CJ-series Output Units CJ1W-OC/OA/OD CSM_CJ1W-OUTPUT_DS_E_8_1 A Wide Range of Basic Output Units for High Speed Output and Different Applications * These Output Units receive the results of output instructions from the CPU Unit and perform ON/OFF control for external devices. * High-speed Output models CJ1W-OD213 and CJ1W-OD234 can help to increase system throughput. CJ1W-OD213 CJ1W-OD234 Features * High-speed output models are available, meeting versatile applications. ON Response Time: 15s, OFF Response Time: 80s * Output Units are available with any of three output types: relay contact outputs, triac outputs, or transistor outputs. * For transistor outputs, select from sinking outputs or sourcing outputs. * Output Units with load short-circuit protection are also available. *1 * Select the best interface for each application: Fujitsu connectors or MIL connectors. *2 * A wide variety of Connector-Terminal Block Conversion Units are available to allow you to easily wire external output devices. *1. The following Units have load short-circuit protection: CJ1W-OC202, CJ1W-OD204, CJ1W-OD212, and CJ1W-OD232. *2. Available for models with 32 outputs or 64 outputs 1 CJ1W-OC/OA/OD Ordering Information International Standards * The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives. * Contact your OMRON representative for further details and applicable conditions for these standards. Output Units Unit type Product name Specifications Current consumption No. of (A) words allocated 5V 24 V Model Output type I/O points Maximum switching capacity Commons External connection - 8 outputs 250 VAC/24 VDC, 2 A Independen t contacts Removable terminal block 1 words 0.09 0.048 max. CJ1W-OC201 - 16 outputs 250 VAC/24 VDC, 2 A 16 points, 1 common Removable terminal block 1 words 0.11 0.096 max. CJ1W-OC211 - 8 outputs 250 VAC, 0.6 A 8 points, 1 common Removable terminal block 1 words 0.22 - CJ1W-OA201 Sinking 8 outputs 12 to 24 VDC, 2 A 4 points, 1 common Removable terminal block 1 words 0.09 - CJ1W-OD201 Sinking 8 outputs 12 to 24 VDC, 0.5 A 8 points, 1 common Removable terminal block 1 words 0.10 - CJ1W-OD203 Sinking 16 outputs 12 to 24 VDC, 0.5 A 16 points, 1 common Removable terminal block 1 words 0.10 - CJ1W-OD211 Transistor Sinking Output Units 16 outputs (High speed) 24 VDC, 0.5 A 16 points, 1 common Removable terminal block 1 words 0.15 - CJ1W-OD213 Sinking 32 outputs 12 to 24 VDC, 0.5 A 16 points, 1 common Fujitsu connector 2 words 0.14 - CJ1W-OD231 Sinking 32 outputs 12 to 24 VDC, 0.5 A 16 points, 1 common MIL connector 2 words 0.14 - CJ1W-OD233 Sinking 32 outputs (High speed) 24 VDC, 0.5 A 16 points, 1 common MIL connector 2 words 0.22 - CJ1W-OD234 Sinking 64 outputs 12 to 24 VDC, 0.3 A 16 points, 1 common Fujitsu connector 4 words 0.17 - CJ1W-OD261 Sinking 64 outputs 12 to 24 VDC, 0.3 A 16 points, 1 common MIL connector 4 words 0.17 - CJ1W-OD263 Sourcing 8 outputs 24 VDC, 2 A 4 points, Short-circuit protection 1 common Removable terminal block 1 words 0.11 - CJ1W-OD202 Sourcing 8 outputs 24 VDC, 0.5 A 8 points, Short-circuit protection 1 common Removable terminal block 1 words 0.10 - CJ1W-OD204 Sourcing 16 outputs 24 VDC, 0.5 A 16 points, Short-circuit protection 1 common Removable terminal block 1 words 0.10 - CJ1W-OD212 Sourcing 32 outputs 24 VDC, 0.5 A 16 points, Short-circuit protection 1 common MIL connector 2 words 0.15 - CJ1W-OD232 Sourcing 64 outputs 12 to 24 VDC, 0.3 A 16 points, 1 common MIL connector 4 words 0.17 - CJ1W-OD262 Relay Contact Output Units Standards Triac Output Unit CJ1 Basic I/O Units UC1, N, L, CE N, L, CE UC1, N, L, CE N, L, CE UC1, N, L, CE Accessories Connectors are not included for models with connectors. Either use one of the applicable connector listed below or use an applicable ConnectorTerminal Block Conversion Unit or I/O Relay Terminal. For details on wiring methods, refer to External Interface. 2 CJ1W-OC/OA/OD Applicable Connectors Fujitsu Connectors for 32-input, 32-output, 64-input, 64-output, 32-input/32-output, and 16-input/16-output Units Name 40-pin Connectors 24-pin Connectors Connection Remarks Applicable Units Soldered FCN-361J040-AU FCN-360C040-J2 Connector Connector Cover Crimped FCN-363J040 FCN-363J-AU FCN-360C040-J2 Housing Contactor Connector Cover Pressure welded FCN-367J040-AU/F Soldered FCN-361J024-AU FCN-360C024-J2 Connector Connector Cover Crimped FCN-363J024 FCN-363J-AU FCN-360C024-J2 Socket Contactor Connector Cover Pressure welded FCN-367J024-AU/F Model Fujitsu Connectors: CJ1W-ID231(32 inputs): 1 per Unit CJ1W-ID261 (64 inputs): 2 per Unit CJ1W-OD231 (32 outputs): 1 per Unit CJ1W-OD261 (64 outputs): 2 per Unit CJ1W-MD261 (32 inputs, 32 outputs): 2 per Unit Standards C500-CE404 C500-CE405 C500-CE403 - C500-CE241 Fujitsu Connectors: CJ1W-MD231 (16 inputs, 16 outputs): 2 per Unit C500-CE242 C500-CE243 MIL Connectors for 32-input, 32-output, 64-input, 64-output, 32-input/32-output, and 16-input/16-output Units Name Connection Pressure welded Remarks FRC5-AO40-3TOS 40-pin Connectors - Crimped 20-pin Connectors Pressure welded FRC5-AO20-3TOS - Crimped Applicable Units Model MIL Connectors: CJ1W-ID232/233 (32 inputs): 1 per Unit CJ1W-OD232/233/234 (32 outputs):1 per Unit CJ1W-ID262 (64 inputs): 2 per Unit CJ1W-OD262/263 (64 outputs): 2 per Unit CJ1W-MD263/563 (32 inputs, 32 outputs): 2 per Unit Standards XG4M-4030-T - XG5N-401* XG4M-2030-T MIL Connectors: CJ1W-MD232/233 (16 inputs, 16 outputs): 2 per Unit XG5N-201* - * Crimp Contacts are also required. Refer to page 31 for details. Applicable Connector-Terminal Block Conversion Units Type Series I/O Number Wiring method of poles Terminal type Size Mounting Common Bleeder Indicators Depth Height Width DIN Screws terminals resistance (mm) (mm) (mm) Track Model Standards CJ1W-OD231 XW2R-J34G-C3 CJ1W-OD261 Phillips screw M3 50 CJ1W-OD232 CJ1W-OD233 CJ1W-OD234 XW2R-J34G-C4 CJ1W-OD262 CJ1W-OD263 48.35 130.7 CJ1W-OD231 XW2R-E34G-C3 CJ1W-OD261 Slotted screw (rise up) M3 (European 50 type) PLCs XW2R Output 34 I/O Units 45.11 98.5 Yes Yes No No No CJ1W-OD232 CJ1W-OD233 CJ1W-OD234 XW2R-E34G-C4 CJ1W-OD262 CJ1W-OD263 - CJ1W-OD231 XW2R-P34G-C3 CJ1W-OD261 Push-in spring Clamp 50 45.11 98.5 CJ1W-OD232 CJ1W-OD233 CJ1W-OD234 XW2R-P34G-C4 CJ1W-OD262 CJ1W-OD263 Note: For the combination of Output Units with Connector-Terminal Block Conversion Units, refer to 2. Connecting Connector-Terminal Block Conversion Units. 3 CJ1W-OC/OA/OD Applicable I/O Relay Terminals Size (horizontal mounting) Specifications Type Series Classification Polarity Relay outputs Vertical type G70D-V MOSFET NPN relay outputs Number of points Rated ON current at contacts 5A or 3A 16 (SPSTNO x 16) 0.3A Operation indicators Terminal block for Horizontal Vertical Height DIN Screws power (mm) (mm) (mm) Track supply wiring Yes Expandable 135 SpaceG70D saving Flat type G70D Highcapacity, G70R spacesaving Outputs Relay outputs PNP Outputs Inputs MOSFET NPN relay outputs PNP 16 0.3A (SPSTNO x 16) Relay outputs NPN 8 (SPST10A NO x 8) NPN 16 1A (SPSTNO x 16) AC inputs DC inputs 8 (SPSTNO x 8) Standard G7TC NPN Outputs Relay outputs PNP NPN Highcapacity socket G70A (Socket only) Relay Outputs outputs PNP 46 81 Yes Yes G70D-VFOM16 68 93 44 G70D-SOC08 16 3A (SPSTNO x 16) 16 (SPST3A NO x 16) Standrads U, C, CE - G70D-SOC16 Yes - - Yes 156 51 Yes 39 G70D-SOC16-1 G70D-FOM16 - G70D-FOM16-1 Yes - 136 93 55 Yes Yes G70R-SOC08 - G7TC-IA16 182 G7TC-ID16 Yes - 16 (SPST5A NO x 16) 102 85 68 Yes - G7TC-OC08 G7TC-OC16 G7TC-OC16-1 10 A (Terminal block No allowable current) U, C 182 16 (SPSTNO x 16) 16 (SPDT x 16 possible with G2R Relays) Model G70D-VSOC16 8 (SPST5A NO x 8) NPN Mounting - 234 75 64 Yes - - G70A-ZOC16-3 (Socket only) + Relay/SSR/ MOSFET Relay/ Timer U, C, G70A-ZOC16-4 CE (Socket only) + Relay/SSR/ MOSFET Relay/ Timer Note: For the combination of Output Units with I/O Relay Terminal and Connecting Cables, refer to 3. Connecting I/O Relay Terminals. 