of keywords ......................................................................................................................................... 53
Legend for all pages ..................................................................................................................................... 55
49229 9923 176 0B
2013-09-09
Blank page
Transport, storage and packing
9229 9923 176 0B 5
2013-09-09
Transport, storage and packing
Transport
Transport weight Refer to the delivery slip for the weight of the transport unit.
Place the transport unit on a level, n on-slip a nd pressur e-resi stant surf ace for inter -
mediate storage.
Transport vacuum circuit-breaker in the original transport unit up to the installation
site or storage location.
Transporting with crane or fork lift
WARNING
Heavy transport weight
Transport unit may fall and fail and sling gear may break.
Use lifting gear, transporting and sling gear suited to the requirements and load-
carrying capacity. Observe transport symbols.
Note
Observe stacking height
For transport, no more than three constructionally identical transport units must
be piled on top of each other.
Observe the loads specified on the transport unit.
Note
Secure load
For transport, secure the load in such a way that the transport unit is not at risk.
Fig. 1 Transporting the pallet with carton
Transport, storage and packing
69229 9923 176 0B
2013-09-09
Transporting with packing Transport the transport unit to the installation site or storage location
with a fork lift or
with sling gear suspended from a crane
- at an angle of twist of approx. 60° or
- with a spreader bar.
After receipt of delivery:
Checking the transport
unit Check transport unit for damage.
Major damage must be documented photographically.
Ensure that any damage to the transport unit is confirmed by the transport com-
pany.
Unpacking
Working equipment Required tools:
- Knife/scissors
- Lifting equipment with lifting gear
- Pliers or lever.
CAUTION
Risk of injury from sharp edges!
Fasteners may break, leaving sharp edges.
Always use a suitable tool to lever ou t fast en e rs.
Note
Do not cut open or dama ge the carton, since it is designed to be re used and
because of the belt straps located underneath.
Belt straps could be severed on the pallet floor when cutting open the carton.
The vacuum circuit-breaker module is attached to the pallet with belt straps. It is
not possible to transport the vacuum circuit-breaker module on the pallet without
using belt straps (see Fig. 4).
Fig. 2 Removing the carton
Transport, storage and packing
9229 9923 176 0B 7
2013-09-09
Opening the transport unit Place the transport unit on a level, non-slip and pressure-resistant surface.
Remove lifting gear or transport means.
Remov e pla st ic wrap .
Lever out fasteners from the carton and lift off carton.
Remove film from the vacuum circuit-breaker module.
Check the delivery is complete.
Check vacuum circuit-breaker module for damage.
If the vacuum circuit-breaker module is damaged, ship it back in the transport
unit (see “Reusing the transport unit” on page 8).
Transporting with pallet,
without carton The vacuum circuit-breaker module can be transported with the pallet, without the
carton.
Thread carrying straps under the pallet or
transport with fork lift.
Note
Do not use the vacuum circuit-breaker if parts are broken, i.e. if you find cracks,
flaking, bent metal parts, damaged plug-in contacts, tears or bare cables.
Send it back in its original transport unit (see “Reusing the transport unit”,
page 8).
Note
Carrying straps may scrape along the vacuum circuit-breaker module and dam-
age it.
If necessary, cover carrying straps with edge protection.
Fig. 3 Removing the film Fig. 4 Transporting with pallet possible
Transport, storage and packing
89229 9923 176 0B
2013-09-09
Transporting without pallet Removing tensioning belts.
Remove accessory pack, if applicable, and store safely in the packaging for
later attachment.
Hang sling gear into the crane eyes.
Carefully lift vacuum circuit-breaker module.
Transport to installation site or leave suspended from crane for further work
steps.
Reusing the transport unit
Reusing the transport unit To transport the vacuum circuit-breaker module again, the pallet with carton and
most of the components can be reused.
Do not reuse severed tensioning belts or plastic wrap.
Pack the vacuum circuit-breaker module in reverse order:
If the transport bracket was already removed, re-mount in reverse order (see
“Delivery state with tra nsport bracket” on p age 36). The transport bracket serve s
to lock the withdrawable part in place in the cartridge insert during transport.
Attach the vacuum circuit-bre aker module safely to the p allet usin g the appropr i-
ate tools.
Cover with film and seal with adhesive tape.
Attach accessories pack.
Attach carton securely to the pallet floor.
Before returning to the factory, ask the responsible sales representative for a
returned goods number (see also “Service”, on page 51).
When returning a vacuum circuit-breaker module, always indicate the type and
serial number (see “Rating plate” on page 27).
Fig. 5 Removing the tensioning belts Fig. 6 Lifting the vacuum circuit-breaker module
Note
If necessary, keep accessory pack on hand for the installation.
Transport, storage and packing
9229 9923 176 0B 9
2013-09-09
Storage
Note
Store the vacuum circuit-breaker module in the following condition:
OPEN switching position
Closing spring discharged
Note
Risk of corrosion damage if stored improperly!
If the storage cond itions listed below are met, the vacuum circu it-breaker module
can be stored for up to a year in its transport unit.
If the stora ge condition s are no t met, the vacuum cir cuit-brea ker module cannot
be stored in the transport unit any longer than 6 months.
If storage of longer than one year is planned, unpack the vacuum circuit-breaker
module fr om the transpor t unit. Further st orage may nece ssitate fresh corr osion
protection, and it must be ensured that the vacuum circuit-breaker module canno t
be damaged.
Storage room Transport unit Storage
time Temperature
range Comments Number of
units per
stack
Enclosed, dry, well
ventilated and as
free from dust as
possible, with a rela-
tive humidity of less
than 60 %.
unopened max.
6months -4C to +5C max. 4
unopened max.
1 year -5 °C to +40 °C max. 4
open over 1 year -5 °C to +40 °C if necessary,
with new corro-
sion protectio n
Transport, storage and packing
10 9229 9923 176 0B
2013-09-09
Blank page
General information
9229 9923 176 0B 11
2013-09-09
General information
Smooth and safe operation of this device requires proper transport and storage, and
professional installation and assembly, as well as careful operation and mainte-
nance.
The basic version and all listed configurations of the vacuum circuit-breaker mod-
ules are type-tested devices as per IEC (3AK3 as per IEEE).
Range of application
3AK vacuum circuit-breaker modules are 3-pole interior circuit-breakers for a rated
voltage range of 7.2 kV - 17.5 kV.
Under norma l operating conditions, the vacuum c ircuit-breaker modu les are main-
tenance-free up to 10 000 operating cycles.
Intended use 3AK vacuum circuit-breaker modules are suitable for switching any type of alternat-
ing current circuits under normal operating conditions, such as:
Three-phase motors for reversing, turning and direct operation
Transformers
Capacitors
Generators
Resistor consumers
Suitable for high frequency of operation and unlimited on-time.
3AK vacuum circuit-breake r modules operate in continuous, periodic and sho rt-term
operation.
WARNING
Dangerous voltage and mechanical movements
When operating electrical devices, certain parts will always be live, and
mechanical parts may move very quickly, even when remotely controlled.
If the warnings are not observed, serio us injury or damage to material may be the
result.
Only personnel with the relevant qualifications may work on or in the vicinity of
this device. These personnel m ust be familiar with all the warnings and servicing
measures specified in these operating instructions.
Note
In the event of subsequent attachments or integrations, e. g. locking parts in con-
nection with switchgears, ensure that
fast-moving parts are not additionally loaded with mass or force, and
additional parts have sufficient clearance, especially from moving and live
parts.
