DATASHEET - ESR5-NO-31-AC-DC Safety relay emergency stop/protective door, 24V-230VDC/AC, 3 enabling paths Delivery program Part no. Catalog No. Eaton Catalog No. EL-Nummer (Norway) ESR5-NO-31-AC-DC 118704 ESR5-NO-31-AC-DC 4133321 Product range Electronic safety relays Basic function Emergency stop; emergency switching off Protective door Feedback circuit Features Mounting width mm 45 Automatic or manual start Start button monitoring Operation Supply voltage single-channel dual-channel Us 24 V DC 24 V AC, 50/60 Hz 24 V AC/DC - 230 V AC/DC, 50/60 Hz 115 V AC, 50/60 Hz 230 V AC, 50/60 Hz Approval Safety related characteristics Cat. 4 PL e according to EN ISO 13849-1 SILCL 3 according to IEC 62061 SIL 3 according to IEC 61508 Number of enabling paths to EN 60204-1 Stop functions category Enable current paths to IEC/EN 60204-1 Stop category 0 3 Signal current paths 1 Technical data General Intended use Sicherheitsrelais zur Uberwachung von Not-Halt- und Schutzturschaltern. Mit Hilfe dieses Modules werden Stromkreise sicherheitsgerichtet unterbrochen. Policies List EMV 2004/108/EG, Maschinen 2006/42/EG Standards EN ISO 13849-1:2008, EN 62061:2005+AC:2010, EN 61508, Parts 1-7:2001, EN 50178:1997, EN 60204-1:2006+A1:2009 Dimensions (W x H x D) mm 45 x 114.5 x 99 Mounting width mm 45 Weight kg 0,31 Mounting position As required Mounting Top-hat rail IEC/EN 60715, 35 mm Connection type M3 screw terminals Lifespan, mechanical Operations 6 10 2 1x (0.2 - 2.5) 2x (0.2 - 1) 2 x 10 Terminal capacity Solid mm Flexible with ferrule mm 1x (0.25 - 2.5) 2x (0.25 - 1) Solid or stranded AWG 24 - 12 Terminal screw Nm Pozidriv screwdriver Size 2 Standard screwdriver mm 0.6 x 3.5 04/09/2018 Eaton 118704 ED2018 V42.0 EN 1/6 Max. tightening torque Stripping length Nm 0.6 mm 7 Material Housing: polyamide PA not reinforced Contacts: Material: silver tin oxide, gold plated (AgSnO2, 0.2 m Au) Duty factor % DF 100 Operating conditions Climatic environmental conditions Climatic proofing Dry heat to IEC 60068-2-2 Damp heat as per EN 60068-2-3 Ambient temperature Operation C -20 - +55 Storage C -25 - +85 Condensation Non-condensing Atmospheric conditions relative humidity % Max. 75 Air pressure (operation) hPa 795 - 1080 Above sea level m 2000 P W 4.8 Altitude Power loss Ambient conditions, mechanical Degree of protection to VDE 0470-1 Enclosures IP20 Terminals IP20 Degree of Protection Installation location: IP54 B10d [switching cycles] 300000 Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof Vibrations (IEC/EN 60068-2-6) 10 - 150 Hz Amplitude: 0.15 mm Acceleration: 2 g Clearance in air and creepage distances EN 50178, UL 508, CSA C22.2, No. 14-95 Rated impulse withstand voltage Uimp V AC 4000 Insulation Basic isolation Safe isolation, reinforced isolation, and 6 kV between input circuit and enable current paths (13-14, 23-24, 33-34) and between (13-14, 23-24, 33-34) with relation to each other. Overvoltage category/pollution degree III/2 Stop category according to EN60204-1 1,26 Performance level according to EN ISO 13849-1 PL e Category according to EN ISO 13849-1 Kat. 4 Safety integrity level claim limit in accordance with 62061 SILCL 3 Safety integrity level In accordance with IEC 61508 SIL 3 Probability of failure per hour PFHd Technical safety parameters: Values according to EN ISO 13849-1 Prooftest High Demand x 10 -10 1.26 Months 240 Prooftest Low Demand Months 59 Rated operational voltage Ue V AC 230 Rated operational voltage Ue V 24 - 230 V AC, 24 - 230 V DC Permissible range Rated insulation voltage 0.85 - 1.1 x Ue Ui V AC 250 Quadratic summation current A 50 A (ITH = I1 + I2 + ... + IN ) Inrush current A min - max 0.025 - 6 Minimum switching capacity W 0.4 04/09/2018 2 2 Eaton 118704 ED2018 V42.0 EN 2 2 2 2 2/6 Control circuit Power supply circuit AC operated 50/60 Hz W 5.8 DC operated W 2.9 Fuse for control circuit supply 24 V short-circuit proof 115 V/230 V short-circuit proof Input data Rated current mA S10, S12, S22:35, S34, S35:45 Current consumption mA 120 V AC: 20 230 V AC: 10 24 V DC: 120 V DC Approx. 24 11 Voltage at input, starting and feedback circuit Max. resistive load of the cable R Short-circuit current A 0.7 Pick-up time (K1, K2) for UN automatic mode, typical tA ms 250 Pick-up time (K1, K2) for UN manual operation, typical tA ms 60 ms at Ue in automatic mode: normally 250 at Ue in manual mode: normally 60 Pick-up time Reset time (K1, K2) for UN , normally tR ms 20 (when actuated via S11/12 and S21/S22) 500 (on actuation via A1) 50 (at 24 V DC) 110 (at 120 V AC) 280 (at 230 V AC) Recovery time tW ms Approx. 