171
Solid-state Relay G3CN
PCB-mounting SSR for FA Equipment
Requiring High Reliability
Wide
I/O voltage range: 3 to 28 VDC input
and 75 to
264 VAC output or 3 to 28 VDC input and 3 to
52.8 VDC output.
Two load currents available: 2 A and 3 A
Flat and vertical models available for a variety of
applications.
Approved by UL and CSA.
RC
Ordering Information
Isolation Zero
cross
function Indicator
Rated output voltage
(Applicable output load)
Rated input voltage
Model
Photocoupler Yes No
2 A at 100 to 240 V
AC
(2 A at 75 to 264 V
AC)
4 to 24 VDC
G3CN-202P-US
G3CN-202P1-US*
3 A at 100 to 240 V
AC
(3 A at 75 to 264 V
AC) G3CN-203P-US
G3CN-203P1-US*
Phototriac No
2 A at 100 to 240 V
AC
(2 A at 75 to 264 V
AC)
5, 12, 24 VDC**
G3CN-202PL-US
G3CN-202PL1-US*
3 A at 100 to 240 V
AC
(3 A at 75 to 264 V
AC) G3CN-203PL-US
G3CN-203PL1-US*
Photocoupler ---
2 A at 4 to 48 VDC
(2 A at 3 to 52.8 VDC)
4 to 24 VDC
G3CN-DX02P-US
G3CN-DX02P1-US*
3 A at 4 to 48 VDC
(3 A at 3 to 52.8 VDC)
G3CN-DX03P-US
G3CN-DX03P1-US*
*V
ertical models.
**When ordering, specify the input voltage
G3CN G3CN
172
Specifications
Ratings
Input
Model Rated
voltage
Operating voltage
Impedance V
oltage level
Must operate
voltage
Must release
voltage
G3CN-202P(1)-US
G3CN-203P(1)-US
4 to 24 VDC 3 to 28 VDC
1.5 k
+20%/–10% 3 VDC max.
1 VDC min.
G3CN-202PL(1)-US
G3CN 203PL(1) US
5 VDC
4 to 6 VDC
390
±20% 4 VDC max.
G3C 0 ( ) US
G3CN-203PL(1)-US 12 VDC
9.6 to 14.4 VDC
900
±20%
9.6 VDC max.
24 VDC
19.2 to 28.8 VDC
2 k±20%
19.2 VDC max.
G3CN-DX02P(1)-US
G3CN-DX03P(1)-US
4 to 24 VDC 3 to 28 VDC
1.5 k
+20%/–10% 3 VDC max.
Note: The
input impedance is measured at the maximum value of the operating voltage. For example, with the model rated at 4 to 24 VDC, the
input
impedance is measured at 28 VDC.
Output
Model
Applicable load
Rated load voltage Load volage range
Load current
Inrush current
W
ithout heat sink
G3CN-202P(1)-US
G3CN-202PL(1)-US
100 to 240 V
AC
75 to 264 V
AC
0.1 to 2 A
30 A (60 Hz, 1 cycle)
G3CN-203P(1)-US
G3CN-203PL(1)-US
0.1 to 3 A
45 A (60 Hz, 1 cycle)
G3CN-DX02P(1)-US
4 to 48 VDC
3 to 52.8 VDC
0.1 to 2 A
12 A (10 ms)
G3CN-DX03P(1)-US
0.1 to 3 A
18 A (10 ms)
Characteristics
Item G3CN-202P(1)/203P(1)-US G3CN-202PL(1)/203PL(1)-US G3CN-DX02P(1)/03P(1)-US
Operate
time
1/2 of load power source cycle +
1 ms max. 1 ms max.
0.5 ms max.
Release time
1/2 of load power source cycle +
1 ms max.
1/2 of load power source cycle
+ 1 ms max.
2 ms max.
Output ON voltage drop
1.6 V (RMS) max.
1.5 V max.
Leakage current
5 mA max. (at 100 V
AC)
10 mA max. (at 200 V
AC)
2.5 mA max. (at 100 V
AC)
5 mA max. (at 200 V
AC)
5 mA max. (at 50 VDC)
Insulation resistance
100 M
min. (at 500 VDC)
Dielectric strength
2,500 V
AC, 50/60 Hz for 1 min
V
ibration resistance
Malfunction: 10 to 55 Hz, 1.5-mm double amplitude
Shock resistance
Malfunction: 1,000 m/s
2
Ambient temperature
Operating: –30°
C to 80
°
C (with no icing nor condensation)
Storage: –30°
C to 100
°
C (with no icing nor condensation)
Ambient humidity
Operating: 45% to 85%
Approved standards
UL508, UL1
14 File No.E64562, CSA C22.2 (No.0, No.14) File No. LR35535
Weight
Approx. 25 g
G3CN G3CN
173
Engineering Data
Load Current vs. Ambient Temperature Characteristics
G3CN-202P(1)/-202PL(1)/-DX02P(1)-US
Ambient
temperature (
°C)
Load current (A)
G3CN-203P(1)/-203PL(1)/-DX03P(1)-US
Load current (A)
Ambient temperature (
°C)
G3CN-203P(1)/-203PL(1)-US
G3CN-DX02P(1)-US
Inrush current (A. Peak)
Energizing time (ms)
Inrush current (A. Peak)
Energizing time (ms)
Inrush Current Resistivity
Non-repetitive
(Keep the inrush current to half the rated value if it occurs repetitively
.)
G3CN-202P(1)/-202PL(1)-US
G3CN-DX03P(1)-US
Inrush current (A. Peak)
Inrush current (A. Peak)
Energizing time (ms) Energizing time (ms)
G3CN G3CN
174
Dimensions
Note:
All units are in millimeters unless otherwise indicated.
Input
voltage
T
erminal Arrangement/
Internal Connections
(Bottom View)
Flat Model
G3CN-20jP/-20jPL/-DX0jP
Vertical Model
G3CN-20jP1/-20jPL1/-DX0jP1
4
+
3+
2
(–)
(+)
1
(–)
(+)
Input Load
Load
Load power
supply
Note: Values
in parentheses apply
to the DC-load versions.
43 2 1
–+ (–) (+)
+ (–) (+)
Input Load
Load
Input voltage Load power supply
Note: Values
in parentheses apply
to the DC-load versions.
0.4
33
max.
25 max.
14.5
max.
20 max. 1.5 max.
25±0.5
12.5±0.5
10±0.5
0.7 0.7
0.7 0.4
33 max.
14 max.
26.5 max.
32 max. 1.5 max.
27.5±0.5
(17.5) 5±0.5 3±1
Four 1.2-dia.
holes 25
12.5
5 (17.5) 5
27.5
Two, 2-dia.
holes
Two, 4 dia.
holes
Two, 2-dia.
holes
Four 1.2-dia.
holes
Pattern Pattern
10
Terminal
Arrangement/
Mounting Holes
(Bottom View)
T
erminal Arrangement/
Internal Connections
(Bottom View)
T
erminal Arrangement/
Mounting Holes
(Bottom View)
5±0.5
G3CN G3CN
175
Precautions
Refer to pages
1
1 to
19 for general precautions.
Connection
With
the SSR for DC switching, the load can be connected to either
positive
or negative output terminal of the SSR.
Protective Component
Since the SSR does not incorporate an overvoltage absorption
component,
be sure to connect an
overvoltage absorption compo
-
nent
when using the SSR under an inductive load.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To
convert millimeters into inches, multiply by 0.03937. T
o convert grams into ounces, multiply by 0.03527.
Cat. No. K063-E1-2A