48-DIN sized PID temperature controller with
adaptive fuzzy self-tuning
■User-selectable for K, J, R, B, PL-II and N
thermocouples and Pt100 resistance thermometers
■User adjustable temperature scale to suit application
■Two temperature alarm contacts independently
programmable with 12 functions
■Alarm hysteresis adjustable from 0.1 to 100.0˚C or ˚F
■3 levels of keypad security locking
■Selectable operation: PID with adaptive fuzzy logic,
PID with auto-tune, PD or On/Off
■Anti-reset windup (ARW) to reduce overshoot
■Relay, voltage pulse, analogue 4-20mA or 0-10VDC
output
■Very fast sampling period 0.125 seconds
■Adjustable PV filter to slow down response if required
■Wide 100-240 VAC or 24 VAC/DC supply voltage
■IP54 protection
■UL and CSA approved
Fuzzy Logic Temperature
Controller with 4-Digit LED Display
FCS-
13A
Options and ordering codes
Specifications
FCS-13A R–/M 100-240VAC
Fuzzy logic PID temperture
controller with 4-digit display
Relay output R
Signal voltage for SSR S
Current output A
Analogue voltage 0-10VDC
100-240VAC supply
24VAC/DC supply
Multisensor input
V
M
Optional extra: heater burnout alarm.
Please note: All models supplied with A2: Two alarms, BL: Screw
mounting bracket, IP: IP54 protection.
Input type
K-thermocouple J-thermocouple R-thermocouple B-thermocouple PL-II thermocouple N-thermocouple DIN Pt100 RTD J Pt100 RTD
Rated scale
–200 to 1370˚C –200 to 1000˚C 0 to 1760˚C 0 to 1820˚C 0 to 1390˚C 0 to 1300˚C –199.9 to 850.0˚C –199.9 to 500.0˚C
Sensor resistance 100Ωor less 10Ωper wire or less
Accuracy ±0.3% of full scale ± 1 digit (Type B thermocouple 0-300˚C, 0-600˚F accuracy not specified)
Display PV: 4-digit red LED, 8mm high; SV: 4-digit green LED, 8mm high
Control action User-selectable: Fuzzy self-tuning PID, PID with autotune, PD, On/Off
Proportional band 0.1 to 100.0%, Factory set to 2.5%
Integral time 1 to 3600 secs (off when set to 0), Factory set to 200 secs
Derivative time 1 to 3600 secs (off when set to 0), Factory set to 50 secs
Anti-reset windup Automatic in PID modes
Reset range in PD action Within the proportional band, providing within –199.9 to 999.9˚C (˚F)
Hysteresis in On/Off action 0.1 to 100.0˚C (˚F)
Proportional cycle 1 to 120 seconds, Relay output type: Factory set to 30 secs; Signal voltage type: Factory set to 3 secs
Output: relay types SPNO: 250V, 3A resistive load; 250V, 1A inductive load, cos ø = 0.4
Output: signal voltage types 12VDC +2VDC/–0VDC 40mA, short-circuit protected
Output: analogue types 4 to 20mA DC - max. load resistance 550Ω, 0-10VDC – output impedance 500Ω
Temperature alarm relay A1 SPNO: 250V 3A resistive load; 250V, 1A inductive load, cos ø = 0.4
Temperature alarm relay A2 SPNO: 250V 3A resistive load; 250V, 1A inductive load, cos ø = 0.4
Temp. alarms setting accuracy ±0.3% of full scale ±1 digit
Temperature alarms action ON/OFF action, hysteresis 0.1 to 100.0˚C (˚F), Factory set to 1.0˚C (˚F)
High limit alarm (1) Deviation from SV: ±200˚C (˚F)
Low limit alarm (1) Deviation from SV: ±200˚C (˚F)
High/low limits alarm (1) Deviation from SV: 1 to 200˚C (˚F)
High/low limit range alarm (1) Deviation from SV: 1 to 200˚C (˚F)
Absolute value (process) alarm (1) Input range minimum value to input range maximum value
Absolute (process) reverse alarm (1) Input range minimum value to input range maximum value
Sensor correction (input shift) –100.0 to 100.0˚C (˚F), Factory set to 0.0˚C (˚F)
Sensor break protection Upscale: Control output off
Supply voltage 85 to 264VAC 50/60Hz (100-240 VAC+10%–15%); 20 to 28 VDC/AC 50/60Hz
Power consumption 8VA approx.
Ambient temperature 0 to 50˚C
Ambient humidity 35 to 85% r.h. (non-condensing)
Insulation resistance (2) >10MΩat 500VDC
1.5k VAC for 1 min between: Sensor input terminals and ground, Power terminals and ground,
Dielectric strength (2) Control output terminals and ground, Alarm output terminals and ground, Sensor input terminals and
Power terminals, Control output terminals and Power terminals, Alarm output terminals and Power terminals,
Sensor input terminals and Control output terminals, Sensor input terminals and Alarm output terminals,
Control output terminals and Alarm output terminals
Mounting Flush
Front panel Membrane sheet keyboard, IP54
Weight 140g approx
Case material Light grey polycarbonate, flame retardant and self-extinguishing
(1) All alarm types can be programmed to operate with or without ‘standby’ function (2) Do not apply voltage between sensor input terminals and control output terminals of FCS-13A-A, FCS-13A-S and FCS-13A-V models
PRICE
INFORMATION
AND ORDERING
PRICE