4 CJ1W-OC/OA/OD Mountable Racks NJ system Model CJ system (CJ1, CJ2) CPU Rack Expansion Rack CPU Rack Expansion Backplane 10 Units 10 Units (Per Expansion Rack) 10 Units 10 Units (Per Expansion Backplane) CP1H system NSJ system CP1H PLC NSJ Controller Expansion Backplane Not Supported Not Supported 10 Units (Per Expansion Backplane) CJ1W-OC201 CJ1W-OC211 CJ1W-OA201 CJ1W-OD201 CJ1W-OD203 CJ1W-OD211 CJ1W-OD213 CJ1W-OD231 CJ1W-OD233 CJ1W-OD234 CJ1W-OD261 CJ1W-OD263 CJ1W-OD202 CJ1W-OD204 CJ1W-OD212 CJ1W-OD232 CJ1W-OD262 5 CJ1W-OC/OA/OD Specifications CJ1W-OC201 Contact Output Unit (Independent Relays, 8 Points) Name 8-point Contact Output Unit with Terminal Block (Independent Relays) Model CJ1W-OC201 Max. Switching Capacity 2 A 250 VAC (cos = 1), 2 A 250 VAC (cos = 0.4), 2 A 24 VDC (16 A/Unit) Min. Switching Capacity 1 mA 5 VDC Relays NY-24W-K-IE (Fujitsu Takamizawa Components, Ltd.), Cannot be replaced. Service Life of Relay Electrical: 150,000 operations (24 VDC, resistive load)/100,000 operations (240 VAC, cos = 0.4, inductive load) Mechanical: 20,000,000 operations Service life will vary depending on the connected load. ON Response Time 15 ms max. OFF Response Time 15 ms max. Number of Circuits 8 independent contacts Insulation Resistance 20 M between external terminals and the GR terminal (500 VDC) Dielectric Strength 2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Internal Current Consumption 90 mA 5 VDC max. 48 mA 24 VDC max. (6 mA x No. of ON points) Weight 140 g max. Signal name Circuit Configuration Internal circuits Jxx_Ch1_Out00 Jxx_Ch1_Out00 Output indicator * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. Connector pin * Signal name Jxx_Ch1_Out00 Jxx_Ch1_Out01 Jxx_Ch1_Out02 Jxx_Ch1_Out03 Jxx_Ch1_Out04 Jxx_Ch1_Out05 External connection and terminal-device variable diagram Jxx_Ch1_Out06 Jxx_Ch1_Out07 NC A0 A1 A2 B0 Jxx_Ch1_Out00 L B1 Jxx_Ch1_Out01 L B2 Jxx_Ch1_Out02 L Jxx_Ch1_Out03 L B4 Jxx_Ch1_Out04 L Jxx_Ch1_Out05 L B6 Jxx_Ch1_Out06 L B7 Jxx_Ch1_Out07 L A3 B3 A4 A5 B5 A6 A7 A8 B8 2A 2A Signal name NC 250 VAC, 24 VDC max. * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. * The input power supply polarity can be connected in either direction. * Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on the Units. Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. 6 CJ1W-OC/OA/OD CJ1W-OC211 Contact Output Unit (16 Points) Name 16-point Contact Output Unit with Terminal Block Model CJ1W-OC211 Max. Switching Capacity 2 A 250 VAC (cos = 1), 2 A 250 VAC (cos = 0.4), 2 A 24 VDC (8 A/Unit) Min. Switching Capacity 1 mA 5 VDC Relays NY-24W-K-IE (Fujitsu Takamizawa Components, Ltd.), Cannot be replaced. Service Life of Relay Electrical: 150,000 operations (24 VDC, resistive load)/ 100,000 operations (250 VAC, cos = 0.4, inductive load) Mechanical: 20,000,000 operations Service life will vary depending on the connected load. ON Response Time 15 ms max. OFF Response Time 15 ms max. Number of Circuits 16 points/common, 1 circuit Insulation Resistance 20 M between external terminals and the GR terminal (500 VDC) Dielectric Strength 2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Internal Current Consumption 110 mA 5 VDC max. 96 mA 24 VDC max. (6 mA x No. of ON points) Weight 170 g max. Signal name Jxx_Ch1_Out00 to Circuit Configuration Internal circuits Jxx_Ch1_Out15 COM COM Output indicator * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. Connector pin * Signal name External connection and terminal-device variable diagram L Jxx_Ch1_Out00 A0 L Jxx_Ch1_Out02 A1 L Jxx_Ch1_Out04 L Jxx_Ch1_Out06 L Jxx_Ch1_Out08 L L L 2A 2A 250 VAC, 24 VDC max. Jxx_Ch1_Out10 Jxx_Ch1_Out12 Jxx_Ch1_Out14 COM B0 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 Signal name Jxx_Ch1_Out01 L Jxx_Ch1_Out03 L Jxx_Ch1_Out05 L Jxx_Ch1_Out07 L Jxx_Ch1_Out09 L Jxx_Ch1_Out11 L Jxx_Ch1_Out13 L Jxx_Ch1_Out15 L COM * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. * Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on the Units. 7 CJ1W-OC/OA/OD CJ1W-OA201 Triac Output Unit (8 Points) Name 8-point Triac Output Unit with Terminal Block Model CJ1W-OA201 Max. Switching Capacity 0.6 A 250 VAC, 50/60 Hz (2.4 A/Unit) Max. Inrush Current 15 A (pulse width: 10 ms max.) Min. Switching Capacity 50 mA 75 VAC Leakage Current 1.5 mA (200 VAC) max. Residual Voltage 1.6 VAC max. ON Response Time 1 ms max. OFF Response Time 1/2 of load frequency + 1 ms or less. Number of Circuits 8 (8 points/common, 1 circuit) Surge Protector C.R Absorber + Surge Absorber Fuses 5 A (1/common, 1 used) The fuse cannot be replaced by the user. Insulation Resistance 20 M between the external terminals and the GR terminal (500 VDC) Dielectric Strength 2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Internal Current Consumption 220 mA max. Weight 150 g max. Signal name Internal circuits Output indicator Circuit Configuration Jxx_Ch1_Out00 to Jxx_Ch1_Out07 COM Fuse * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. Signal name Connector pin * NC A0 B0 NC A1 Jxx_Ch1_Out00 L Jxx_Ch1_Out01 L Jxx_Ch1_Out02 L Jxx_Ch1_Out03 L B1 NC A2 B2 External connection and terminal-device variable diagram NC A3 NC A4 B3 Jxx_Ch1_Out04 B4 NC A5 Jxx_Ch1_Out05 L Jxx_Ch1_Out06 L Jxx_Ch1_Out07 L B5 NC A6 B6 NC A7 B7 NC A8 L 250 VAC max. COM B8 * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. * Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on the Units. Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. 8 CJ1W-OC/OA/OD CJ1W-OD201 Transistor Output Unit (8 Points) Name 8-point Transistor Output Unit with Terminal Block (Sinking Outputs) Model CJ1W-OD201 Rated Voltage 12 to 24 VDC Operating Load Voltage Range 10.2 to 26.4 VDC Maximum Load Current 2.0 A/point, 8.0 A/Unit Maximum Inrush Current 10 A/point, 10 ms max. Leakage Current 0.1 mA max. Residual Voltage 1.5 V max. ON Response Time 0.5 ms max. OFF Response Time 1.0 ms max. Insulation Resistance 20 M between the external terminals and the GR terminal (100 VDC) Dielectric Strength 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Number of Circuits 8 (4 points/common, 2 circuits) Internal Current Consumption 90 mA max. Fuse 6.3 A (1/common, 2 used) The fuse cannot be replaced by the user. External Power Supply 12 to 24 VDC, 10 mA min. Weight 110 g max. Signal name +V Jxx_Ch1_Out00 to Circuit Configuration Internal circuits Jxx_Ch1_Out03 Fuse COM0 Output indicator +V Jxx_Ch1_Out04 to Jxx_Ch1_Out07 Fuse COM1 * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. Connector pin * Signal name L L Jxx_Ch1_Out00 A0 B0 Jxx_Ch1_Out02 A1 B1 NC 12 to 24 VDC A2 B2 COM0 A3 B3 NC External connection and terminal-device variable diagram A4 B4 L Jxx_Ch1_Out04 L Jxx_Ch1_Out06 A5 B5 A6 B6 NC 12 to 24 VDC COM1 A7 B7 A8 B8 Signal name Jxx_Ch1_Out01 L Jxx_Ch1_Out03 L NC +V NC Jxx_Ch1_Out05 L Jxx_Ch1_Out07 L NC +V * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. * Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on the Units. Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. 9 CJ1W-OC/OA/OD CJ1W-OD203 Transistor Output Unit (8 Points) Name 8-point Transistor Output Unit with Terminal Block (Sinking Outputs) Model CJ1W-OD203 Rated Voltage 12 to 24 VDC Operating Load Voltage Range 10.2 to 26.4 VDC Maximum Load Current 0.5 A/point, 4.0 A/Unit Maximum Inrush Current 4.0 A/point, 10 ms max. Leakage Current 0.1 mA max. Residual Voltage 1.5 V max. ON Response Time 0.1 ms max. OFF Response Time 0.8 ms max. Insulation Resistance 20 M between the external terminals and the GR terminal (100 VDC) Dielectric Strength 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Number of Circuits 8 (8 points/common, 1 circuit) Internal Current Consumption 100 mA max. Fuse None External Power Supply 10.2 to 26.4 VDC, 20 mA min. Weight 110 g max. Signal name Circuit Configuration Internal circuits Output indicator +V Jxx_Ch1_Out00 to Jxx_Ch1_Out07 COM * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. Signal name External connection and terminal-device variable diagram Connector pin * L Jxx_Ch1_Out00 A0 L Jxx_Ch1_Out02 A1 L Jxx_Ch1_Out04 A2 L Jxx_Ch1_Out06 A3 NC A4 NC A5 NC A6 NC 12 to 24 VDC A7 COM A8 B0 B1 B2 B3 B4 B5 B6 B7 B8 Signal name Jxx_Ch1_Out01 L Jxx_Ch1_Out03 L Jxx_Ch1_Out05 L Jxx_Ch1_Out07 L NC NC NC NC +V * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. * Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on the Units. Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. 10 CJ1W-OC/OA/OD CJ1W-OD211 Transistor Output Unit (16 Points) Name 16-point Transistor Output Unit with Terminal Block (Sinking Outputs) Model CJ1W-OD211 Rated Voltage 12 to 24 VDC Operating Load Voltage Range 10.2 to 26.4 VDC Maximum Load Current 0.5 A/point, 5.0 A/Unit Maximum Inrush Current 4.0 A/point, 10 ms max. Leakage Current 0.1 mA max. Residual Voltage 1.5 V max. ON Response Time 0.1 ms max. OFF Response Time 0.8 ms max. Insulation Resistance 20 M between the external terminals and the GR terminal (100 VDC) Dielectric Strength 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Number of Circuits 16 (16 points/common, 1 circuit) Internal Current Consumption 5 VDC 100 mA max. Fuse None External Power Supply 10.2 to 26.4 VDC, 20 mA min. Weight 110 g max. Circuit Configuration Internal circuits Signal name Output indicator +V Jxx_Ch1_Out00 to Jxx_Ch1_Out15 COM * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. Connector pin * Signal name L L L External connection and terminal-device variable diagram Jxx_Ch1_Out00 Jxx_Ch1_Out02 Jxx_Ch1_Out04 L Jxx_Ch1_Out06 L Jxx_Ch1_Out08 L Jxx_Ch1_Out10 L Jxx_Ch1_Out12 L Jxx_Ch1_Out14 COM 12 to 24 VDC A0 B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 Signal name Jxx_Ch1_Out01 Jxx_Ch1_Out03 Jxx_Ch1_Out05 Jxx_Ch1_Out07 Jxx_Ch1_Out09 Jxx_Ch1_Out11 Jxx_Ch1_Out13 Jxx_Ch1_Out15 L L L L L L L L +V * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. * Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on the Units. 11 CJ1W-OC/OA/OD CJ1W-OD213 Transistor Output Unit (16 Points) Name 16-point Transistor Output Unit with Terminal Block (Sinking Outputs) Model CJ1W-OD213 Rated Voltage 24 VDC Operating Load Voltage Range 20.4 to 26.4 VDC Maximum Load Current 0.5 A/point, 5.0 A/Unit Maximum Inrush Current 4.0 A/point, 10 ms max. Leakage Current 0.1 mA max. Residual Voltage 1.5 V max. ON Response Time 15 s max. OFF Response Time 80 s max. Insulation Resistance 20 M between the external terminals and the GR terminal (100 VDC) Dielectric Strength 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Number of Circuits 16 (16 points/common, 1 circuit) Internal Current Consumption 5 VDC 150 mA max. Fuse None External Power Supply 20.4 to 26.4 VDC, 55 mA min. Weight 110 g max. Signal name +V Jxx_Ch1_Out00 Internal circuits Circuit Configuration to Jxx_Ch1_Out15 COM Output indicator * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. Connector pin * Signal name L L L External connection and terminal-device variable diagram Jxx_Ch1_Out00 Jxx_Ch1_Out02 Jxx_Ch1_Out04 L Jxx_Ch1_Out06 L Jxx_Ch1_Out08 L Jxx_Ch1_Out10 L Jxx_Ch1_Out12 L Jxx_Ch1_Out14 COM 24 VDC A0 B0 A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 Signal name Jxx_Ch1_Out01 Jxx_Ch1_Out03 Jxx_Ch1_Out05 Jxx_Ch1_Out07 Jxx_Ch1_Out09 Jxx_Ch1_Out11 Jxx_Ch1_Out13 Jxx_Ch1_Out15 L L L L L L L L +V * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. * Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on the Units. 12 CJ1W-OC/OA/OD CJ1W-OD231 Transistor Output Unit (32 Points) Name Model Rated Voltage Operating Load Voltage Range Maximum Load Current Maximum Inrush Current Leakage Current Residual Voltage ON Response Time OFF Response Time Insulation Resistance Dielectric Strength Number of Circuits Internal Current Consumption Fuse External Power Supply Weight Accessories 32-point Transistor Output Unit with Fujitsu Connector (Sinking Outputs) CJ1W-OD231 12 to 24 VDC 10.2 to 26.4 VDC 0.5 A/point, 2.0 A/common, 4.0 A/Unit 4.0 A/point, 10 ms max. 0.1 mA max. 1.5 V max. 0.1 ms max. 0.8 ms max. 20 M between the external terminals and the GR terminal (100 VDC) 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. 32 (16 points/common, 2 circuits) 5 VDC 140 mA max. None 10.2 to 26.4 VDC, 30 mA min. 70 g max. None Signal name Allocated CIO word +V Jxx_Ch1_Out00 to Wd m Connector row A Wd m+1 Connector row B Internal circuits Jxx_Ch1_Out15 Circuit Configuration Output indicator COM0 COM0 SW +V Jxx_Ch2_Out00 to Jxx_Ch2_Out15 COM1 COM1 * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. Allocated CIO word Wd m External connection and terminal-device variable diagram Wd m * * * * * * 12 to 24 VDC ConnecSignal Signal tor pin name name L Jxx_Ch1_Out00 A1 B1 Jxx_Ch2_Out00 L Jxx_Ch1_Out01 Jxx_Ch2_Out01 A2 B2 L L L Jxx_Ch1_Out02 A3 B3 Jxx_Ch2_Out02 L L Jxx_Ch1_Out03 A4 B4 Jxx_Ch2_Out03 L L Jxx_Ch1_Out04 A5 B5 Jxx_Ch2_Out04 L L Jxx_Ch1_Out05 A6 B6 Jxx_Ch2_Out05 L Jxx_Ch2_Out06 Jxx_Ch1_Out06 L A7 B7 L Jxx_Ch2_Out07 Jxx_Ch1_Out07 L A8 B8 L COM1 COM0 A9 B9 +V +V A10 B10 Jxx_Ch1_Out08 Jxx_Ch2_Out08 L A11 B11 L Jxx_Ch1_Out09 Jxx_Ch2_Out09 A12 B12 L L L Jxx_Ch1_Out10 A13 B13 Jxx_Ch2_Out10 L L Jxx_Ch1_Out11 A14 B14 Jxx_Ch2_Out11 L Jxx_Ch1_Out12 Jxx_Ch2_Out12 L L A15 B15 Jxx_Ch2_Out13 Jxx_Ch1_Out13 L A16 B16 L Jxx_Ch2_Out14 Jxx_Ch1_Out14 L A17 B17 L L Jxx_Ch1_Out15 A18 B18 Jxx_Ch2_Out15 L COM1 COM0 A19 B19 +V +V A20 B20 Allocated CIO word 12 to 24 VDC Wd m+1 Wd m+1 When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. Be sure to wire both terminals A9 and A19 (COM0). Be sure to wire both terminals B9 and B19 (COM1). Be sure to wire both terminals A10 and A20 (+V). Be sure to wire both terminals B10 and B20 (+V). The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. 13 CJ1W-OC/OA/OD CJ1W-OD233 Transistor Output Unit (32 Points) Name Model Rated Voltage Operating Load Voltage Range Maximum Load Current Maximum Inrush Current Leakage Current Residual Voltage ON Response Time OFF Response Time Insulation Resistance Dielectric Strength Number of Circuits Internal Current Consumption Fuse External Power Supply Weight 32-point Transistor Output Unit with MIL Connector (Sinking Outputs) CJ1W-OD233 12 to 24 VDC 10.2 to 26.4 VDC 0.5 A/point, 2 A/common, 4 A/Unit 4.0 A/point, 10 ms max. 0.1 mA max. 1.5 V max. 0.1 ms max. 0.8 ms max. 20 M between the external terminals and the GR terminal (100 VDC) 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. 