1000 Simultaneity for inputs 1/2 tsync ms Maximum permissible total cable resistance (input and starting circuits for UN) RL 11 Maximum switching frequency Hz 0.5 Status indication LED Green Output data Contact type Non-delayed enable current paths 3 Delayed signal current path 1 Switching voltage Limiting continuous current min - max 15 - 250 V AC 15 - 250 V DC A Short-circuit protection for output circuits, external per N/O: 6 N/C: 6 Fuse 6 A gL/gG Output fuse NEOZED (N/O) gL/gG 6 NEOZED (N/C) gL/gG 6 24 V DC W 144 48 V DC W 384 110 V DC W 80 220 V DC W 66 250 V AC VA 2000 24 V DC W 48 48 V DC W 48 110 V DC W 48 220 V DC W 48 Maximum breaking power Resistive load ( = 0 ms) Inductive load ( = 40 ms) Switching capacity In accordance with IEC 60947-5-1 AC-15 230 V A 3 A bei 3600S/h A 3 A bei 3600S/h DC-13 24 V 04/09/2018 Eaton 118704 ED2018 V42.0 EN 3/6 Further information (flip catalog) description Emitted interference In accordance with EN 61000-6-4 Interference immunity according to EN 61000-6-2 Electromagnetic compatibility (EMC) Design verification as per IEC/EN 61439 Technical data for design verification Rated operational current for specified heat dissipation In A 0 Heat dissipation per pole, current-dependent Pvid W 0 Equipment heat dissipation, current-dependent Pvid W 0 Static heat dissipation, non-current-dependent Pvs W 4.8 Heat dissipation capacity Pdiss W 0 Operating ambient temperature max. C -20 Operating ambient temperature max. C 55 IEC/EN 61439 design verification 10.2 Strength of materials and parts 10.2.2 Corrosion resistance Meets the product standard's requirements. 10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements. 10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements. 10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects Meets the product standard's requirements. 10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements. 10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated. 10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated. 10.2.7 Inscriptions Meets the product standard's requirements. 10.3 Degree of protection of ASSEMBLIES Meets the product standard's requirements. 10.4 Clearances and creepage distances Meets the product standard's requirements. 10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated. 10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated. 10.7 Internal electrical circuits and connections Is the panel builder's responsibility. 10.8 Connections for external conductors Is the panel builder's responsibility. 10.9 Insulation properties 10.9.2 Power-frequency electric strength Is the panel builder's responsibility. 10.9.3 Impulse withstand voltage Is the panel builder's responsibility. 10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility. 10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. 10.11 Short-circuit rating Is the panel builder's responsibility. 10.12 Electromagnetic compatibility Is the panel builder's responsibility. 10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. Technical data ETIM 6.0 Relays (EG000019) / Device for monitoring of safety-related circuits (EC001449) Electric engineering, automation, process control engineering / Low-voltage switch technology / Monitoring equipment (low-voltage switch technology) / Device for monitoring of safetyrelated circuits (ecl@ss8.1-27-37-18-19 [ACO304008]) Model Basic device Suitable for monitoring of position switches Yes Suitable for monitoring of emergency-stop circuits Yes Suitable for monitoring of valves No Suitable for monitoring of optoelectronic protection equipment No Suitable for monitoring of tactile sensors No Suitable for monitoring of magnetic switches No Suitable for monitoring of proximity switches No Type of electric connection Screw connection Rail mounting possible Yes Rated control supply voltage Us at AC 50HZ 04/09/2018 V 0 - 26.4 Eaton 118704 ED2018 V42.0 EN 4/6 Rated control supply voltage Us at AC 60HZ V 0-0 Rated control supply voltage Us at DC V 0-0 Voltage type for actuating AC/DC With detachable clamps Yes Evaluation inputs One- and two-channel With start input Yes With muting function No With feedback circuit Yes Release-delay s 0-0 Number of outputs, safety related, undelayed, with contact 3 Number of outputs, safety related, delayed, with contact 0 Number of outputs, safety related, undelayed, semiconductors 0 Number of outputs, safety related, delayed, semiconductors 0 Number of outputs, signalling function, undelayed, with contact 1 Number of outputs, signalling function, delayed, with contact 0 Number of outputs, signalling function, undelayed, semiconductors 0 Number of outputs, signalling function, delayed, semiconductors 0 Category according to EN 954-1 4 Type of safety acc. IEC 61496-1 - Stop category acc. to IEC 60204 0 Performance level acc. to EN ISO 13849-1 Level e SIL according to IEC 61508 3 With approval for TUV Yes With approval for BG BIA No With approval according to UL Yes Width mm 45 Height mm 99 Depth mm 114.5 Approvals Product Standards IEC/EN see Technical Data; UL 508; CSA-C22.2 No. 14-95; CE marking UL File No. E29184 UL Category Control No. NKCR; NKCR7 CSA File No. UL report applies to both US and Canada CSA Class No. 3211-83; 3211-03 North America Certification UL listed, certified by UL for use in Canada Degree of Protection IEC: IP20, UL/CSA Type: - 04/09/2018 Eaton 118704 ED2018 V42.0 EN 5/6 Dimensions Assets (Links) Declaration of Conformity 00002514 Additional product information (links) IL05013031Z operator manual for electricians IL05013031Z operator manual for electricians ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL05013031Z2014_04.pdf description http://de.ecat.moeller.net/flip-cat/?edition=HPLTE&startpage=13.15 04/09/2018 Eaton Industries GmbH http://www.eaton.eu (c) 03/2018 by Eaton Industries GmbH Eaton 118704 ED2018 V42.0 EN 6/6