If vacuum circuit-breaker modu les are to be equipped with additional functions by
the customer, we recommend consulting the factory, since tried and tested solu-
tions are frequently available (see also “Additional equipment”, on page 17).
General information
12 9229 9923 176 0B
2013-09-09
Standards
The 3AK vacuum circuit-breaker modules comply with the regulations:
IEC 62271-100,
IEC 62271-1,
IEC 60265-1
IEEE C37.013 (only 3AK3).
All 3AK vacuum circuit-breaker modules comply with the specifications for C2-, E2-
and M2-class circuit-breakers in accordance with IEC 62271-100.
Design approval as per X-Ray Ordinance
The vacuum interrupters installed in the vacuum circuit-breaker modules are of a
design approved under the X-Ray Ordina nce (RöV ) of the Feder al Republic of Ger-
many. They meet the requirements of RöV of 8 January 1987 (BGbl. I, page 114)
§ 8 and Annex II No. 5 up to the level of the rated voltage stipulated according to DIN
VDE/IEC.
Scope of delivery
Delivery includes:
3AK Vacuum circuit-breaker module
Hand crank for circuit-breaker 3AX 1530-2B (optional)
Traversing crank with hand screen for disconnecting component 3AX 1531-4B
(optional)
Operating tool for the earthing switch (manual operation) 3AX1531-3C
(optional)
Operating tool for the earthing switch (motor operation) 3AX1531-3D (optional)
Operating ins tru ct ion s
Circuit-breaker-specific circuit diagrams
Description
9229 9923 176 0B 13
2013-09-09
Description
Design
The 3AK vacuum circuit-breaker module consists of
the mechanism box (60.),
the 3 pole assemblies (19.) with vacuum interrupters (30.),
the cartridge insert (90.) with withdrawable part (80.).
Fig. 7 Opera tin g mech a nism side
15. Pole plate 90. Cartridge insert
19. Pole assembly, complete 93. Locking pin
51. Rating plate 95. Unlocking lever of the cartridge insert
60. Mechanism box 96. Actuating opening for manually operating the earthing switch (optional)
60.3 Transportation eye 97. Position indicator of the earthing switch (optional)
80. Withdrawable part of the cartridge
insert 98. Actuating opening for manually operating the withdrawable part
81. Locking bracket 99. Indication of the operating and disconnected position of the withdrawable part
84. Mounting rail
Description
14 9229 9923 176 0B
2013-09-09
Pole assembly The pole assembly of the 3AK vacuum circuit-breake r module consists of
the upper interrupter support (20.),
with the upper terminal (27.) and the break contact (21.),
the vacuum interrupter (30.),
the lower interrupter support (40.) with the lower terminal (29.) and the break
contact (21.).
Each of the 3 pole assemblies is supported by the pole columns (23.), which are
screwed to the pole plate (15.).
Contact system in the vacuum interrupters
A slight change in the conta ct stroke that occurs over the entire useful life of the vac-
uum interrupter has no effect on its function. There is no need for a status indicator
for the contact system.
Fig. 8 Pole side
15. Pole plate 48. Insulating operating rod
20. Upper interrupter support 68.7 Automatically coupling low-voltage plug
21. Break contact 80. Withdrawable part
23. Pole column 84. Mounting rail
26. Earth terminal 87. Coding
27. Upper terminal 90. Cartridge insert
29. Lower terminal 93. Locking pin
30. Interrupter 109. Coupling of the earthing switch drive
40. Lower interrupter support
Description
9229 9923 176 0B 15
2013-09-09
Mechanism box The mechanism box (60.) contains all the electrical and mechanical components
required to switch the vacuu m circu it- breake r mo du le on or off. In sulating op era ting
rods (48.) transfer the switching movement to the pole assemblies.
The mechanism box is closed with a removable cover (60.1).
There are openings in the cover (60.1) for the operating and indicator elements.
Functions The CLOSE pushbutton (53.) is used to close the vacuum circuit-b reaker module.
The motor (50.4) immedi ately charges the clos ing spring (62.). If th e supply voltage
for the motor fails, the closing spring can be charged wi th a hand crank (50.). Ther e
is an opening (50.1) for this in the cover, behind which you will find the hand crank
coupling (50.5) of the gear unit (50.2).
Indicators The charged state o f the springs is indicated via the sprin g state indicator (55.). The
position indicator (59.) shows the CLOSED or OPEN state. The operating cycle
counter (58.) indicates the number of operating cycles. An operating cycle consists
of one closing and one opening. The rating plate (51.) is attached to the pole plate
(15.).
Fig. 9 Operating and indicator elements
50.1 Opening for hand crank 58. Operating cycle counter
51. Rating plate 59. Position indicator CLOSED-OPEN
53. CLOSE pushbutton 60.1 Cover
54. OPEN pushbutton a) Tightening torque Md = 10 Nm
55. Spring state indicator
Description
16 9229 9923 176 0B
2013-09-09
Fig. 10 Opened mechanism box
50.2 Gear unit 60. Mechanism box
50.4 Motor M1 61. Dashpot
50.4.1 Position switch 62. Closing spring
50.5 Hand crank coupling 63. Circuit-breaker shaft
53.1 Closing solenoid Y9 64. Opening spring
54.1 Shunt release Y1 66. Closing damper
54.2 Shunt release Y2 68. Auxiliary switch S1
54.3 Transformer-operated release Y4 68.1 Operating rod (for auxiliary switch S1)
54.4 Undervoltage release Y7 69. Contactor relay K1
54.5 Transformer-operated release (0.1 Ws) Y6 71. Heater (condensation water protection)
55. Spring state indicator
58. Operating cycle counter
59. Position indicator CLOSED-OPEN
Description
9229 9923 176 0B 17
2013-09-09
Equipment
Basic equip m en t The basic equipment of the 3AK vacuum circuit-breaker module contains:
Additional equipment Every 3AK vacuum circuit-breaker module can also be fitted with the following
equipment:
In addition to the serial shunt release (Y1), the vacuum circuit-breaker module can
be equipped with a maximum of 2 releases of the type 3AX11.
For the permitted possible combinations of the additional equipment as well as spe -
cial designs, refer to catalogue HG11, or contact the responsible sales representa-
tive.
Motor (M1)
Contactor re la y (e lec tric al an ti- pu m pin g device) (K1)
Closing solenoid (Y9)
Shunt release (Y1)
Auxiliary switch (optional) (S1)
•6NO + 6NC
•12NO + 12NC
Position switch for signal “Closing spring charged” (S41, S42)
Circuit-breaker tripping signal, cut-out switch (S6, S7)
Low-voltage interface (automatically coupling low-voltage plug 64-
pole) (X0)
Operating cycle counter
Mechanical anti-pumping device
Mechanical manual closing and opening
Mechanical locking device
Shunt release1) 3AX1101
1) Subsequent installation possible
(Y2, Y3)
Transformer-operated release 3AX11021) (Y 4, Y5)
Transformer-operated release 3AX1104 (0.1 AC)1) (Y6)
Undervoltage release 3AX11031) (Y7)
Heater (condensation water protection)1) (R01)
Electrical manual closing2)
Priority opening 2)
2) No subsequent installation possib le
Description
18 9229 9923 176 0B
2013-09-09
Motor M1
*) The operator' s sup ply voltage may de viat e fro m th e rated su pply voltag e of the
vacuum circuit-breaker module by -15 % to +10 %.
**) Built-in automatic circuit-breaker with C characteristic
Fig. 12 Recommendation for motor protection device
Contactor relay K1
After the supply voltage is applied and if the closing
spring is discharged, the motor starts immediately and
is automatically deactivated internally after charging has
taken place.
