-20- All Data Subject To Change Without Notice
www.andersonpower.com
| PP15-45 ORDERING INFORMATION |
PP15-45 series are the smallest Powerpole® housings. They can
be used for wire-to-wire or wire-to-board applications. Wire sizes
from#20AWG(0.75mm²)to#10(6mm²)offerpowercapabilities
up to 55 amps per pole. Finger proof housings and the ability
toincorporaterst-matelast-breakgroundconnectorsenhancethe
capabilities of this Powerpole® series.
High Power Density
• Up to 55 amps in a compact footprint
Wire-to Wire & Wire-to-Board Congurations
• Wire & PCB contacts can be used in the same housings
Finger Proof Housings Available
• Protects against accidental contact with live circuits
Powerpole® Connectors
- PP15 to PP45 :
up to 55 Amps
Finger Proof
Rib Feature
SECTION 2
Powerpole® PP15 to 45
PP15-45 Finger Proof Housings
Improved on the original APP design by adding ribs to mating interface to
protect against accidental contact with live circuits. Meets the requirements
ofUL1977section10.2andisratedIP20.Willnotmatewithstandardhousings.
Description ------------ Part Numbers ------------
MinimumQuantity...2,500 200.....
Red 1327FP-BK 1327FP
Green 1327G5FP-BK 1327G5FP
Black 1327G6FP-BK 1327G6FP
White 1327G7FP-BK 1327G7FP
Blue 1327G8FP-BK 1327G8FP
Yellow 1327G16FP-BK 1327G16FP
PP15-45 Standard Housings
This original housing design has an open interface and is available
in a wide array of colors.Willnotmatewithngerproofhousings.
Description ------- Part Numbers ------
MinimumQuantity...2,500 200...
Red 1327-BK 1327
Green 1327G5-BK 1327G5
Black 1327G6-BK 1327G6
White 1327G7-BK 1327G7
Blue 1327G8-BK 1327G8
Yellow 1327G16-BK 1327G16
Orange 1327G17-BK 1327G17
Gray 1327G18-BK 1327G18
Brown 1327G21-BK 1327G21
Pink 1327G22-BK 1327G22
Purple 1327G23-BK 1327G23
45A Premate Ground Housings
Green housings are keyed to prevent accidental mating with
standardorngerproofPowerpole® housings.
Description ------ Part Numbers -----
MinimumQuantity...2,500 200...
Green 1827G1-BK 1827G1
PP15-45 Finger Proof & Standard & Ground
Housing Dimensions
Front View
MatedLength
[ 24.6 ]
0.97
[ 41.2 ]
1.62
[ 8.4 ]
0.33
[ 7.9 ]
0.31
[ 7.9 ]
0.31
©2017AndersonPowerProducts,Inc.Allrightsreserved.APP®,AndersonPowerProducts®,A®,Powerpole®,SPECPak®andtheAPPLogoareregisteredtrademarksof
Anderson Power Products, Inc.
-21-
All Data Subject To Change Without Notice www.andersonpower.com
SECTION 2
Powerpole® PP15 to 45
Open Barrel Contact
A
B
[ 16.26 ]
0.64
[ 3.81 ]
0.15
[ 7.35 ]
0.29
[ 17.27 ]
0.68
[ 3.81 ]
0.15
[ 6.35 ]
0.25
A
Closed Barrel Contact
[ 3.1 ]
0.12 A
Housing end
[ 19.1 ]
0.75
[ 6.4 ]
0.25
[ 3.6 ]
0.14
[ 6.1 ]
0.24
[ 6.1 ]
0.24
Open Barrel Premate Contact
PP15-45 Tin Plated Power Contacts
Offercosteffectiveperformanceupto1,500matingcycles.Seespecicationsandtemperature
charts for amperage ratings by wire size.
Dimensions
MatingLoosePieceReeled-A-
Barrel AWG mm² Force -------- Part Numbers ------- inches mm
MinimumQuantity....................................... 200 5,000.........................