32 (16 points/common, 2 circuits) 140 mA max. None 12 to 24 VDC, 30 mA min. 70 g max. Signal name Allocated CIO word +V Internal circuits Jxx_Ch1_Out00 to Jxx_Ch1_Out15 Circuit Configuration Wd m COM0 COM0 Output indicator SW +V Jxx_Ch2_Out00 to Jxx_Ch2_Out15 Wd m+1 COM1 COM1 * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. Connector pin 12 to 24 VDC +V COM1 L L Wd m+1 L L L L L L Jxx_Ch2_Out15 Jxx_Ch2_Out14 Jxx_Ch2_Out13 Jxx_Ch2_Out12 Jxx_Ch2_Out11 Jxx_Ch2_Out10 Jxx_Ch2_Out09 Jxx_Ch2_Out08 +V COM0 External connection and terminal-device variable diagram L L Wd m L L L L 12 to 24 VDC * * * * * * L L Jxx_Ch1_Out15 Jxx_Ch1_Out14 Jxx_Ch1_Out13 Jxx_Ch1_Out12 Jxx_Ch1_Out11 Jxx_Ch1_Out10 Jxx_Ch1_Out09 Jxx_Ch1_Out08 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 Signal name Allocated CIO word +V COM1 Jxx_Ch2_Out07 Jxx_Ch2_Out06 Jxx_Ch2_Out05 Jxx_Ch2_Out04 Jxx_Ch2_Out03 Jxx_Ch2_Out02 Jxx_Ch2_Out01 Jxx_Ch2_Out00 L L L L L Wd m+1 Signal name L L L +V COM0 Jxx_Ch1_Out07 Jxx_Ch1_Out06 Jxx_Ch1_Out05 Jxx_Ch1_Out04 Jxx_Ch1_Out03 Jxx_Ch1_Out02 Jxx_Ch1_Out01 Jxx_Ch1_Out00 L L L L L Wd m Allocated CIO word L L L When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. Be sure to wire both terminals 23 and 24 (COM0). Be sure to wire both terminals 3 and 4 (COM1). Be sure to wire both terminals 21 and 22 (+V). Be sure to wire both terminals 1 and 2 (+V). The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. 14 CJ1W-OC/OA/OD CJ1W-OD234 Transistor Output Unit (32 Points) Name Model Rated Voltage Operating Load Voltage Range Maximum Load Current Maximum Inrush Current Leakage Current Residual Voltage ON Response Time OFF Response Time Insulation Resistance Dielectric Strength Number of Circuits Internal Current Consumption Fuse External Power Supply Weight 32-point Transistor Output Unit with MIL Connector (Sinking Outputs) CJ1W-OD234 24 VDC 20.4 to 26.4 VDC 0.5 A/point, 2 A/common, 4 A/Unit 4.0 A/point, 10 ms max. 0.1 mA max. 1.5 V max. 15 s max. 80 s max. 20 M between the external terminals and the GR terminal (100 VDC) 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. 32 (16 points/common, 2 circuits) 220 mA max. None 20.4 to 26.4 VDC, 110 mA min. 70 g max. Signal name +V Jxx_Ch1_Out00 Allocated CIO word Wd m to Jxx_Ch1_Out15 Internal circuits COM0 COM0 Circuit Configuration Output indicator SW +V Jxx_Ch2_Out00 Wd m+1 to Jxx_Ch2_Out15 COM1 COM1 * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. L L L L L L L L Jxx_Ch2_Out15 Jxx_Ch2_Out14 Jxx_Ch2_Out13 Jxx_Ch2_Out12 Jxx_Ch2_Out11 Jxx_Ch2_Out10 Jxx_Ch2_Out09 Jxx_Ch2_Out08 +V COM0 External connection and terminal-device variable diagram L L Wd m L L L L L 24 VDC * * * * * * L Jxx_Ch1_Out15 Jxx_Ch1_Out14 Jxx_Ch1_Out13 Jxx_Ch1_Out12 Jxx_Ch1_Out11 Jxx_Ch1_Out10 Jxx_Ch1_Out09 Jxx_Ch1_Out08 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 +V COM1 Jxx_Ch2_Out07 Jxx_Ch2_Out06 Jxx_Ch2_Out05 Jxx_Ch2_Out04 Jxx_Ch2_Out03 Jxx_Ch2_Out02 Jxx_Ch2_Out01 Jxx_Ch2_Out00 L L L L L Wd m+1 +V COM1 Allocated CIO word Signal name L L L +V COM0 Jxx_Ch1_Out07 Jxx_Ch1_Out06 Jxx_Ch1_Out05 Jxx_Ch1_Out04 Jxx_Ch1_Out03 Jxx_Ch1_Out02 Jxx_Ch1_Out01 Jxx_Ch1_Out00 L L L L L Wd m 24 VDC Wd m+1 Connector pin Signal name Allocated CIO word L L L When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. Be sure to wire both terminals 23 and 24 (COM0). Be sure to wire both terminals 3 and 4 (COM1). Be sure to wire both terminals 21 and 22 (+V). Be sure to wire both terminals 1 and 2 (+V). The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. 15 CJ1W-OC/OA/OD CJ1W-OD261 Transistor Output Unit (64 Points) Name 64-point Transistor Output Unit with Fujitsu Connectors (Sinking Outputs) Model CJ1W-OD261 Rated Voltage 12 to 24 VDC Operating Load Voltage Range 10.2 to 26.4 VDC Maximum Load Current 0.3 A/point, 1.6 A/common, 6.4 A/Unit Maximum Inrush Current 3.0 A/point, 10 ms max. Leakage Current 0.1 mA max. Residual Voltage 1.5 V max. ON Response Time 0.5 ms max. OFF Response Time 1.0 ms max. Insulation Resistance 20 M between the external terminals and the GR terminal (100 VDC) Dielectric Strength 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Number of Circuits 64 (16 points/common, 4 circuits) Internal Current Consumption 5 VDC, 170 mA max. Fuse None External Power Supply 10.2 to 26.4 VDC, 50 mA min. Weight 110 g max. Accessories None Signal name Allocated CIO word Circuit Configuration Internal circuits +V SW Output indicator Jxx_Ch1_Out00 to Jxx_Ch1_Out15 COM0 COM0 +V Jxx_Ch2_Out00 to Jxx_Ch2_Out15 COM1 COM1 +V Jxx_Ch3_Out00 to Jxx_Ch3_Out15 COM2 COM2 +V Jxx_Ch4_Out00 to Jxx_Ch4_Out15 COM3 COM3 Wd m Connector row A CN1 Wd m+1 Connector row B Connector row A Wd m+2 Connector row B CN2 Wd m+3 * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. 16 CJ1W-OC/OA/OD Jxx_Ch2_Out14 Wd m+1 L L B17 A17 Jxx_Ch2_Out12 L Jxx_Ch2_Out10 L Jxx_Ch2_Out09 Jxx_Ch2_Out08 +V External connection and terminal-device variable diagram COM1 L Jxx_Ch2_Out07 L Jxx_Ch2_Out06 L Jxx_Ch2_Out05 12 to 24 VDC L L L L L Jxx_Ch1_Out14 Jxx_Ch2_Out04 Jxx_Ch2_Out03 Jxx_Ch2_Out02 Jxx_Ch2_Out01 Jxx_Ch2_Out00 L L L L Jxx_Ch1_Out12 L B14 A14 12 to 24 VDC L L L L L Jxx_Ch1_Out11 Jxx_Ch2_Out11 L Jxx_Ch1_Out15 Jxx_Ch1_Out13 B15 A15 L COM0 B16 A16 Jxx_Ch2_Out13 L Wd m+1 B18 A18 L +V Wd m+2 L Jxx_Ch2_Out15 B19 A19 B13 A13 B12 A12 B11 A11 B10 A10 B9 A9 B8 A8 B7 A7 B6 A6 Jxx_Ch1_Out10 Jxx_Ch1_Out09 Jxx_Ch1_Out08 L L COM0 L L Jxx_Ch1_Out07 L Jxx_Ch1_Out06 L Jxx_Ch1_Out05 Jxx_Ch1_Out04 B4 A4 Jxx_Ch1_Out03 Jxx_Ch1_Out02 B2 A2 Jxx_Ch1_Out01 B1 A1 Jxx_Ch1_Out00 L Jxx_Ch3_Out01 Jxx_Ch3_Out02 Jxx_Ch3_Out03 Jxx_Ch3_Out04 Jxx_Ch3_Out05 Jxx_Ch3_Out06 Jxx_Ch3_Out07 +V L L Jxx_Ch3_Out00 COM2 L +V B5 A5 B3 A3 L L Wd m+2 COM1 L B20 A20 Connector pin Signal name Allocated CIO word Allocated CIO word Wd m +V Signal name 12 to 24 VDC L L L * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. * Be sure to wire both terminals A9 and A19 (COM0) of CN1. * Be sure to wire both terminals B9 and B19 (COM1) of CN1. * Be sure to wire both terminals A10 and A20 (+V) of CN1. * Be sure to wire both terminals B10 and B20 (+V) of CN1. * The signal names of the terminals are the device variable names.The device variable names are the names that use "Jxx" as the device name. L L L L L Jxx_Ch3_Out08 Jxx_Ch3_Out09 Jxx_Ch3_Out10 Jxx_Ch3_Out11 Jxx_Ch3_Out12 Jxx_Ch3_Out13 Jxx_Ch3_Out14 Jxx_Ch3_Out15 COM2 +V A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 A6 B6 A7 B7 A8 B8 A9 B9 A10 B10 A11 B11 A12 B12 A13 B13 A14 B14 A15 B15 A16 B16 A17 B17 A18 B18 A19 B19 A20 B20 Signal name Jxx_Ch4_Out00 Jxx_Ch4_Out01 Jxx_Ch4_Out02 Jxx_Ch4_Out03 Jxx_Ch4_Out04 Jxx_Ch4_Out05 Jxx_Ch4_Out06 Jxx_Ch4_Out07 Allocated CIO word L L L L L 12 to 24 VDC Wd m+3 Connector pin Signal name Wd m Allocated CIO word CN2 L L L COM3 +V Jxx_Ch4_Out08 Jxx_Ch4_Out09 Jxx_Ch4_Out10 Jxx_Ch4_Out11 Jxx_Ch4_Out12 Jxx_Ch4_Out13 Jxx_Ch4_Out14 Jxx_Ch4_Out15 L L L L L Wd m+3 CN1 L L L COM3 +V * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. * Be sure to wire both terminals A9 and A19 (COM2) of CN2. * Be sure to wire both terminals B9 and B19 (COM3) of CN2. * Be sure to wire both terminals A10 and A20 (+V) of CN2. * Be sure to wire both terminals B10 and B20 (+V) of CN2. * The