Power consumption, maximum:
in the event of direct voltage approx. 750 W
in the event of alternating voltage 1400 W.
In the short charging time, the motor temporarily oper-
ates in the overload range. See Fig. 12 for the rate d cur-
rent for the required motor short-circuit protection.
Note: The motor protection devices are not included in
the delivery of the vacuum circuit-breaker module and
must be ordered separately.
Fig. 11 Motor (50.4)
Rated supply voltage U*) VDC
24 DC
48 DC
60 DC
110 AC 50/60 Hz
110 DC
220 AC 50/60 Hz
230
Recommended rated current of the protective
device I**)A16106462 3
If simultaneous CLOSED and OPEN commands are
continuously applied to the vacuum circuit-breaker, it
returns to the open position after being closed.
Via the function of the contactor relay K1, the vacuum
circuit-breaker pauses there until the CLOSE command
is given again.
This prevents continuous closing and opening (pump-
ing).
Fig. 13 Contactor relay (69.)
Description
9229 9923 176 0B 19
2013-09-09
Closing solenoid (Y9) 3AY1510
1st shunt release (Y1) 3AY1510
The closing solenoid Y9 unlatches the charged closing
spring and switches the vacuum circuit-breaker module
on electrically. It is available for DC or AC voltage.
The closing solenoid Y9 is not designed for continuous
operation and is a utomaticall y deactivated within the cir-
cuit-breaker.
The operator's supply voltage may deviate from the
rated supply voltage of the vacuum circuit-breaker mod-
ule by -15 % to 10 %.
The closing solenoid Y9 can be operated using AC or DC
voltage and is protected against overvoltage.
Power consumption is approximately 140 W / VA
Fig. 14 Closing solenoid (53.1)
In the case of the 1st shunt release Y1, the electrically
fed tripping pulse is passed to the “OPEN” latch by
means of a directly acting magnet armature, thus switch -
ing off the vacuum circuit-breaker module.
The 1st shunt release Y1 is not designed for continuous
operation and is automatically deactivated within the
circuit-breaker.
The operator's supply voltage may deviate from the
rated supply voltage of the vacuum circuit-breaker mod-
ule by -30 % to +10 % in the event of DC voltage and by
-15 % to +10 % in the event of AC voltage.
The 1st shunt release Y1 can be operated using AC or
DC voltage and is protected against overvoltage.
Power consumption is approximately 140 W / VA
Fig. 15 1st shunt release (54.1)
Description
20 9229 9923 176 0B
2013-09-09
Auxiliary swit ch S 1
Breaking capacity
Fig. 17 Breaking capacity of the auxiliary switch 3SV92
Two versions of the auxiliary switch S1 are available for
delivery: with 6 or 12 NO/NC contacts each.
Rated insulation voltage: 250 V AC/DC
Insulation group: C as per VDE 0110
Continuous current: 10 A
Closing capacity: 50 A
Fig. 16 Auxiliary switch (68.)
AC 40 to 60 Hz DC
Operating voltage Operating current Operating voltage Operating current
U (V) I (A) U (V) I (A)
Ohmic load Inductive load
(T = 20 ms)
Up to 230 10
24 10 10
48 10 9
60 9 7
110 5 4
220 2.5 2
Description
9229 9923 176 0B 21
2013-09-09
Position switch
Circuit-breaker tripping signal, cut-out switch (S6, S7)
S21, S22 Position switches (switch off the motor after
charging)
S3 Position switch (opens when closing spring
is charged)
S41, S42 Position switches (report charging state)
Fig. 18 Pos i tio n switc h (5 0. 4.1 )
The position switch S6 makes contact briefly when the
vacuum circuit-breaker module is opened by means of
an electrical release.
This contacting can be used for a signal.
In the event of intentional mechanical opening, the cut-
out switch S7 interrupts the contacting.
Fig. 19 Circuit-breaker tripping signal
Description
22 9229 9923 176 0B
2013-09-09
Low-voltage interface X0, 64-pole
For connection of the control line, the standard version of the vacuum circuit-breaker
modules is equipped with a 64-pole low-voltage plug (68.7).
Fig. 20 Low-voltage interface X0
Description
9229 9923 176 0B 23
2013-09-09
A further shunt release, transformer-operated release, undervoltage release or
instantaneous release can be installed as a 2nd release.
2nd shunt release (Y2) 3AX1101
Transformer-operated releases (Y4, Y5) 3AX1102, (Y6) 3AX1104
The second shunt release Y2 is installed whenever more
than one shunt release is needed.
In this version, the electrical “open” command is passed
by means of a magnet armature to the “OPEN” latch by
release of an energy storage mechanism, thus opening
the vacuum circuit-breaker module. This opening sole-
noid is not designed for continuous operation. Any nec-
essary varistors and rectifiers are integrated in the
release.
Power consumption is approximately 60 W / VA
Fig. 21 2nd shunt release (54.2)
The transformer-op erated re leases Y4, Y5 or Y6 consist
of an energy storage mechanism, an unlatching fixture
and an electromagnetic system. If the tripping current is
exceeded (90 % of the transformer-operated release's
rated current), the energy storage mechanism is
unlatched, thus initiating opening of the vacuum circuit-
breaker module.
For use of the transformer-operated release, matching
transformers are also n eeded for matching, in addition to
the main current transformers.
Power consumption for 0.5 A and 1 A 6 VA at 90 %
of the transformer-operated release's rated current and
with open armature.
Fig. 22 Transformer-operated releases (54.3)
Description
24 9229 9923 176 0B
2013-09-09
Undervoltage release (Y7) 3AX1103
The undervolta ge release Y7 has an electromagne t system that has voltage perma-
nently applied to it when the va cuum circ uit-breaker module is in the closed state. If
the voltage drops below a certain value, the undervoltage release Y7 is unlatched,
thus initiating opening of the vacuum circuit-breaker module via the stored energy
mechanism.
Random tripping of the undervoltage release Y7 is generally performed by an NC
contact in the tripping circuit, but can al so be done with the aid of an NO contact by
short-circuiting the solenoid coil. If this latter method is used, the solenoid coil's
short-circuit cu rr en t is limite d by the bu ilt- in re sist or .
The undervoltage release Y7 can also be connected to voltage transformers.
The undervo ltage relea se Y7 au tomatically trips the vacuum cir cuit-br eaker module
if the rated supply voltage drops to an inadmissible value. Any necessary varistors
and rectifiers are integrated in the release.
Power consumption 6.5 W or 7.5 VA
Note
The undervoltage release Y7 must only be operated with the supplied series
resistor R1.
Note
For switching operations (mechanical or electrical), the undervoltage release
3AX1103… must be connected to control voltage, as otherwise closing is not pos-
sible.
Fig. 23 Undervoltage release (54.4) Fig. 24 Typical circuit for connection of the undervolt-
age release Y7
A
B
R1 resistor
S1 auxiliary switch
Y7 undervoltage release
Description
9229 9923 176 0B 25
2013-09-09
Heater (condensation water protection)
Electrical manual closing/electr. locking device
In the basic version, the vacuum circuit-breaker module with on-site connection is
closed by direct mechanical unlatching of the closing spring. Instead of this mechan-
ical manual closing, “electrical manual closing” is also available.
In this version, the closing circuit of the vacuum circuit-breaker module is electrically
actuated by a sensing device and must also be enabled via a command element
from the control room.
With on-site closing, this permits taking into account system-related interlocking and
allows you to prevent unintentional closing by the control room, for example. This
allows for interlo cking the vacuum circuit-br eaker module, for example, via the aux-
iliary contact of a disconnector.