Open 14to10K* 2.1to5.3 High 269G3-LPBK 269G3 0.21 5.33
Open 14to10K* 2.1to5.3 Low 261G2-LPBK 261G2 0.20 5.08
Open 14to10SF* 2.1to6.0 High 201G1H-LPBK 201G1H 0.24 6.10
Open 14to10SF* 2.1to6.0 Low 200G1L-LPBK 200G1L 0.24 6.10
Open 16to12 1.3to3.3 High 269G1-LPBK 269G1 0.18 4.57
Open 16to12 1.3to3.3 Low 261G1-LPBK 261G1 0.18 4.57
Open 20to16 0.52to1.3 High 269G2-LPBK 269G2 0.16 4.06
Open 20to16 0.52to1.3 Low 262G1-LPBK 262G1 0.16 4.06
K*-For#10AWGclassKstrandedwireorsmaller.Forlargerwiresusesuperexcontacts.
SF*- Indicates wires with high stranding such as Super Flex.
PP15-45 Silver Plated Power Contacts
Maximize performance by offering up to 10,000 mating cycles and are recommended for circuit interrupt or
hotplugapplications.Seespecicationsandtemperaturechartsforamperageratingsbywiresize.Onlyclosed
barrel contacts are suitable for soldering.
Dimensions
Mating LoosePiece Reeled - A - - B -
Barrel AWG mm² Force ------- Part Numbers -------- Part Numbers inches mm inches mm
MinimumQuantity..........................................5,000 200 5,000.................................................
Open 14to10K* 2.1to5.3 Low - 261G3-LPBK 261G3 0.20 5.08 - -
Open 14to10SF* 2.1to6.0 Low - 200G3L-LPBK 200G3L 0.24 6.10 - -
Open 20to16 0.52to1.3 Low - 262G2-LPBK 262G2 0.16 4.06 - -
Closed 16to12 1.3to3.3 Low 1331-BK 1331 - 0.15 3.81 0.10 2.54
Closed 20to16 0.52to1.3 Low 1332-BK 1332 - 0.12 3.05 0.07 1.78
K*-For#10AWGclassKstrandedwireorsmaller.Forlargerwiresusesuperexcontacts.
SF*- Indicates wires with high stranding such as Super Flex.
45A Premate Ground Wire Contacts
Tin or silver plated contacts are rated for ground or power. Hand tools are available for loose piece
contacts. Reeled contacts can be used with high volume press and applicator tooling. Tin contacts
are rated for up to 1,500 mating cycles. Silver contacts are rated up to 10,000 mating cycles.
Reeled
Mating LoosePiece Part
Type AWG mm² Force - Part Numbers - - Numbers -
MinimumQuantity............................................. 200  5,000.....
Open,Tin 14to10 2.1to6.0 Low 1830G1-LPBK 1830G1
Open,Silver 14to10 2.1to6.0 Low 1830G2-LPBK 1830G2
25A Right Angle PCB Contacts Tin Plated
Suitableforrightangleapplicationsupto25Aperpole.Tinplatingenhancessolderability.
Cannot be mixed with 45A PCB contacts. For mating with wire contacts only.
Dimensions
Mating LoosePiece -A- -B-
Row Force ------- Part Numbers ------- inches mm inches mm
Minimum Quantity ... 1,000 100 ...................................................
Top Low 1377G1-BK 1377G1 0.59 14.80 1.52 38.60
High 1317G1-BK 1317G1
Bottom Low 1377G2-BK 1377G2 0.29 7.20 1.36 34.50
High 1317G2-BK 1317G2
Top Low 1377G11-BK 1377G11 0.59 14.80 1.21 30.70
High 1317G11-BK 1317G11
Bottom Low 1377G12-BK 1377G12 0.29 7.20 1.01 25.70
High 1317G12-BK 1317G12
25A Vertical PCB Contacts Tin Plated
Formatingwithwirecontactsonly.Suitableforverticalapplicationsupto25Aperpole,
tin plating enhances solderability.
Dimensions
Mating LoosePiece - A -
Force ---------------- Part Numbers --------------- inches mm
Minimum Quantity .... 1,000 100 .......................
Low 1377G3-BK 1377G3 2.22 56.40
High 1317G3-BK 1317G3 2.22 56.40
Low 1377G4-BK 1377G4 1.76 44.70
High 1317G4-BK 1317G4 1.76 44.70
Low 1377G13-BK 1377G13 1.17 29.70
High 1317G13-BK 1317G13 1.17 29.70
See website for PCB layout drawing.