signal names of the terminals are the device variable names.The device variable names are the names that use "Jxx" as the device name. 17 CJ1W-OC/OA/OD CJ1W-OD263 Transistor Output Unit (64 Points) Name 64-point Transistor Output Unit with MIL Connectors (Sinking Outputs) Model CJ1W-OD263 Rated Voltage 12 to 24 VDC Operating Load Voltage Range 10.2 to 26.4 VDC Maximum Load Current 0.3 A/point, 1.6 A/common, 6.4 A/Unit Maximum Inrush Current 3.0 A/point, 10 ms max. Leakage Current 0.1 mA max. Residual Voltage 1.5 V max. ON Response Time 0.5 ms max. OFF Response Time 1.0 ms max. Insulation Resistance 20 M between the external terminals and the GR terminal (100 VDC) Dielectric Strength 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Number of Circuits 64 (16 points/common, 4 circuits) Internal Current Consumption 170 mA max. Fuse None External Power Supply 12 to 24 VDC, 50 mA min. Weight 110 g max. Signal name Allocated CIO word Circuit Configuration Internal circuits +V SW Output indicator Jxx_Ch1_Out00 to Jxx_Ch1_Out15 COM0 COM0 +V Jxx_Ch2_Out00 to Jxx_Ch2_Out15 COM1 COM1 +V Jxx_Ch3_Out00 to Jxx_Ch3_Out15 COM2 COM2 +V Jxx_Ch4_Out00 to Jxx_Ch4_Out15 COM3 COM3 Wd m CN1 Wd m+1 Wd m+2 CN2 Wd m+3 * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. 18 CJ1W-OC/OA/OD Jxx_Ch1_Out01 L Jxx_Ch1_Out02 L Jxx_Ch1_Out03 L Jxx_Ch1_Out04 L Jxx_Ch1_Out05 L Jxx_Ch1_Out06 L Jxx_Ch1_Out07 COM0 External connection and terminal-device variable diagram Wd m+1 +V L Jxx_Ch2_Out00 L Jxx_Ch2_Out01 L Jxx_Ch2_Out02 L Jxx_Ch2_Out03 L Jxx_Ch2_Out04 L Jxx_Ch2_Out05 L Jxx_Ch2_Out06 L Jxx_Ch2_Out07 COM1 +V 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 Jxx_Ch1_Out08 Jxx_Ch1_Out09 Jxx_Ch1_Out10 Jxx_Ch1_Out11 Jxx_Ch1_Out12 Jxx_Ch1_Out13 Jxx_Ch1_Out14 Jxx_Ch1_Out15 L L L 12 to 24 VDC L L L L L L L L L L L COM0 L +V L 20 19 Jxx_Ch2_Out08 L 18 17 Jxx_Ch2_Out09 L 16 15 Jxx_Ch2_Out10 L 14 13 Jxx_Ch2_Out11 L 12 11 Jxx_Ch2_Out12 L 10 9 Jxx_Ch2_Out13 L 8 7 Jxx_Ch2_Out14 L 6 5 Jxx_Ch2_Out15 L 4 3 2 1 Jxx_Ch4_Out15 Jxx_Ch4_Out14 Jxx_Ch4_Out13 Jxx_Ch4_Out12 Jxx_Ch4_Out11 Jxx_Ch4_Out10 Jxx_Ch4_Out09 Jxx_Ch4_Out08 +V 1 2 3 4 5 6 7 8 Signal name Allocated CIO word +V COM3 9 10 11 12 13 14 15 16 17 18 19 20 21 22 COM2 Jxx_Ch4_Out07 Jxx_Ch4_Out06 Jxx_Ch4_Out05 Jxx_Ch4_Out04 Jxx_Ch4_Out03 Jxx_Ch4_Out02 Jxx_Ch4_Out01 Jxx_Ch4_Out00 L L L L L L L L +V COM2 23 24 Jxx_Ch3_Out15 L L Jxx_Ch3_Out14 Jxx_Ch3_Out13 L Jxx_Ch3_Out12 L L Jxx_Ch3_Out11 Jxx_Ch3_Out10 L COM1 +V +V COM3 Wd m+3 Jxx_Ch1_Out00 L Connector pin Signal name Allocated CIO word 12 to 24 VDC Wd m+2 L Allocated CIO word Signal name 12 to 24 VDC * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. * Be sure to wire both terminals 23 and 24 (COM0) of CN1. * Be sure to wire both terminals 3 and 4 (COM1) of CN1. * Be sure to wire both terminals 21 and 22 (+V) of CN1. * Be sure to wire both terminals 1 and 2 (+V) of CN1. * The signal names of the terminals are the device variable names.The device variable names are the names that use "Jxx" as the device name. 12 to 24 VDC Jxx_Ch3_Out09 L L Jxx_Ch3_Out07 25 26 L Jxx_Ch3_Out06 L 27 28 Jxx_Ch3_Out05 L 29 30 Jxx_Ch3_Out04 L 31 32 Jxx_Ch3_Out03 L 33 34 Wd m+2 Connector pin Wd m Signal name Wd m+1 Wd m Allocated CIO word CN2 Wd m+3 CN1 Jxx_Ch3_Out02 35 36 L Jxx_Ch3_Out01 L 37 38 Jxx_Ch3_Out00 Jxx_Ch3_Out08 39 40 L * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. * Be sure to wire both terminals 23 and 24 (COM2) of CN2. * Be sure to wire both terminals 3 and 4 (COM3) of CN2. * Be sure to wire both terminals 21 and 22 (+V) of CN2. * Be sure to wire both terminals 1 and 2 (+V) of CN2. * The signal names of the terminals are the device variable names.The device variable names are the names that use "Jxx" as the device name. 19 CJ1W-OC/OA/OD CJ1W-OD202 Transistor Output Unit (8 Points) Name 8-point Transistor Output Unit with Terminal Block (Sourcing Outputs) Model CJ1W-OD202 Rated Voltage 24 VDC Operating Load Voltage Range 20.4 to 26.4 VDC Maximum Load Current 2 A/point, 8 A/Unit Leakage Current 0.1 mA max. Residual Voltage 1.5 V max. ON Response Time 0.5 ms max. OFF Response Time 1.0 ms max. Load Short-circuit Protection Detection current: 6 A min. Automatic restart after error clearance. Line Disconnection Detection Detection current: 200 mA Insulation Resistance 20 M between the external terminals and the GR terminal (100 VDC) Dielectric Strength 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Number of Circuits 8 (4 points/common, 2 circuits) Internal Current Consumption 110 mA max. Fuse None External Power Supply 24 VDC, 50 mA min. Weight 120 g max. Signal name Jxx_Ch1_Out00 to Jxx_Ch1_Out03 0V Output indicator COM1 (+V) Short-circuit protection Circuit Configuration Internal circuits Short-circuit protection COM0 (+V) Jxx_Ch1_Out04 to Jxx_Ch1_Out07 0V ERR indicator * When overcurrent or line disconnection is detected, the ERR indicator will light, and the corresponding bit (two points per bit) in the Basic I/O Unit Information Area (A050 to A069) will change to TRUE. * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. Signal name L L Jxx_Ch1_Out00 Jxx_Ch1_Out02 NC 0V NC External connection and terminal-device variable diagram L L Signal name Connector pin * Jxx_Ch1_Out04 Jxx_Ch1_Out06 NC 0V A0 A1 A2 A3 A4 A5 A6 A7 A8 B0 B1 B2 B3 B4 B5 B6 B7 B8 Jxx_Ch1_Out01 Jxx_Ch1_Out03 L L NC 24 VDC COM0 (+V) NC Jxx_Ch1_Out05 Jxx_Ch1_Out07 L L NC 24 VDC COM1 (+V) * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. * Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on the Units. Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. 20 CJ1W-OC/OA/OD CJ1W-OD204 Transistor Output Unit (8 Points) Name 8-point Transistor Output Unit with Terminal Block (Sourcing Outputs) Model CJ1W-OD204 Rated Voltage 24 VDC Operating Load Voltage Range 20.4 to 26.4 VDC Maximum Load Current 0.5 A/point, 4.0 A/Unit Leakage Current 0.1 mA max. Residual Voltage 1.5 V max. ON Response Time 0.5 ms max. OFF Response Time 1.0 ms max. Load Short-circuit Protection Detection current: 0.7 to 2.5 A Automatic restart after error clearance. Insulation Resistance 20 M between the external terminals and the GR terminal (100 VDC) Dielectric Strength 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Number of Circuits 8 (8 points/common, 1 circuit) Internal Current Consumption 5 VDC, 100 mA max. Fuse None External Power Supply 20.4 to 26.4 VDC, 40 mA min. Weight 120 g max. Signal name Circuit Configuration Short-circuit protection Internal circuits COM (+V) Jxx_Ch1_Out00 to Jxx_Ch1_Out07 0V Output indicator ERR indicator * When overcurrent is detected, the ERR indicator will light, and the corresponding bit in the Basic I/O Unit Information Area (A050 to A069) will change to TRUE. * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. Signal name External connection and terminal-device variable diagram Signal name Connector pin * L Jxx_Ch1_Out00 A0 L Jxx_Ch1_Out02 A1 L Jxx_Ch1_Out04 A2 L Jxx_Ch1_Out06 A3 NC A4 NC A5 NC A6 NC A7 0V A8 B0 B1 B2 B3 B4 B5 B6 B7 B8 Jxx_Ch1_Out01 L Jxx_Ch1_Out03 L Jxx_Ch1_Out05 L Jxx_Ch1_Out07 L NC NC NC NC COM (+V) 24 VDC * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. * Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on the Units. Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O. 21 CJ1W-OC/OA/OD CJ1W-OD212 Transistor Output Unit (16 Points) Name 16-point Transistor Output Unit with Terminal Block (Sourcing Outputs) Model CJ1W-OD212 Rated Voltage 24 VDC Operating Load Voltage Range 20.4 to 26.4 VDC Maximum Load Current 0.5 A/point, 5.0 A/Unit Maximum Inrush Current 0.1 mA max. Leakage Current 1.5 V max. ON Response Time 0.5 ms max. OFF Response Time 1.0 ms max. Load Short-circuit Protection Detection current: 0.7 to 2.5 A Automatic restart after error clearance. Insulation Resistance 20 M between the external terminals and the GR terminal (100 VDC) Dielectric Strength 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Number of Circuits 16 (16 points/common, 1 circuit) Internal Current Consumption 5 VDC, 100 mA max. External Power Supply 20.4 to 26.4 VDC, 40 mA min. Weight 120 g max. Signal name Internal circuits Circuit Configuration Short-circuit protection COM (+V) Jxx_Ch1_Out00 to Jxx_Ch1_Out15 0V Output indicator ERR indicator * When overcurrent is detected, the ERR indicator will light, and the corresponding bit in the Basic I/O Unit Information Area (A050 to A069) will change to TRUE. * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. Connector pin * Signal name L L L L External connection and terminal-device variable diagram L L L L Jxx_Ch1_Out00 Jxx_Ch1_Out02 Jxx_Ch1_Out04 Jxx_Ch1_Out06 Jxx_Ch1_Out08 Jxx_Ch1_Out10 Jxx_Ch1_Out12 Jxx_Ch1_Out14 0V A0 A1 A2 A3 A4 A5 A6 A7 A8 B0 B1 B2 B3 B4 B5 B6 B7 B8 Signal name Jxx_Ch1_Out01 Jxx_Ch1_Out03 Jxx_Ch1_Out05 Jxx_Ch1_Out07 Jxx_Ch1_Out09 Jxx_Ch1_Out11 Jxx_Ch1_Out13 Jxx_Ch1_Out15 L L L L L L L L COM (+V) 24 VDC * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. * Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on the Units. 22 CJ1W-OC/OA/OD CJ1W-OD232 Transistor Output Unit (32 Points) Name 32-point Transistor Output Unit with MIL Connector (Sourcing Outputs) Model CJ1W-OD232 Rated Voltage 24 VDC Operating Load Voltage Range 20.4 to 26.4 VDC Maximum Load Current 0.5 A/point, 2.0 A/common, 4.0 A/Unit Leakage Current 0.1 mA max. Residual Voltage 1.5 V max. ON Response Time 0.5 ms max. OFF Response Time 1.0 ms max. Load Short-circuit Protection Detection current: 0.7 to 2.5 A Automatic restart after error clearance. Insulation Resistance 20 M between the external terminals and the GR terminal (100 VDC) Dielectric Strength 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Number of Circuits 32 (16 points/common, 2 circuits) Internal Current Consumption 5 VDC 150 mA max. External Power Supply 20.4 to 26.4 VDC, 70 mA min. Weight 80 g max. Accessories None Short-circuit protection Signal name COM0 (+V) COM0 (+V) Jxx_Ch1_Out00 to Jxx_Ch1_Out15 Allocated CIO word Wd m SW Output indicator Short-circuit protection Circuit Configuration Internal circuits 0V COM1 (+V) COM1 (+V) Jxx_Ch2_Out00 to Wd m+1 Jxx_Ch2_Out15 0V ERR indicator * When overcurrent is detected, the ERR indicator will light, and the corresponding bit (bit allocated for each common) in the Basic I/O Unit Information Area (A050 to A069) will change to TRUE. * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. 23 CJ1W-OC/OA/OD Connector pin 24 VDC COM1 (+V) 0V L Wd m+1 L Jxx_Ch2_Out15 Jxx_Ch2_Out14 L Jxx_Ch2_Out13 L Jxx_Ch2_Out12 L L L L Jxx_Ch2_Out11 Jxx_Ch2_Out10 Jxx_Ch2_Out09 Jxx_Ch2_Out08 COM0 (+V) 0V External connection and terminal-device variable diagram L L Wd m L L L L L L 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Allocated CIO word Signal name COM1 (+V) 0V Jxx_Ch2_Out07 Jxx_Ch2_Out06 L L Jxx_Ch2_Out05 L Jxx_Ch2_Out04 L Jxx_Ch2_Out03 Jxx_Ch2_Out02 Jxx_Ch2_Out01 Jxx_Ch2_Out00 L Wd m+1 Signal name L L L COM0 (+V) 0V Jxx_Ch1_Out15 25 26 Jxx_Ch1_Out07 Jxx_Ch1_Out14 27 28 Jxx_Ch1_Out06 Jxx_Ch1_Out13 29 30 Jxx_Ch1_Out05 Jxx_Ch1_Out12 31 32 Jxx_Ch1_Out04 Jxx_Ch1_Out11 33 34 Jxx_Ch1_Out03 Jxx_Ch1_Out10 35 36 Jxx_Ch1_Out02 Jxx_Ch1_Out09 37 38 Jxx_Ch1_Out01 Jxx_Ch1_Out08 39 40 Jxx_Ch1_Out00 L L L L L Wd m Allocated CIO word L L L 24 VDC * * * * * * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. Be sure to wire both terminals 21 and 22 (COM0 (+V)). Be sure to wire both terminals 1 and 2 (COM1 (+V)). Be sure to wire both terminals 3 and 4 (0 V). Be sure to wire both terminals 23 and 24 (0 V). The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. 24 CJ1W-OC/OA/OD CJ1W-OD262 Transistor Output Unit (64 Points) Name 64-point Transistor Output Unit with MIL Connectors (Sourcing Outputs) Model CJ1W-OD262 Rated Voltage 12 to 24 VDC Operating Load Voltage Range 10.2 to 26.4 VDC Maximum Load Current 0.3 A/point, 1.6 A/common, 6.4 A/Unit Maximum Inrush Current 3.0 A/point, 10 ms max. Leakage Current 0.1 mA max. Residual Voltage 1.5 V max. ON Response Time 0.5 ms max. OFF Response Time 1.0 ms max. Insulation Resistance 20 M between the external terminals and the GR terminal (100 VDC) Dielectric Strength 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max. Number of Circuits 64 (16 points/common, 4 circuits) Internal Current Consumption 170 mA max. (5 VDC) Fuse None External Power Supply 10.2 to 26.4 VDC, 50 mA min. Weight 110 g max. Accessories None Signal name Allocated CIO word COM0 COM0 Circuit Configuration Internal circuits Output indicator Indicator switch Jxx_Ch1_Out00 to Jxx_Ch1_Out15 0V COM1 COM1 Jxx_Ch2_Out00 to Jxx_Ch2_Out15 0V COM2 COM2 Jxx_Ch3_Out00 to Jxx_Ch3_Out15 0V COM3 COM3 Jxx_Ch4_Out00 to Jxx_Ch4_Out15 0V Wd m CN1 (OUT) Wd m+1 Wd m+2 CN2 (OUT) Wd m+3 * The signal names of the terminals are the device variable names. The device variable names are the names that use "Jxx" as the device name. 25 CJ1W-OC/OA/OD CN1 Jxx_Ch1_Out02 L L L L L Jxx_Ch1_Out03 Jxx_Ch1_Out04 Jxx_Ch1_Out05 Jxx_Ch1_Out06 Jxx_Ch1_Out07 0V COM0 (+V) L L Wd m+1 External connection and terminal-device variable diagram L L L L L L Jxx_Ch2_Out00 Jxx_Ch2_Out01 Jxx_Ch2_Out02 Jxx_Ch2_Out03 Jxx_Ch2_Out04 Jxx_Ch2_Out05 Jxx_Ch2_Out06 Jxx_Ch2_Out07 0V COM1 (+V) 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 L Jxx_Ch1_Out09 L Jxx_Ch1_Out10 L Jxx_Ch1_Out11 Jxx_Ch1_Out12 Jxx_Ch1_Out13 Jxx_Ch1_Out14 Jxx_Ch1_Out15 L L COM3 (+V) 0V L L L 0V COM0 (+V) Jxx_Ch2_Out08 Jxx_Ch2_Out09 Jxx_Ch2_Out10 Jxx_Ch2_Out11 Jxx_Ch2_Out12 Jxx_Ch2_Out13 Jxx_Ch2_Out14 Jxx_Ch2_Out15 L Jxx_Ch4_Out15 L Jxx_Ch4_Out14 L Jxx_Ch4_Out13 L Jxx_Ch4_Out12 L Jxx_Ch4_Out11 L Jxx_Ch4_Out10 L Jxx_Ch4_Out09 L Jxx_Ch4_Out08 COM2 (+V) L 0V L L L L Allocated CIO word L L L 0V COM1 (+V) 12 to 24 VDC * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. * Be sure to wire both terminals 21 and 22 (COM0 (+V)) of CN1. * Be sure to wire both terminals 1 and 2 (COM1 (+V)) of CN1. * Be sure to wire both terminals 23 and 24 (0 V) of CN1. * Be sure to wire both terminals 3 and 4 (0 V) of CN1. * The signal names of the terminals are the device variable names.The device variable names are the names that use "Jxx" as the device name. L Jxx_Ch3_Out15 L Jxx_Ch3_Out14 L Jxx_Ch3_Out13 L Jxx_Ch3_Out12 L Jxx_Ch3_Out11 L Jxx_Ch3_Out10 L Jxx_Ch3_Out09 L Jxx_Ch3_Out08 1 2 3 4 5 6 7 8 9 10 10 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 COM3 (+V) 0V Jxx_Ch4_Out07 L Jxx_Ch4_Out06 L Jxx_Ch4_Out05 L Jxx_Ch4_Out04 L Jxx_Ch4_Out03 L Jxx_Ch4_Out02 L Jxx_Ch4_Out01 L Jxx_Ch4_Out00 L Wd m+3 L 40 39 Signal name COM2 (+V) 0V Jxx_Ch3_Out07 L Jxx_Ch3_Out06 L Jxx_Ch3_Out05 L Jxx_Ch3_Out04 L Jxx_Ch3_Out03 L Jxx_Ch3_Out02 L Jxx_Ch3_Out01 L Jxx_Ch3_Out00 L Wd m+2 Jxx_Ch1_Out01 Connector pin 12 to 24 VDC 12 to 24 VDC Wd m+3 L Jxx_Ch1_Out08 Signal name Allocated CIO word