Vacuum circuit-breaker modu les with ele ctr ic al manu al closing cann ot b e switched
mechanically.
Locking devices
To lock vacuum circuit-breakers as a function of the switching position, the spring
charge mechanisms of the vacuum circuit-breaker ca n be equipped with a lo cking
device. This is also the case for vacuum circuit-breakers on switch gear trucks, in
withdrawable sections or with disconnectors.
Conditions The vacuum circuit-breaker must only be switched on in operating or disconnected
position. The operating or disconnected position is the position of the vacuum circuit-
breaker on the switchgear truck or withdrawable section in the switchgear. At the
same time, the vacuum circuit-breaker may be moved on the switchgear truck or
withdrawable section only when it is open.
Positions of th e vac uum circuit-br ea ke r in the switchgear
Disconnected position The isolating distance between the vacuu m circuit-breaker contacts and the switch-
gear counter-contacts is attained fully .
Operating position The vacuum circuit-breaker is inserted fully into the switchgear and the vacuum cir -
cuit-breaker contacts overlap completely with the switchgear counter-contacts.
The heater limits conden sation and corrosion of the vac-
uum circuit-breaker module.
To this end, the heater has to be connected to the sup-
ply voltage (see circuit diagram included with the deliv-
ery).
The heater's surface tempe rature is at the most 180 °C.
Power consumption 50 W
Fig. 25 Heater (71.)
Description
26 9229 9923 176 0B
2013-09-09
Locking the vacuum circuit-breaker
A sensing and actuation component in the cartridge insert detects the operating
position (CLOSED/OPEN) of the vacuum circuit-breaker.
CLOSED switching posi-
tion If the vacuum circuit-breaker is closed, actuation of the system's sensing and actu-
ation component in the cartridge insert is prevented. A mechanical system in the
switchgear truck or withdrawable section reliably blocks movements of the with-
drawable part on the switchgear truck or withdrawable section.
OPEN switching position If the vacuum circuit-breaker is open, the sensing and actuation component in the
cartridge insert actuates the vacuum circuit-breaker's mechanical locking device
and reliably blocks closing of the vacuum circuit-breaker.
Locking device of the cartridge insert
When the unlo cking le ver (9 5.) is fully folded down, the cartridge insert is locked in
the switchgear by the locking pins projecting from the side (93.) With this the with-
drawable par t is enable d fo r mo vin g.
Locking device for the actuating openings (optional)
The locking magnets Y8 (102.) and Y10 (103.) are u sed to electrically lock the actu-
ating openings in the switch cabinet door. As a result the actuating openings for
manually operating the earthing switch (96.) and the withdrawable part (98.) are no
longer accessible.
Fig. 26 Locking the withdrawable section Fig. 27 Locking the actuating openings
Description
9229 9923 176 0B 27
2013-09-09
Rating plate
Technical data
Fig. 29 Technical data
Dimensions and weights
The dimensions of the vacuum circuit-breaker module can be taken from the rele-
vant dimension drawing. If required, these are available from your sales represent-
ative.
The weight is given on the rating plate of the vacuum circuit-breaker module (see
Fig. 28) or can be taken from the relevant dimension drawing.
Fig. 28 Example – vacuum circuit-breaker module rating plate 3AK
a Manufacturer
b Type designation
c Works serial number
d Rated voltage Ur
e Rated frequency fr
f Rated short-circuit breaking current Isc
g Rated power frequency withstand
voltage Ud
h Rated lightning impulse withstand
voltage Up
i Quality control seal
k Year of manufacture
m Rated operating current Ir
n Rated short-circuit duration tk
oMass m
p Rated operating sequence
r Classification to standard
Rated voltage* UrkV 7.2 12 17.5 17.5
Rated operating current IrA 1250, 2000 , 2500, 3150 , 4000** 1250, 2000,
2500
Rated lightning impulse withstand voltage (peak
value) UpkV 60 75 95 95
Rated power freq uency withstand voltage (effective
value) UdkV 20 (32,
42***) 28 (42***) 38 (42***) 38 (42***)
Rated short-circuit breaking currentIsc kA 40/50 40
Distance between pole centres mm 210 210
Rated operating sequence A B
A O - 3 min - CO - 3 min - CO
B CO - 30 min - CO
* In the event of a rated frequency fr of 50/60 Hz
** 4000 A only with additional cooling
*** On request
Description
28 9229 9923 176 0B
2013-09-09
Ambient conditions
Installation altitudes
Insulating capacity The insulating capacity of insulation in air decreases with rising altitude due to the
lower air density. In conformity with IEC 62271-102, the rated lightning impulse volt-
age values given in Fig. 29 are valid up to an installation altitude of 1,000 m above
sea level.
At altitudes of 1,000 m and higher, the insulation level must be corrected as shown
in Fig. 31:
3AK vacuum circuit-breaker modules are suitable for use
in the following climate classes in accordance with
IEC 60721, Part 3- 3: Class
Climatic ambient conditions: 3K41),
3K62),
3Z2,
3Z5
Biological ambient conditions: 3B1
Mechanical ambient conditions: 3M2
Chemically active substances: 3C23)
Mechanically active substances: 3S24)
1) Peak value of the 24-hour means: +35 °C
2) Without ice formation and wind-driven precipitation
3) Without occurrence of salt fog and simultaneous condensation
4) Restriction: clean insulating parts
5) Average value, measured over 24 hours
6) Average value, measured over 1 month
Fig. 30 Ambient conditions
U U0 Ka
U Rated withstand voltage U under standard reference
atmosphere
U0Required rated withstand voltage for the installation
location
KaAltitude correction factor
Ka = em (H – 1000)/8150
Calculating the altitude correction factor Ka:
H = Installation altitude in metres
m = 1 for AC voltage, lightning impulse voltage (between
phases, phase-to-earth, applied longitudinally)
Example
For a required rated withstand voltage of 75 kV at an alti-
tude of 2,500 m, an insulation level of at least 90 kV
under standard reference atmosphere conditions is
required:
90 kV 75 kV e1 (2500 – 1000)/8150
75 kV 1.2
Fig. 31 Altitude correction factor Ka
Description
9229 9923 176 0B 29
2013-09-09
Switching times
Fig. 32 Switching times
Closing time = period between starting (command) of the closing movement and
the moment of contact touch in all poles.
Opening time = period betwe en starting (comma nd) of the opening m ovement and
opening of the last pole.
Arcing time = period from the start of the first arc to extinction of the arcs in all poles.
Break-time = period between starting (command) of the opening movement and
extinction of the arc in the la st pole to become extinc t (= opening time + arcing time).
Close/Open time = period in an OPEN/CLOSE cycle between the moment of con-
tact touch in the first pole during closing and the time when contact touch has been
cancelled in all poles during subsequent opening.
Dead-time = period from the en d of the current flow in all poles up to the start of cur-
rent flow in the first pole.
Closing time < 75 ms
Opening time
1st shunt release (Y1) < 60 ms
2nd and 3rd release (Y2, Y4, Y6, Y7) < 55 ms
Arcing time < 15 ms
Break time
1st shunt release (Y1) < 75 ms
2nd and 3rd release (Y2, Y4, Y6, Y7) < 70 ms
Dead time 300 ms
Close/Open time
1st shunt release (Y1) < 90 ms
2nd and 3rd release (Y2, Y4, Y6, Y7) < 70 ms
Minimum command duration
Closing solenoid (Y9) 45 ms
1st shunt release (Y1) 40 ms
2nd and 3rd release (Y2, Y4, Y6, Y7) 20 ms
Shortest pulse time for br ea ke r tr ipp ing si gn al
1st shunt release (Y1) > 15 ms
2nd and 3rd release (Y2, Y4, Y6, Y7) > 10 ms
Charging time if actuated electrically (M1) < 15 s
Synchronous operation error between the poles 2 ms
Description
30 9229 9923 176 0B
2013-09-09
Circuit diagrams
The circuit diagrams show all the available components with their wiring options.