[ 9.9 ]
0.39
A
B
Use mounting staples with right angle contacts
(see accessories).
Open Barrel Contact
[ 17.2 ]
0.68
[ 3.6 ]
0.14
[ 6.4 ]
0.25
A
[ 3.6 ]
0.14
-22- All Data Subject To Change Without Notice
www.andersonpower.com
SECTION 2
Powerpole® PP15 to 45
45A Right Angle and Vertical PCB Contacts Tin Plated
Suitable for right angle or vertical applications up to 45A per pole. Tin plating
enhancessolderability.Rightanglecontactscannotbemixedwith25APCB
contacts. For mating with wire contacts only.
LoosePiece
Description ----------- Part Numbers -----------
Minimum Quantity ............. 1,000 100 ....................
Vertical 3-5911P1 1335G1
RightAngleBottomRow 3-5912P1 1336G1
RightAngleTopRow 3-5913P1 1337G1
45A Premate Ground PCB Contacts
Right angle contacts are suitable for power or ground. Use to mate with 45A
ground wire contacts. Tin plated contacts are rated up to 1,500 mating cycles.
Can be used with other 45A PCB connectors in the bottom row.
Mating LoosePiece 
Force ------- Part Numbers -------
Minimum Quantity ................... 1000 100 ....
PCB,BottomRowLow 3-5952P11836G1
Pre-mate wire
connector
[ 45.3 ]
1.78 [ 41.2 ]
1.62
[ 14.7 ]
0.578
[ 7.9 ]
0.31 TYP
[ 8.4 ]
0.33 TYP
[ 7.9 ]
0.31
[ 28.1 ]
1.11
[ 5.6 ]
0.22
[ 3.6 ]
0.14
Mated Pair
| PP15-45 ULTRASONICALLY BONDED ASSEMBLIES |
Assemblies feature housings that are ultrasonically welded to create a one piece connector unit using an APP special process. After welding, retaining pins are
no longer required to secure the stacked housings to each other. This allows Powerpole® 15-45 connectors to be used as a durable one piece connector header.
Contactcustomerserviceforcongurationsnotshownbelow.
Single Row 1x2 Assemblies
Housings with Housings with
45A Vertical 45A Right Angle Color & Type
Circuit Description Housings Only PCB Contacts PCB Contacts Position Matrix
MinimumQuantity................................ 500 500 500..... 1 2
DC2WireStandardHousings ASMPP30-1X2-RK ASMPV45-1X2-RK ASMPR45-1X2-RK RED/STD BLK/STD
DC2WireReverseStandardHousings ASMPP30-1X2-KR ASMPV45-1X2-KR ASMPR45-1X2-KR BLK/STD RED/STD
DC2WireFingerProof ASMFP30-1X2-RK ASMFV45-1X2-RK ASMFR45-1X2-RK RED/FP BLK/FP
DC2WireFingerProofReverse ASMFP30-1X2-KR ASMFV45-1X2-KR ASMFR45-1X2-KR BLK/FP RED/FP
Single Row 1x3 Assemblies
Housings with Housings with
45A Vertical 45A Right Angle Color & Type
Circuit Description Housings Only PCB Contacts PCB Contacts Position Matrix
MinimumQuantity................................ 500 500 500..... 1 2 3
DC2WireFingerProofwithGround ASMFP30-1X3-KER N/A ASMFR45-1X3-KER BLK/FP GRN/GND RED/FP
ACSinglePhaseFingerProof ASMFP30-1X3-KEW ASMFV45-1X3-KEW ASMFR45-1X3-KEW BLK/FP GRN/GND WHT/FP
Two Row 2x1 Assemblies
Housings with Housings with
45A Vertical 45A Right Angle Color & Type
Circuit Description Housings Only PCB Contacts PCB Contacts Position Matrix
MinimumQuantity................................ 500 500 500.... 1 2
DC2WireFingerProof ASMFP30-2X1-KR ASMFV45-2X1-KR ASMFR45-2X1-KR BLK/FP RED/FP
DC2WireFingerProofMate ASMFP30-2X1-RK ASMFV45-2X1-RK ASMFR45-2X1-RK RED/FP BLK/FP
Two Row 2x2 Assemblies
Housings with Housings with
45A Vertical 45A Right Angle Color & Type
Circuit Description Housings Only PCB Contacts PCB Contacts Position Matrix