Wd m+2 L Jxx_Ch1_Out00 Allocated CIO word Signal name Wd m Connector pin Signal name Wd m+1 Wd m Allocated CIO word CN2 12 to 24 VDC * When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed. * Be sure to wire both terminals 21 and 22 (COM2 (+V)) of CN2. * Be sure to wire both terminals 1 and 2 (COM3 (+V)) of CN2. * Be sure to wire both terminals 23 and 24 (0 V) of CN2. * Be sure to wire both terminals 3 and 4 (0 V) of CN2. * The signal names of the terminals are the device variable names.The device variable names are the names that use "Jxx" as the device name. 26 CJ1W-OC/OA/OD Bit Allocations for Output Unit 8-point Output Unit 16-point Output Unit Allocated CIO word CIO Bit Wd m (Output) Signal name (CJ/NJ) Wd m+1 (Output) Signal name (CJ/NJ) OUT0/Jxx_Ch1_Out00 00 OUT0/Jxx_Ch1_Out00 01 OUT1/Jxx_Ch1_Out01 01 OUT1/Jxx_Ch1_Out01 : : 06 Wd m (Output) : : OUT6/Jxx_Ch1_Out06 14 OUT14/Jxx_Ch1_Out14 07 OUT7/Jxx_Ch1_Out07 15 OUT15/Jxx_Ch1_Out15 08 - 09 - : : 14 - 15 - 64-point Output Unit Allocated CIO word Wd m (Output) Bit 00 32-point Output Unit CIO Allocated CIO word CIO Bit Signal name (CJ/NJ) Allocated CIO word CIO Bit Signal name (CJ/NJ) 00 OUT0/Jxx_Ch1_Out00 00 OUT0/Jxx_Ch1_Out00 01 OUT1/Jxx_Ch1_Out01 01 OUT1/Jxx_Ch1_Out01 : : 14 Wd m (Output) : : OUT14/Jxx_Ch1_Out14 14 OUT14/Jxx_Ch1_Out14 15 OUT15/Jxx_Ch1_Out15 15 OUT15/Jxx_Ch1_Out15 00 OUT0/Jxx_Ch2_Out00 00 OUT0/Jxx_Ch2_Out00 01 OUT1/Jxx_Ch2_Out01 01 OUT1/Jxx_Ch2_Out01 : : 14 15 Wd m+1 (Output) : : OUT14/Jxx_Ch2_Out14 14 OUT14/Jxx_Ch2_Out14 OUT15/Jxx_Ch2_Out15 15 OUT15/Jxx_Ch2_Out15 00 OUT0/Jxx_Ch3_Out00 01 OUT1/Jxx_Ch3_Out01 Wd m+2 (Output) Wd m+3 (Output) : : 14 OUT14/Jxx_Ch3_Out14 15 OUT15/Jxx_Ch3_Out15 00 OUT0/Jxx_Ch4_Out00 01 OUT1/Jxx_Ch4_Out01 : : 14 OUT14/Jxx_Ch4_Out14 15 OUT15/Jxx_Ch4_Out15 27 CJ1W-OC/OA/OD External Interface 8-point/16-point Units (18-point Terminal Blocks) Model number label I/O indicators Connector Connect to the connector on the next Unit. Terminal block for I/O wiring, 18P x 1 ERR 0 1 8 9 10 11 12 13 14 15 2 3 4 5 6 7 Note: The CJ1W-OD202, CJ1W-OD204, and CJ1W-OD212 also have an ERR indicator for the load short-circuit alarm. 32-point Units (Models with 40-point Fujitsu Connector or MIL Connector) Model number Indicator Switch ID231 1 ID232 I/O indicators 2 Changes the 16 I/O displayed on the I/O indicators. I/O wiring connector (40-pin x 1) Unit with Fujitsu-compatible Connector Word m or m+1 ERR 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Setting 1 Setting 2 MIL connector Fujitsu connector Bottom of connector Wd m (Row A on connector) Wd m+1 (Row B on connector) Top of connector Unit with MIL Connector Connector Connected to the connector on the next Unit. Note: Only the CJ1W-OD232 has an ERR indicator for the load short-circuit alarm. 28 CJ1W-OC/OA/OD 64-point Units (Models with Two 40-point Fujitsu Connectors or MIL Connector) Indicator Switch Model number 1 2 Changes the 32 I/O displayed on the I/O indicators. ID261 ID261 I/O indicators Setting 1 Setting 2 Wd m and m+1: CN1 Wd m+2 and m+3: CN2 I/O wiring connector (40-pin x 2) Unit with MIL Connector Unit with Fujitsu-compatible Connector Connector Connected to the connector on the next Unit. Word m or m+2 I Word m+1 or m+3 II 0 8 0 8 1 9 1 9 2 10 2 10 3 4 5 6 7 11 12 13 14 15 3 4 5 6 7 11 12 13 14 15 Wiring Basic I/O Units with Terminal Blocks Electric Wires The following wire gauges are recommended. Terminal Block Connector 18-terminal Wire Size AWG 22 to 18 (0.32 to 0.82 mm2) Crimp terminals Use crimp terminals (M3) having the dimensions shown below. 6.2 mm max. 6.2 mm max. 29 CJ1W-OC/OA/OD I/O Unit Wiring Methods An I/O Unit can be connected to an external device by any of the following three methods. 1. User-provided Cable An I/O Unit can be directly connected to an external device by using a connector. A B A User-provided cable B External device C Connector C 2. Connector-Terminal Block Conversion Unit Use a Connecting Cable to connect to a Connector-Terminal Block Conversion Unit. Converting the I/O Unit connector to a screw terminal block makes it easy to connect external devices. A B A Connecting Cable for Connector-Terminal Block Conversion Unit XW2Z B Connector-Terminal Block Conversion Unit XW2R C Conversion to a screw terminal block C 3. I/O Relay Terminal Use a Connecting Cable to connect to an I/O Relay Terminal. The I/O specifications can be converted to relay outputs and AC inputs by connecting the I/O Relay Terminal to an I/O Unit. A B A G79 I/O Relay Terminal Connecting Cable B G7@@ I/O Relay Terminals Or, conversion to relay outputs and AC inputs. B 30 CJ1W-OC/OA/OD 1. Using User-made Cables with Connector Available Connectors Use the following connectors when assembling a connector and cable. 32- and 64-point Basic I/O Units with Fujitsu-compatible Connectors Applicable Units Model Specifications CJ1W-OD231 Transistor Output Unit with Sinking Outputs, 32 outputs CJ1W-OD261 Transistor Output Unit with Sinking Outputs, 64 outputs Pins 40 Applicable Cable-side Connectors Connection Pins OMRON set Fujitsu parts Solder-type 40 C500-CE404 Socket: FCN-361J040-AU Connector cover: FCN-360C040-J2 Crimped 40 C500-CE405 Socket: FCN-363J040 Connector cover: FCN-360C040-J2 Contacts: FCN-363J-AU Pressure-welded 40 C500-CE403 FCN-367J040-AU/F 32- and 64-point Basic I/O Units with MIL Connectors Applicable Units Model Specifications CJ1W-OD232 Transistor Output Unit with sourcing outputs, 32 outputs CJ1W-OD262 Transistor Output Unit with sourcing outputs, 64 outputs CJ1W-OD233 CJ1W-OD234 Transistor Output Unit with sinking outputs, 32 outputs CJ1W-OD263 Transistor Output Unit with sinking outputs, 64 outputs Pins 40 Applicable Cable-side Connectors Connection Pressure-welded Crimped Pins OMRON set DDK parts 40 XG4M-4030-T *1 FRC5-A040-3T0S 40 XG5N-401 *2 HU-40OS2-001 - Crimp Contacts for XG5N *3 XG5W-0232 (loose contacts: 100 pieces) XG5W-0232-R (reel contacts: 10,000 pieces) HU-111S *1. Socket and Stain Relief set. *2. Crimp Contacts (XG5W-0232) are sold separately. *3. Applicable wire size is AWG 28 to 24. For applicable conductor construction and more information, visit the OMRON website at www.ia.omron.com. Wire Size We recommend using cable with wire gauges of AWG 28 to 24 (0.08 to 0.2 mm2). Use cable with external wire diameters of 1.61 mm max. Crimping Tools The following models are recommended for crimping tools and pressure-welding tools for Fujitsu connectors. Tools for Crimped Connectors (Fujitsu Component) Product Name Model Hand Crimping Tool FCN-363T-T005/H Contact Withdrawal Tool FCN-360T-T001/H Tools for Pressure-welded Connectors (Fujitsu Component) Product Name Hand Press Model FCN-707T-T101/H Cable Cutter FCN-707T-T001/H Locator Plate FCN-367T-T012/H The following models are recommended for tools for OMRON MIL connectors. Tools for Pressure-welded Connectors (OMRON) Product Name Model Pressure-welding Tool XY2B-0002 Attachment XY2B-1007 Tools for Crimped Connectors (OMRON) Product Name Manual Crimping Tool Model XY2B-7007 31 CJ1W-OC/OA/OD 2. Connecting Connector-Terminal Block Conversion Units Connection Patterns for Connector-Terminal Block Conversion Units Pattern Configuration Number of Connectors Connecting Cable Connector-Terminal Block Conversion Unit A 1 34 terminals Connecting Cable Connector-Terminal Block Conversion Unit B 34 terminals 2 34 terminals Combination