Fig. 33 to Fig. 39 show some non-binding examples of vacuum circuit- breaker mod-
ules.
The circuit diagrams for the vacuum circuit-breaker module are compiled depending
on your order.
Mechanical manual closing and electrical closing
Fig. 33 Sample circuit diagram – connection via low-voltage interface, 64-pole,
basic version
Electrical manual closing and electrical clos ing
Fig. 34 Example – circuit diagram with connection via low-voltage interface 64-
pole.
This legend is also valid fo r the following circuit diagrams.
-Y1 -Y2 -Y4
-Y4 -Y5
-Y6 -Y7
-Y7
”OPEN” release
-Y1 -Y2 -Y4
-Y4 -Y5
-Y6 -Y7
-Y7
”OPEN” release
extended auxiliary switch
HA Manual opening S3 Position switch (opens when closing spring is charged)
HE Manual closing S41, S42 Position switches (signal charging status)
K1 Contactor relay (anti-pumping device) S6, S7 Position switches (for circuit-breaker tripping signal)
M1 Motor X0 Low-voltage interface
P Energy storage mechanism Y1 1st shunt release
R1 Resistor Y2 2nd shunt release
S1 Auxiliary switch Y4, Y5, Y6 Transformer-operated release
S10, S11 Position switch (mechanical anti-pumping device) Y7 Undervoltage release
S12 Position switch (prevents electrical closing if there is a
mechanical locking device) Y9 Closing solenoid
S21, S22 Position switches (switch off the motor after charging) V6 Integrated rectifiers for motor
Description
9229 9923 176 0B 31
2013-09-09
1) Integrated varistor
2) Integrated rectifier for AC/DC 100 V
3) Line H07V-K1x2.5sw (as per EN 50525-2-31) when motors are used with DC 24 V/48 V and 60 V
4) Only if a mechanical closing lock is ordered at the same time
a) Motor winding for DC
b) Motor winding with rectifier for AC
c) Closing
d) Closing with anti-pumping device
Fig. 35 Sample circuit diagram 64-pole (part 1) of the vacuum circuit-breaker
a) b) c) d)
Description
32 9229 9923 176 0B
2013-09-09
1) Integrated varistor
2) Integrated rectifier for AC/DC 100 V
a) 1st shunt release with 64-pole plug-connector
b) 2nd shunt release with 64-pole plug-connector
Fig. 36 Sample circuit diagram (part 2) of the vacuum circuit-breaker module
a) b)
Description
9229 9923 176 0B 33
2013-09-09
1) Integrated varistor
2) Integrated rectifier for AC/DC 100 V
3) Attention: connect L+ for direct current (DC)
a) Undervoltage release
b) Low-energy trip-coil
c) 1st transformer-operated release
d) Signal: spring state with 64-pole plug-connector
e) Circuit-breaker tripping signal for 64-pole plug-connector
Fig. 37 Sample circuit diagram (part 3) of the vacuum circuit-breaker module
a) b) c) d) e)
Description
34 9229 9923 176 0B
2013-09-09
The unassigned auxiliary switch terminals are wired up (as shown) with the 64-pole
plug bottom.
Fig. 38 Example – auxiliary switch terminals
Fig. 39 Sample switching operation for connection of the undervoltage release Y7
Normal auxiliary switch Extended auxiliary switch
No wiring required if
a) 2nd shunt release Y2 available
b) Undervoltage release Y7 available
a) b)
System wiring Tripping via NO con-
tact
Tripping via
NC contact
System wiring
Circuit-breaker wiring
Mounting
9229 9923 176 0B 35
2013-09-09
Mounting
Attachment in the switching cubicle
The vacuum circuit-breaker module is delivered in the OPEN switching position.
Before installing the vacuum circuit-breaker module, remove the transport aids (see
“Unpacking” on page 6).
Mounting position The 3AK vacuum circuit-breaker module can only be installed vertically (to the vac-
uum interrupter), as an indoor withdrawable section and as an indoor fixed installa-
tion.
DANGER
High-voltage – danger to life
Touching live parts causes an electric shock.
Do not touch live parts!
When per for m ing wor k on th e switc hg e ar, de-energise it and ea rt h it.
The work described in the following sections must only be performed when
the switchgear has been de-energised:
- Take safety measures to prevent reclosing.
- Observe industrial safety regulations.
- Ensure that the vacuum circuit-breaker module is installed and commis-
sioned only by qualified personnel who are familiar with the operating
instructions and observe the warning notices.
WARNING
Risk of injury due to wrong transport means!
Using wrong transport means may cause the vacuum circuit-breaker module to
fall and injure persons.
Observe weight.
Use means of transport suited to the requirements and load-carrying capac-
ity.
The vacuum circuit-breaker module must not fall over.
Sharp edges may cause injury.
Note
For preliminary work, the vacuum circuit-breaker modulemust be
secured against falling over,
placed on to a su itable supp or t or
suspended from a crane to prepare for installation.
Fig. 40 Mounting position
Mounting
36 9229 9923 176 0B
2013-09-09
Coding
Delivery state with trans-
port bracket The transport bracket locks the withdrawable part into place during transport and
must be removed as follows:
Removal of the M10 nut with washer.
Carefully pull the transport bracket forwards, lift slightly and over closing sole-
noid Y8 (optional).
Remove film and now loose nut underneath. It serves as height adjustment and
must be reused for further transport securing, as does the film.
Note
The vacuum circuit-breaker module can only be fitted into switchbays or switch
cabinets whose coding allows for such fitting.
The coding must not be modified.
The mechanical coding of t he circuit-breaker and th e cir-
cuit-breaker room prevents that similar withdrawable
sections with lower rated operating currents are fitted
into switchbays with larger rated operating currents.
For example, a circuit-breaker for 2 500 A rated operat-
ing current can replace a 1 250 A circuit-breaker, if the
voltage and opening values are equal or larger than
those of the 1250 A switchbay.
However, the 1250 A circuit-breaker cannot replace the
2500 A circuit-breaker.
Fig. 41 Coding, example
Mounting
9229 9923 176 0B 37
2013-09-09
Earthing
Fig. 42 Removal of the M10 nut with washer Fig. 43 Removal of the transport bracket
Note
If the 3AK vacuum circuit-br eaker module is installed into an earthed meta l frame
and is connected permanently and electrically conductive, no separate earthing
is required.
Place serrated washers under the screw heads when fastening the vacuum cir-
cuit-breaker module in this case.
Connect the vacuum circuit-breaker module under the
cartridge insert (90.) on the earth termin al (70.) the high-
voltage protective earth as specified (DIN EN 50341).
For this, connection to earth on the system must be
present in the form of a clamp. If the vacuum circuit-
breaker module is moved into the system, the clamp
must positively lock onto the bolt.
Fig. 44 Earth terminal
Mounting
38 9229 9923 176 0B
2013-09-09
Fitting the vacuum circuit-breaker module
Lift the withdrawable section unlocking lever (95.). This draws in the laterally
projecting locking pins (93.).
Fit the vacuum circuit-breaker module into the system's guide rails and push in
as far as it will go.
Fully fold the withdrawable section unlocking le ve r (95.) ba ck do wn . The locking
pins (93.) now secure the vacuum circuit-breaker module in the switchgear.