MinimumQuantity................................ 500 500 500..... 1 2 3 4
AC3Phase,3WireFingerProof ASMFP30-2X2-KRWE N/A N/A BLK/FP RED/FP WHT/FP GRN/GND
AC3Phase,3WireFingerProofMate ASMFP30-2X2-WEKR N/A ASMFR45-2X2-WEKR WHT/FP GRN/GND BLK/FP RED/FP
Type
STD=StandardHousingFP=FingerProofHousingGND=GroundHousing
SingleRow1x2AssemblySingleRow1x3AssemblyTwoRow2x1AssemblyTwoRow2x2Assembly
1 2 1 2 3
1 2
3 4 Hood Up
1
2
[ 5.1 ]
0.20
[ 7.9 ]
0.31
TYP
[ 29.7 ]
1.17
REF
[ 7.9 ]
0.31
TYP
Vertical [ 36.5 ]
1.44
[ 28.6 ]
1.13
[ 5.8 ]
0.23 [ 16.3 ]
0.64
Right Angle Contact
Horizontal (top), Cat.No. 1337G1
Right Angle Contact
Horizontal (bottom)
Cat.No. 1336G1
PP15/45 Housings
(1327 Series)
Use mounting staples with right angle
contacts (see accessories).
-23-
All Data Subject To Change Without Notice www.andersonpower.com
Powerpole® Pak connector shells enclose stacked
groupings of PP15-45 sized housings in a durable black
shell for a nished connector appearance and additional
features.Inline,panelmount,andblindmatecongurations
are available. Plug shells offer the option of integral latches
and strain relief to help secure your connection.
• Package Groupings of PP15-45 Connectors
Provides a nished appearance while protecting the individual
connectors with an outer shell
• Inline, Panel Mount, “T” or Blindmate Congurations
Allows one connection system to meet multiple needs
• Optional Latching and Strain Relief
Secures your connection and wires
| Powerpole® Pak ORDERING INFORMATION |
Plug Shell without Latch
Can mate inline with other plug shells with or without latches, or mate to a panel
mount receptacle. For use with Powerpole® wire connectors only. Cable Clamp
and Hardware Pak or Retaining Pins must be ordered separately.
Dimensions
- A -
Description -------------- Part Numbers -------------- inches mm
MinimumQuantity...1,000 500 25.............................
Black,2-4Poles 1461G1-BK - 1461G1 1.24 31.50
Black,5-6Poles - 1461G2-BK 1461G2 1.56 39.62
Black,7-8Poles - 1461G3-BK 1461G3 1.87 47.50
For environmentally sealed connector shells to hold Powerpole®
15-180 connectors, see SPEC Pak® product series on our
website, www.andersonpower.com
Snap-in
T-Pak Plug shell
without latch
Plug shell
with latch
Blindmate
Powerpole® Pak Connectors
- PP15 to PP45
Powerpole® housings and contacts are sold separately.
Seepage20fororderinginformation.
SECTION 2
Powerpole® Pak
A
Retaining Pin
[ 53.09 ]
2.09
[ 21.59 ]
0.85
[ 49.28 ]
1.94
Side View Top View
MaxwireO.D.for2-4poleplugshellsis0.60inches[15.2mm²].
Forallotherplugshellsis0.63inches[16.0mm²].
Side View
Top View
C
D
B
Retaining Pin
[ 21.59 ]
0.85
NOTE: Retaining pins are used to secure and position
Powerpole® housings in one of three positions in plug shells.
Plug Shell with Latch
Can mate inline with other plug shells without latches, or mate to a panel mount receptacle. For use
with Powerpole® wire connectors only. Cable Clamp and Hardware Pak or Retaining Pins must
be ordered seperately.
Dimensions
- B - - C - - D -
Description ------------- Part Numbers -------------- inches mm inches mm inches mm
MinimumQuantity.....1,000 500 25................................................................................
