Raychem 99T1131 Issue 1 October 1989 beg 2D CABLE, ELECTRIC, THREE CONDUCTOR, POLYESTER INSULATED, ZEROHALOGEN JACKETED, LIGHTWEIGHT, 600 VOLT The complete requirements for procuring the wire herein shall consist of this document and the issue in effect of Raychem Specification WCD 282 and WCD 2015 as applicable. SHIELD - Tin Plated Copper - 85% coverage COMPONENT - JACKET - 99T0111 Extruded Crosslinked er FZ Zerohal* Material WY, PART WIRE | SHIELD JACKET OUTSIDE | MAXIMUM NUMBER SIZE SIZE THICKNESS| DIAMETER | WEIGHT MIN | NOM _ | NOM|MAX 99T1131-24-*/*/*-* 24 0.10 0.28 | 0.33 3.36 | 3.53 21.54 99T1131-22-*/*/*-* | 22 0.10 0.28 | 0.33 | 3.71 | 3.90 28.01 99T1131-20-*/*/*-* | 20 0.10 0.28 | 0.33 | 4.25 | 4.47 39.40 99T1131-18-*/*/*-* 18 0.10 0.28 | 0.33 4.79 | 5.03 53.05 99T1131-16-*/*/*-* 16 0.10 0.28 | 0.33 5.33 | 5.60 68.97 99T1131-14-*/*/*-* 14 0.10 0.28 | 0.33 5.98 | 6.28 89.48 99T1131-12-*/*/*-* 12 0.10 0.28 | 0.33 6.95 | 7.30 128.52 Raychem Limited Faraday Road, Swindon SN3 SHH Tel (0793) 28171 Telex 449409 COMPONENT: To meet all the reqiuirements of component wire Specification Control Drawing ADDITIONAL CABLE REQUIREMENTS TEMPERATURE RATING: 105C for 10,000 hours VOLTAGE TEST: JACKET COLOUR: PART NUMBER: Dorcan LONDON EC4A 1NH 2.5kV 1 minute Black preferred The '*' in the part number shall be replaced by a standard colour code designator in accordance with Mil Std 681. ie: 99T1131-20-2/6/9-0, Size 20 conductor, red/blue/white insulation, black jacket. * Zerohal is a trade mark of Raychem Ltd. Registration Number: 674709 London, England Registered Office: Rolls House 7 Rolls Buildings, FetterLane This drawing and the information set forth hereon are the property of Raychem Ltd. andareto beheld intrust and confidence. Publication, duplication, disclosure or use for any purpose not expressly authorised in writing by Raychem Ltd. is prohibited This specification sheet takes precedence over documents referenced herein. As Raychem Ltd reserve the rightto make changes in construction without notice please contact Raychem Ltd. to ensure that this documentis the latestissue. GB-|-W-17 DESIGN PROD. MAN. a TECH. Q.C. N MAN. ENG. Danes ready hn fe ASE Vanesa |e | ee | B/tnyeg ret PERFORMANCE AND TEST REQUIREMENTS TO WCD 2015 AND NES 518 WCD 2015 Clause No 5.11 6.1.1 6.1.3 6.1.4 6.1.12 6.1.12 7.2.1 7.2.1 7.2.1 7.2.1 7.2.1 7.2.1 N/A IL 100% PQ IL IL PQ QA QA OA QA QA PQ FREQUENCY DEFINITION Jacket concentricity Spark Test 1.5kV rms 50/60Hz Impulse Test 6.0kV peak Jacket Insulation Resistance Heat shock Jacket Tensile Strength Jacket Elongation Jacket Heat Ageing Jacket Limiting Oxygen Index Jacket Temperature Index Jacket Toxicity Jacket Halogen Content Jacket Smoke Index Flammability BS 4066 (IEC 332 Part 1) REQUIREMENTS 70% minimum No failures No failures 01.0 Mohms km 4 hours at 150C + 3C, 4x mandrel, no cracking, dripping flowing of jacket material. No dielectric failure 1kV ac 5 seconds 8N/mm minimum 200% minimum 200C, 4 hours, 60% minimum retention of tensile strength and elongation 29 minimum 250C 5 maximum Negative result for halogens 20 maximum 50mm maximum burn length