Fig. 45 Fitting the vacuum circuit-breaker module Fig. 46 Locking the vacuum circuit-breaker module
Mounting
9229 9923 176 0B 39
2013-09-09
Removing the transport securing device from the undervoltage release
Undervoltage release (Y7)
present? The vacuum circuit-breaker modules with an undervoltage release (Y7) 3AX1103
are supplied with a transport securing device.
Remove the two top screws (60.2) from the cover (60.1).
Undo the two bottom screws (60.2) on the co ver (60.1) until the cover (60.1) can
be taken off.
Slightly tilt the cover (60.1) of the mechanism box and lift off.
Shift th e locking screw of the striker fr om position A to B (see refer ence note in
mechanism box [60.] of the vacuum circuit-breaker module).
Replace the cover (60.1) in the reverse order
and fasten the screws (60.2) with a tightening torque of 10 Nm.
Fig. 47 Removing the cover Fig. 48 Removing the transport securing device
A
B
Mounting
40 9229 9923 176 0B
2013-09-09
Moving the vacuum circuit-breaker module into operating posi-
tion
Note
When moving, en sure that the vacuu m circuit-bre aker module is in following con-
dition:
OPEN switching position
Closing spring discharged
If the switchgear door is locked, the actuating opening
(98.) for manual operation of the withdrawable part (80.)
is enabled.
Moving the withdrawable section with traversing crank
with hand screen 3AX1531-4B:
Through the actuating opening (98.) Fit traversing
crank with hand screen (108.) onto the hexagon
head.
Turn clockwise until the position indicator (99.) for
the withdrawable part (80.) switches the symbol
to .
While turning, a progress indicator between these two
symbols indicates the traversing path.
Fig. 49 Moving the vacuum-circuit breaker module
into operating position
Mounting
9229 9923 176 0B 41
2013-09-09
Electrical connection of the prime conductor
The main current path is automatically closed by the tulip contacts (21.) when the
withdrawable part withdraws.
For this there must be mating contacts in the switchbay that do not deviate by more
than ±2 mm from the nominal dimensions.
The mating contacts can be purchased from the Siemens Service Center.
DANGER
High-voltage – danger to life
Test the vacuum circuit-breaker module in the switchbay with high-voltage
applied only after faultless functionin g has been ascertaine d (see “Commission -
ing” on page 43).
Note
Grease the mating contacts with contact grease prior to mounting.
Fig. 50 Tulip contacts
Mounting
42 9229 9923 176 0B
2013-09-09
Blank page
Operation
9229 9923 176 0B 43
2013-09-09
Operation
Commissioning
Before commissioning, check the following points to ensure that the 3AK vacuum
circuit-breaker module is functioning faultlessly:
DANGER
High voltage – danger to life
Touching live parts causes an electric shock.
Do not touch live parts!
Ensure that the vacuum circuit-breaker module is operated only by qualified
personnel who are familiar with the operating instructions and observe the
warning notices.
Check through all of the items on the checklist and ensure correct functioning
before commissioning.
Checklist Notes
Does the information on the rating plate (see page 27) match the order
data?
Ensure correct operating voltage.
If necessary, clean the vacuum circuit-breaker module (details on this in
section “Cleaning” on page 47).
Check that screw connections are tightened securely.
Check functioning of the auxiliary switches.
If necessary, check and adjust customer's devices.
If there is an undervoltage release (Y7) 3AX1103 : has the locking screw
of the striker been shifted from position A to B (see “Removing the trans-
port securing device from the undervoltage release” on page 39)?
Test switching without supply voltage
Charge the closing spring (62.) with the hand crank (50.) (see Fig. 51),
then actuate the CLOSE pushbutton (53.) and, once closing has been
performed, actuate OPEN pushbutton (54.).
Test switching with supply voltage
To perform test switching with the motor, switch on the supply voltage.
The motor starts up immediately and charges the closing spring (62.).
Check the indicator for charge state of the closing spring (mechanically
and electrically).
Electrically check through auxiliary switch S1 (68.) and position switch
(50.4.1) in both end positions – operate the 3AK vacuum circuit-breaker
module to do so.
Check functioning of the closing solenoid Y9 (53.1) and all available shunt
releases by operating them electrically.
Operation
44 9229 9923 176 0B
2013-09-09
First closing operation
If all functions have been checked an d ar e ok, switch o n high- volta ge while obse rv-
ing all of the safety regulations and operative requirements.
Charging the closing spring
If the supply voltage is applied, the closing spring (62.) is automatically charged by
the motor (50. 4) .
Hand crank If the supply voltage fails, the closing spring (62.) can be char ged with a hand cran k
(50.).
1. For this, fit th e hand crank (50.) onto the hand cran k coupling (50.5) throug h the
opening (50.1) with the adapter pushed forward (50.6).
2. Turn clockwise until the spring state indicator (55.) changes over:
WARNING
Do not commission the vacuum circuit-breaker module if there are malfunctions.
If the malfunctions or the damage cannot be remed ied, contact a sales represent-
ative or Siemens Service and, if necessary , send back the vacuum circuit-breaker
module.
WARNING
Risk of injury if hand cranks other than the original hand crank are used.
When the supply voltage is present, the motor immediately recharges the spring
after a closing operation. If the hand crank does not have a slip coupling, the hand
crank will also rotate.
To avoid injuries caused by the motor starting suddenly, the vacuum circuit-
breaker module must be charged only using the original hand crank.
Discharged Charged
Fig. 51 Charging the closing spring with the hand
crank Fig. 52 Operating elements and spring state indicator
Operation
9229 9923 176 0B 45
2013-09-09
The adapter (50.6) of the hand crank (50.) is designed in such a way that the hand
crank becomes un co up le d wh en the motor supply voltage returns.
Closing
Provided there is no lock-out due to a mechanical locking device, send the closing
command via the CLOSE pushbu tton (53.) or the corres ponding command element
until the vacuum circuit-breaker module is closed and shows and signals the
CLOSED position.
Change of the position indicator (59.):
After switching on and possibly releasing the CLOSE pushbutton (53. ), the closing
spring (62.) is immediately automatically charged by the motor and the indicator
“Closing spring charged” (55.) becomes visible.
Change of the spring state indicator (55.):
Opening
The opening spring (64) is charged during the closing operation.
To open, send the opening command via the OPEN pushbutton (54.) or the corre-
sponding command element until the vacuum circuit-breaker module is open and
shows and signals the OPEN switching position.
Change of the posit i on indic at or (59.) after electrical opening:
The spring state indicator (55.) does not change.
Discharging the closing spring
To discharge the closing spring:
the supply voltage must be deactivated
the vacuum circuit-breaker module must be closed manually (see “Closing” on
page 45) and then
opened manually (see “Opening” on page 45).
The spring state indicator (55.) does not change.
OPEN CLOSED

Charged Discharged Charged
Note
If an undervoltage release 3AX1103… is fitted, it must be connected to the control
voltage for switching operations (mechanical or electrical), as otherwise closing
is not possible.
CLOSED OPEN
Operation
46 9229 9923 176 0B
2013-09-09
Operating tools
Fig. 53 Operating tools
50. 3AX1530-2B hand crank (optional) for charging the closing spring by hand
106. Operating tool for the earthing switch (manual operation) 3AX1531-3C (optional)
107. Operating tool for the earthing switch (motor operation) 3AX1531-3D (optional)
108. Traversing crank with hand screen for withdrawable part 3AX 1531-4B (optional)
Maintenance
9229 9923 176 0B 47
2013-09-09
Maintenance
Maintenance and servicing
Maintenance
The 3AKvacuum circuit-breaker module is maintenance-free under normal operat-
ing conditions. We do, however, recommend you carry out regular visual inspec-
tions. The maximum permitted mechanical operating cycle number is 10 000.