of I/O Units with Connector-Terminal Block Conversion Units Unit CJ1WOD231 CJ1WOD232 CJ1WOD233 CJ1WOD234 I/O capacity 32 outputs 32 outputs 32 outputs 32 outputs Number of connectors 1 Fujitsu connector 1 MIL connector 1 MIL connector 1 MIL connector Polarity NPN PNP NPN NPN Connection pattern A A A A Connecting Cable XW2Z-@@@B XW2Z-@@@K XW2Z-@@@K XW2Z-@@@K Connector-Terminal Block Conversion Unit Wiring method XW2R-J34G-C3 Phillips screw XW2R-E34G-C3 Slotted screw (rise up) XW2R-P34G-C3 Push-in spring XW2R-J34G-C4 Phillips screw XW2R-E34G-C4 Slotted screw (rise up) XW2R-P34G-C4 Push-in spring XW2R-J34G-C4 Phillips screw XW2R-E34G-C4 Slotted screw (rise up) XW2R-P34G-C4 Push-in spring XW2R-J34G-C4 Phillips screw XW2R-E34G-C4 Slotted screw (rise up) XW2R-P34G-C4 Push-in spring Common terminals No No No No XW2R-J34G-C3 (2 Units) Phillips screw CJ1WOD261 64 outputs 2 Fujitsu connectors NPN B XW2Z-@@@B (2 Cables) XW2R-E34G-C3 (2 Units) Slotted screw (rise up) No XW2R-P34G-C3 (2 Units) Push-in spring XW2R-J34G-C4 (2 Units) Phillips screw CJ1WOD262 64 outputs 2 MIL connectors PNP B XW2Z-@@@K (2 Cables) XW2R-E34G-C4 (2 Units) Slotted screw (rise up) No XW2R-P34G-C4 (2 Units) Push-in spring XW2R-J34G-C4 (2 Units) Phillips screw CJ1WOD263 64 outputs 2 MIL connectors NPN B XW2Z-@@@K (2 Cables) XW2R-E34G-C4 (2 Units) Slotted screw (rise up) No XW2R-P34G-C4 (2 Units) Push-in spring 32 CJ1W-OC/OA/OD Types of Connecting Cables Appearance Connectors Model XW2Z-050B XW2Z-@@@B One 40-pin Connector Made by Fujitsu Component, Ltd. to One 40-pin MIL Connector XW2Z-@@@K Cable lenght [m] 0.5 XW2Z-100B 1 XW2Z-150B 1.5 XW2Z-200B 2 XW2Z-300B 3 XW2Z-500B 5 XW2Z-C50K 0.5 XW2Z-100K 1 XW2Z-150K 1.5 XW2Z-200K 2 XW2Z-300K 3 XW2Z-500K 5 One 40-pin MIL Connector to One 40-pin MIL Connector 3. Connecting I/O Relay Terminals Connection Patterns for I/O Relay Terminals Pattern Configuration Connecting Cable I/O Relay Terminal A I/O Relay Terminal I/O Relay Terminal B Connecting Cable Combination of I/O Units with I/O Relay Terminal and Connecting Cables Unit CJ1W-OD231 CJ1W-OD232 I/O capacity 32 outputs 32 outputs Number of connectors 1 Fujitsu connector 1 MIL connector Polarity NPN PNP Connection pattern Number of branches Connecting Cable I/O Relay Terminal A 2 G79-O@C-@ G7TC-OC16 A 2 G79-O@C-@ G7TC-OC08 A 2 G79-O@C-@ G70D-SOC16 A 2 G79-O@C-@ G70D-FOM16 A 2 G79-O@C-@ G70D-VSOC16 A 2 G79-O@C-@ G70D-VFOM16 A 2 G79-O@C-@ G70A-ZOC16-3 and Relay A 2 G79-O@C-@ G70R-SOC08 A 2 G79-O@C-@ G70D-SOC08 A 2 G79-I@-@-D1 G7TC-OC16-1 A 2 G79-O@-@-D1 G70D-SOC16-1 A 2 G79-O@-@-D1 G70D-FOM16-1 A 2 G79-O@-@-D1 G70A-ZOC16-4 and Relay 33 CJ1W-OC/OA/OD Unit CJ1W-OD233 CJ1W-OD234 CJ1W-OD261 CJ1W-OD262 CJ1W-OD263 I/O capacity 32 outputs Number of connectors 1 MIL connector 32 outputs NPN 1 MIL connector 64 outputs NPN 2 Fujitsu connectors 64 outputs 2 MIL connectors 64 outputs Polarity 2 MIL connectors NPN PNP NPN Connection pattern Number of branches Connecting Cable I/O Relay Terminal A 2 G79-O@-@-D1 G7TC-OC16 A 2 G79-O@-@-D1 G7TC-OC08 A 2 G79-O@-@-D1 G70D-SOC16 A 2 G79-O@-@-D1 G70D-FOM16 A 2 G79-O@-@-D1 G70D-VSOC16 A 2 G79-O@-@-D1 G70D-VFOM16 A 2 G79-O@-@-D1 G70A-ZOC16-3 and Relay A 2 G79-O@-@-D1 G70R-SOC08 A 2 G79-O@-@-D1 G70D-SOC08 A 2 G79-O@-@-D1 G7TC-OC16 A 2 G79-O@-@-D1 G7TC-OC08 A 2 G79-O@-@-D1 G70D-SOC16 A 2 G79-O@-@-D1 G70D-FOM16 A 2 G79-O@-@-D1 G70D-VSOC16 A 2 G79-O@-@-D1 G70D-VFOM16 A 2 G79-O@-@-D1 G70A-ZOC16-3 and Relay A 2 G79-O@-@-D1 G70R-SOC08 A 2 G79-O@-@-D1 G70D-SOC08 B 2 G79-O@C-@ G7TC-OC16 B 2 G79-O@C-@ G7TC-OC08 B 2 G79-O@C-@ G70D-SOC16 B 2 G79-O@C-@ G70D-FOM16 B 2 G79-O@C-@ G70D-VSOC16 B 2 G79-O@C-@ G70D-VFOM16 B 2 G79-O@C-@ G70A-ZOC16-3 and Relay B 2 G79-O@C-@ G70R-SOC08 B 2 G79-O@C-@ G70D-SOC08 B 2 G79-I@-@-D1 G7TC-OC16-1 B 2 G79-O@-@-D1 G70D-SOC16-1 B 2 G79-O@-@-D1 G70D-FOM16-1 B 2 G79-O@-@-D1 G70A-ZOC16-4 and Relay B 2 G79-O@-@-D1 G7TC-OC16 B 2 G79-O@-@-D1 G7TC-OC08 B 2 G79-O@-@-D1 G70D-SOC16 B 2 G79-O@-@-D1 G70D-FOM16 B 2 G79-O@-@-D1 G70D-VSOC16 B 2 G79-O@-@-D1 G70D-VFOM16 B 2 G79-O@-@-D1 G70A-ZOC16-3 and Relay B 2 G79-O@-@-D1 G70R-SOC08 B 2 G79-O@-@-D1 G70D-SOC08 Types of Connecting Cables G79-O@C-@ G79-O@-@-D1 0.25m Cable length - - 0.5m - G79-O50-25-D1 G79-I@-@-D1 - G79-I50-25-D1 1.0m G79-O100C-75 1.5m G79-O150C-125 G79-O75-50-D1 - G79-I75-50-D1 - 2.0m G79-O200C-175 - - 3.0m G79-O300C-275 - - 5.0m G79-O500C-475 - - 34 CJ1W-OC/OA/OD Dimensions (Unit: mm) 8-point/16-point Units (18-point Terminal Blocks) CJ1W-OC201/ OC211/ OA201/ OD201 / OD202/ OD203/ OD204/ OD211/ OD213 / OD212 2.7 89 65 ID211 0 1 2 8 9 10 11 12 13 14 15 3 4 5 6 7 0 1 2 3 4 5 6 90 7 8 9 10 11 12 13 14 15 COM COM 2.7 DC24V 7mA 31 32-point Unit (Output Units) With Fujitsu-Compatible Connector (40-pin x 1) CJ1W-OD231 (112.5) 2.7 66.5 65 ID231 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 1 2.7 DC24V 4.1mA 90 1 20 20 A B 20 With MIL Connector (40-pin x 1) CJ1W-OD232 / OD233 / OD234 2.7 83.6 65 ID231 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2.7 DC24V 4.1mA 90 1ch 0ch 20 35 CJ1W-OC/OA/OD 64-point Units (Output Units) With Fujitsu-Compatible Connector (40-pin x 2) CJ1W-OD261 66.5 65 31 2.7 90 2.7 (112.5) With MIL Connector (40-pin x 2) CJ1W-OD262 / OD263 65 2.7 90 2.7 83.6 31 Related Manuals Name Cat. No. Contents CJ-series CJ2 CPU Unit Hardware User's Manual CJ2H-CPU6@-EIP CJ2H-CPU6@ CJ2M-CPU@@ W472 Describes the following for CJ2 CPU Units: * Overview and features * Basic system configuration * Part nomenclature and functions * Mounting and setting procedure * Remedies for errors * Also refer to the Software User's Manual (W473). CJ Series CJ1H-CPU@@H-R, CJ1G/H-CPU@@H, CJ1G-CPU@@P, CJ1G-CPU@@, CJ1M-CPU@@ Programmable Controllers Operation Manual W393 Provides an outlines of and describes the design, installation, maintenance, and other basic operations for the CJ-series PLCs. W500 An introduction to the entire NJ-series system is provided along with the following information on a Controller built with an NJ501 CPU Unit. * Features and system configuration * Introduction * Part names and functions * General specifications * Installation and wiring * Maintenance and inspection Use this manual together with the NJ-series CPU Unit Software User's Manual (Cat. No. W501). NJ-series CPU Unit Hardware User's Manual NJ501-@@@@ 36 Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron's exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron's sole obligation hereunder shall be, at Omron's election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron's analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer's application or use of the Product. At Buyer's request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer's application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user's programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron's test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron's Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron's representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. 2014.9 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2014 All Right Reserved. Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Omron: G7TC-OC08 DC24V G70D-VSOC16 DC24 G70D-SOC16-1 DC24 G70D-VFOM16 DC24 G7TC-OC16 DC12V G7TC-OC08-1 DC24V G7TC-ID16 DC24V G7TC-OC16 DC24V G70D-FOM16 G70D-ET G7TC-OC08 DC12V G70D-SOC16 DC24 G7TC-ID16-5 DC24 CJ1W-OD234 CJ1W-OD213