1
Power Meter Front End Design:
The Delta Connection
Atmel’s AT73C500 + AT73C501-based
meter chipset measures power and
energy in three-phase systems or, alter-
natively, the chipset can be set to
operate in a mode where it measures
three separate, single-phase connec-
tions. In normal modes of operation, the
chipset measures Y-connected three-
phase, four-wire environments, but there
is no dedicated operating mode for
Delta-connected three-phase, three-wire
systems. This application note describes
how to implement the chipset in three-
phase, three-wire environments.
Three-Phase Basics
To understand the measurement
method, it is important to outline some of
the following basic concepts.
Terminology
Voltages (and currents) in a three-phase
system are referred to as either phase
voltages (currents) or main voltages
(currents), depending on the point of
reference.
•A Phase Voltage(1) (UP1, UP2 and UP3)
is always referenced to the neutral
wire. In systems where there is no
physical neutral wire, the phase
voltages are referenced to a virtual
neutral.
Note: 1. Also called neutral voltage. This
should not be confused with the
ground neutral that is at zero
potential.
• The Main Voltage (U1, U2 and U3) is
defined as the voltage between two of
the phase conductors.
•A Phase Current (IP1, IP2 and IP3) is
the current flowing through the load
impedance. Depending on the type of
connection, this current is not
necessarily directly measurable from
the meter connection points, but must
be derived from the vector sum of
other currents.
• The Main Current (I1, I2 and I3) is
defined as the current that flows
through the phase conductor.
Depending on the type of connection,
this current is not necessarily the
same that flows through the load.
The Star Connection
A typical three-phase, four-wire service
with a grounded neutral is illustrated in
Figure 1. The system shown is com-
monly referred to as a YN-configuration,
with the subscript denoting there is a
neutral wire present. The wiring method
is sometimes also referred to as Star
connection.
In Figure 1, the circuit on the left illus-
trates the power generator and the
circuit on the right the load. In this type of
connection, the energy meter would
interface to measure the phase volt-
ages (UP1, UP2 and UP3) and phase
currents (IP1, IP2 and IP3).
In a balanced (all loads are equal) Star
connection, the neutral line carries no
current and the main current is equal to
the phase current. The main voltage is
related to the phase voltage as follows:
P
U3U ×=
Rev. 1680A–07/00
Power Meter
Front End
Design:
The Delta
Connection
Application
Note