Cleaning
The insulating parts must be clean if their insulating capacity is to be guaranteed.
Rub insulating parts with a moist cloth.
As a cleaning agent, use only warm water with a mild, liquid household detergent
added and leave to dry.
Joints and bearings that cannot be disassembled must not be washed out with a
detergent prior to work.
DANGER
High voltage – danger to life
Touching live parts is fatal or causes serious physical injury.
Before beginning maintenance work, note the five safety rules for high-voltage
equipment specified in EN 50110-1, namely:
Isolate from the power supply*)
Secure against reclosing
Verify safe isolation from the power supply
Earth and short-circuit
Cover or cordon off neighbouring live parts
*) On the vacuum circuit-breaker, actuate the OPEN, CLOSE and OPEN pushbut-
tons manually one after the o ther. This ensures that the vacuum circuit-breaker is
open and the closing spring is discharged.
Note
The vacuum circuit-breaker module should be taken out of the switch cabinet or
switchgear for servicing.
Maintenance
48 9229 9923 176 0B
2013-09-09
Special operating conditions
If the vacuum circuit-breaker module is operated under unfavourable conditions
indoors (heavy and frequent condensation, dusty air, etc.), we recommend cleaning
the insulating parts and possibly the outer parts of the circuit-breaker at shorter inter-
vals.
For this, only the following agents may be used on the individual functional parts of
the circuit breaker module:
Lubricant:
Lubricants are available from the responsible Siemens representative:
Bearings, sliding surfaces: Isoflex Topas L 32
Bearings and bearings of the auxiliary switch S1
that are inaccessible in terms of greasing: Shell Tellus Oil 32
Order no.
180 g Isoflex Topas L 32 3AX11 33-3H
1 kg Shell Tellus Oil 32 (special oil) 3AX11 33-2D
1kg Isoflex Topas L32 3AX11 33-3E
Maintenance
9229 9923 176 0B 49
2013-09-09
Fig. 54 Be ar ing s an d slid ing sur faces of the operating mechanism
Isoflex Topas L 32 Shell Tellus Oil 32
a Crankpin for sensing device actuation b Bearing for deflection lever
c Curve contour f Auxiliary switch
d Close-latch j Circuit-breaker shaft bearing
e Deflection of auxiliary switch p Opening spring bearing
g Opening spring guide r Spring eyelet on closing spring
h Deflection of auxiliary switch
kOPEN-latch
l Curve for OPEN-latch
m End stop
s Contact area of instantaneous release
Maintenance
50 9229 9923 176 0B
2013-09-09
Vacuum interrupter service life
If switching operations occur frequently under overload or short circuit, the service
life of the vacuum interrupters may be reached prematurely.
Replace the interrupters after reaching the maximum permitted operating cycle
number of 10 000 mechanical or electrical loa d setting changes (up to the rated cur-
rent).
When ordering vacuum interrupters, please always state the circuit-breaker type
and serial number (see“Rating plate” on page 27).
Accessories and spare parts
Replacing spare parts To ensure that the device operates reliably, spare parts must be replaced only by
trained and certified personnel.
Fig. 55 Acce ssories availabl e for orde r
Always specify the vacuum circuit-breaker module's type and serial no . (see “Rating
plate” on page 27) when ordering spare parts.
CAUTION
Risk of injury!
The vacuum circuit-breaker module should be taken out of the switch cabinet or
switchgear for servicing.
Separate vacuum circuit-breaker module from the control feed voltage or switch
it off and disconnect the low-voltage plug or clip connection.
Accessories Order no.
Hand crank for circuit-breaker 3AX1530-2B
Traversing crank with hand shield for withdrawable part 3AX1430-2C
Operating instructions 9229 9923 100
Operating tool for the earthing switch (manual operation) 3AX1531-3C
Operating tool for the earthing switch (motor operation) 3AX1531-3D
Klüber lsoflex Topas L32 lubricant 3AX1133-3H 180 g
3AX1133-3E 1 kg
Shell Tellus lubricant 3AXl 133-2D 1 kg tin
Maintenance
9229 9923 176 0B 51
2013-09-09
Manufacturer's product liability
The manufacturer's product liability shall be excluded if at least one of the following
criteria applies:
Original Siemens spare parts are not used.
Fitters carrying out replacements have not been trained and certified by Sie-
mens.
Parts have been incorrectly fitted or adjusted.
Adjustments are not made in accordance with Siemens specifications.
After installation and adjustment, no final test is performed with a tester
approved by Siemens including documentation of the test results.
To keep documentation complete, it is important that measu rement results are sub-
mitted to the responsible sales representative.
Disposal
The materials of the vacuum circuit-breaker module should be recycled. Disposal o f
the vacuum circui t-breake r modu le with minimu m environ mental impa ct is possible
on the basis of existing legal regulations.
Metal The circuit bre aker's metal componen ts can be recycled as mixed scrap, althoug h it
is more environmentally sustainable to dismantle the unit as th or oughly as p ossi ble
into sorted scrap and residual mixed scrap.
Electronics Electronic scrap must be disposed of in accordance with applicable regulations.
Materials The vacuum circuit-breaker module consists of the following materials:
Steel (partly phosphatised, galvanised and yellow chromated)
Copper (partly silver-plated)
Plastics (epoxy resin, polyamide, polyester, polycarbonate, ABS-PC mixture;
partly glass fibre reinforced)
Rubber materials
•Ceramics
•Lubricant
Packaging If the packaging is no longer needed, it can be fully recycled.
Hazardous substances When delivered by Siemens, the product does not contain any hazardous sub-
stances within the scope of the Hazardous Substances Ordnance applicable to the
territory of the Federal Republic of Germany. For operation outside the Federal
Republic of Germany, the applicable local laws and regulations must be complied
with.
Further information Contact your Siemens Service Center if you require further information.
Service
For details of contacts for service work, consult Siemens IC LMV SE Services at
Telephone: +49 180/5247000
Fax: +49 180/5242471 or
on the Internet at the Web address: www.siemens.com/energy-support
by e-mail: support.energy@siemens.com
or any local sales representative.
Maintenance
52 9229 9923 176 0B
2013-09-09
Blank page
Index of keywords
9229 9923 176 0B 53
2013-09-09
Index of keywords
A
Accessories ........................................................... 50
Accessories available for order ............................. 50
Accessory pack ....................................................... 8
Actuating opening ................................................. 40
Altitude correction factor ....................................... 28
Ambient conditions ................................................ 28
Auxiliary switch ............................................. 16 17
Auxiliary switch S1 ................................................ 20
B
Basic equipment ................................................... 17
Bearings and sliding surfaces ............................... 49
Break contact ........................................................ 14
Breaking capacity .................................................. 20
C
Cartridge insert ..................................... 13 14, 37
Circuit-breaker shaft .............................................. 16
Circuit-breaker tripping signal ....................... 17, 21
Climate classes ..................................................... 28
CLOSE pushbutton ............................................... 15
Closing damper ..................................................... 16
Closing solenoid .................................... 16 17, 19
Closing spring ............................................... 16, 25
Coding ................................................................... 14
Contact stroke ....................................................... 14
Contact system ..................................................... 14
Contactor relay .............................................. 16 17
Contactor relay K1 ................................................ 18
Coupling of the earthing switch drive .................... 14
Cover .................................................................... 15
Cut-out switch ............................................... 17, 21
D
Dashpot ................................................................. 16
Disconnected position ........................................... 25
Distance between pole centres ............................. 27
E
Earth terminal ................................................ 14, 37
Earthing switch, actuating opening for
manual operation .................................................. 13
Earthing switch, position indicator ......................... 13
Electrical manual closing .............................. 17, 25
F
Factory number ..................................................... 27
Fitting the circuit-breaker withdrawable section .... 38
G
Gear unit ............................................................... 16
H
Hand crank .................................................... 44, 46
Hand crank coupling ............................................. 16
Hand crank, opening ............................................. 15
Heater (condensation water protection) 16 17, 25
High-voltage protective earth ................................ 37
I
Indication of the operating and disconnected
position of the withdrawable part .................... ... .... 13
Installation altitudes ..................... ... ... ... .... ............. 28
Insulating capacity ............. ... ................................. 28
Interrupter .............................................................. 14
Interrupter support .......................... ... ... .... ... .......... 14
Interrupter, service life ........................................... 50
Interrupter, vacuum check .................... .... ... ... ....... 50
L
Locking bracket .............. ....................................... 13
Locking device for the actuating openings
(optional) ...................... ... ... ... .... ... ... ... .................... 26
Locking devices ..................................................... 25
Locking pin ........................................... 13 14, 38
Locking the withdrawable section ................ ... ... .... 26
Low-voltage interface .................. ... ... ... .... ... . 17, 22
Low-voltage plug ...................... ... .......................... 14
M
Mating contacts ........... ... ... ... .... ... ... ... .................... 41
Mechanical anti-pumping device ................. ... ... .... 17
Mechanical locking device ........... ... ... ... .... ............. 17
Mechanical manual closing .. .... .................... 17, 25
Mechanical manual opening .................................. 17
Mechanism box .................... .... ... ... .............. 13, 16
Motor ............................................................ 16 18
Mounting position ........ .......................................... 35
Mounting rail ...................... ........................... 13 14
Moving the circuit-breaker withdrawable
section into operating position .............. .... ... ... ... .... 40
O
OPEN pushbutton .................................................. 15
Opening spring ........ .... ... ....................................... 16
Operating and disconnected position, indicator ..... 13
Operating cycle counter ........................ .... ... . 15 17
Operating position .......................... ... ... .... ... ... ....... 25
Operating rod ........ ... .... ... ... ... .... ... .......................... 16
Operating tool ....................... .... ... .......................... 46
Operating tool, earthing switch
(manual operation) ............... .... ... ... ....................... 46
Operating tool, earthing switch (motor operation) . 46
P
Pole assembly ............. ... ... .................................... 13
Pole plate ................. .... ................................. 13 14
Position indicator CLOSED-OPEN ........... ... . 15 16
position indicator for the withdrawable part ........... 40
Position indicator of the earthing switch ................ 13
Position switch ...................................... 16 17, 21
Priority opening ............... ... .................................... 17
R
Range of application .......................... ... .... ... ... ....... 11
Rated frequency ................ ... .... ... .......................... 27
Rated lightning impulse withstand voltage ............ 27
Rated operating current ..................... ... ................. 27
Index of keywords
54 9229 9923 176 0B
2013-09-09
Rated operating sequence ......................... .... ... ... . 27
Rated power frequency withstand voltage ............ 27
Rated short-circuit breaking current ...................... 27
Rated short-circuit duration .................. ... .............. 27
Rated voltage .......................... ... ... .... ... ................. 27
Rating plate ........................................... 13, 15, 27
S
Scope of delivery ........................ ........................... 12
Shunt release ............................... 16 17, 19, 23
Spring state indicator .............. ... ... .... ... ... ... ... 15 16
Standards .......................... ... ... ... ... .... ... ................. 12
T
Transformer-operated release .............. 16 17, 23
Transformer-operated release (0.1 Ws) ................ 16
Transport weig h t ..................................................... 5
Transporta tio n ey e .. ... ... ........................................ 13
Traversing crank for withdrawable part ................. 46
Traversing crank with hand screen 3AX1430-2C .. 40
Tulip contact s ... .... ... .............................................. 41
Type designation ..... ... ........................................... 27
U
Undervoltage release ............................ 16 17, 24
Unlocking lever of the cartridge insert ................... 13
V
Vacuum interrupter, contact system ...................... 14
W
Withdrawable part ...... ... .... ... ... .............................. 14
Withdrawable part of the cartridge insert .......... ... . 13
Withdraw ab le pa rt , act ua tin g op e nin g fo r
manual operation .................... ... ... .... ... ... ... ........... 13
Withdrawable part, indication of the operating
and disconnected position ................. ... ... ... ........... 13
Withdraw ab le se ctio n un lockin g lever ................... 38
Legend for all pages
9229 9923 176 0B 55
2013-09-09
Legend for all pages
15. Pole plate
16.1 Upper post insulator
16.2 Lower post insulator
19. Pole assembly, complete
20. Upper interrupter support
21. Break contact
23. Pole column
26. Earth terminal
27. Upper terminal
29. Lower terminal
30. Interrupter
40. Lower interrupter support
48. Insulating operating rod
50. Hand crank for circuit-breaker 3AX1530-2B
(optional)
50.1 Opening for hand crank for charging the clos-
ing spring
50.2 Gear unit
50.4 Motor M1
50.4.1 Position switch
50.5 Hand crank coupling
50.6 Hand crank adapter
51. Rating plate
51.1 Opening for rating plate
53. CLOSE pushbutton
53.1 Closing solenoid Y9
54. OPEN pu sh bu tt on
54.1 Shunt release Y1
54.2 Shunt release Y2
54.3 Transformer-operated release Y4
54.4 Undervoltage release Y7
54.5 Transformer-operated release (0.1 Ws) Y6
55. Spring state indicator
55.1 Opening for spring state indicator
58. Operating cycle counter
58.1 Opening for operating cycle counter
59. Position indicator CLOSED-OPEN
59.1 Opening for position indicator CLOSED-OPEN
60. Mechanism box
60.1 Cover
60.3 Transportation eye
61. Dashpot
62. Closing spring
63. Ci rcu it- br ea ke r sh aft
64. Opening spring
66. Closing damper
68. Auxiliary switch S1 (6NO+6NC)
68.0.1 Extended auxiliary switch S1 (12NO + 12NC)
68.1 Operating rod (for auxiliary switch S1)
68.7 Automatically coupling low-voltage plug
69. Contactor relay K1
70. Earth terminal
71. Heater R01 (condensation water protection)
72. Spring charge release
72.1 Lever of the spring charge release
80. Withdrawabl e part
81. Locking bracket
84. Mounting rail
87. Coding
90. Cartridge insert
93. Locking pin
95. Unlocking lever of the cartridge insert
96. Actuating opening for manually operating the
earthing switch (optional)
97. Position indicator of the earthing switch
(optional)
98. Actuating opening for manually operating the
withdrawable part
99. Indication of the operating and disconnected
position of the withdrawable part
102. Locking magnet Y8 (optional)
103. Locking magnet Y10 (optional)
106. Operating tool for the earthing switch (manual
operation) 3AX1531-3C (optional)
107. Operating tool for the earthing switch (motor
operation) 3AX1531-3D (optional)
108. Traversing crank with hand screen for discon-
necting component 3AX 1531-4B (optional)
109. Coupling of the earthing switch drive
Published by
Siemens AG
Infrastructure & Cities Sector
Low and Medium Voltage Division
Medium Voltage & Systems
Schaltwerk Berlin
Nonnendammallee 104
13629 Berlin