Black,2-4Poles 1460G1-BK - 1460G1 1.94 49.28 2.25 57.15 1.24 31.50
Black,5-6Poles - 1460G2-BK 1460G2 1.94 49.28 2.25 57.15 1.56 39.62
Black,7-8Poles - 1460G3-BK 1460G3 1.94 49.28 2.25 57.15 1.87 47.50
Black,9-10Poles - 1460G4-BK 1460G4 2.51 63.75 2.82 71.63 1.84 46.74
-24- All Data Subject To Change Without Notice
www.andersonpower.com
SECTION 2
Powerpole® Pak
PlugShellWithLatchShown
Shell, housing and contacts
are sold separately.
Retaining Pin
Conduit Clamp
With Screws
Retaining Pin
[ 27.94 ]
1.10
[ 1.78 ]
0.07 [ 19.56 ]
0.77
E
NOTE: Retaining pins are used to secure and
position Powerpole® housings in one of two
positions in receptacle shells.
Retaining Pin
Cable Clamp
With Screws
Shell, housing and contacts
are sold separately.
PlugShellWithoutLatchShown
Shell and housing are
sold separately.
Clamp
Retaining
Pins
Screws
NOTE: Max wire O.D. for
1460G23is0.80inches
[20.3mm²].
[ 81.5 ]
3.21
[ 26.1 ]
1.03
[ 51.4 ]
2.02
[ 73.5 ]
2.90
[ 21.5 ]
0.85
Plug Shell with Latch & Non-Conductive Strain Relief
New2X3Powerpole® Pak offers an improved ergonomic shell for easier latch operation as
well as a plastic, non-conductive strain relief. The new strain relief can accommodate up
to a 6 conductor #10 AWG cable. Can mate to a panel mount receptacle. For use with
Powerpole® wire connectors only. Cable Clamp and Hardware Pak or Retaining Pins
mustbeorderedseparately.Tobeusedwith115G23cableclamponly.
Description -------- Part Numbers -------
MinimumQuantity.. 1,000 25... 
Black,5-6Poles 1460G23-BK 1460G23
Snap-in Receptacle Shell
Mate to plug shells with or without latches, or mate to another panel mount receptacle to create a bulkhead to
bulkhead connection. For use with Powerpole® wire or PCB connectors. Order the number of retaining pins for
each receptacle as shown below separately.
Number of Dimensions Knock Out Size
Retaining Pins - E - - Width -
Description ---------------- Part Numbers ---------------- to Order inches mm inches mm
MinimumQuantity...1,000 500 25...............................................................................
Black,2-4Poles 1470G1-BK - 1470G1 1 1.50 38.10 1.25 31.75
Black,5-6Poles - 1470G2-BK 1470G2 2 1.88 47.75 1.62 41.15
Black,7-8Poles - 1470G3-BK 1470G3 3 2.13 54.10 1.88 47.75
Black,9-10Poles - 1470G4-BK 1470G4 4 2.44 61.98 2.19 55.63
*Height=[25.4mm]1.0in.
Cable Clamp & Hardware Pak
Includescableclamp,2screws,andrequiredamountofretainingpinsforeachconguration.
Screw Head Cable
Description Type Type ------------ Part Numbers ------------
MinimumQuantity...................................1,000 500 25...
2-4Poles StraightSlot Bundled 115G1-BK - 115G1
5-6Poles StraightSlot Bundled 115G2-BK - 115G2
7-8Poles StraightSlot Bundled 115G3-BK - 115G3
9-10Poles StraightSlot Bundled - 115G4-BK 115G4
2-4Poles Philips Bundled 115G7-BK - 115G7
5-6 Poles Philips Bundled 115G8-BK - 115G8
Cable Clamp & Hardware Pak
Includes2cableclamphalves,2screwsand2retainingpins.Tobeusedwith
1460G23PlugShellonly.
Screw Head Cable
Description Type Type ------ Part Numbers ------
Minimum Quantity ............................…… 1,000 25
5-6Poles Philips Bundled 115G23-BK 115G23
Flexible Conduit Clamp & Hardware Pak
Includescableclamp,2screws,andneedamountofretainingpinsforeachconguration.
Description - Part Number -
Minimum Quantity ...... 100 ......
2-4Poles 110G10
Retaining Pin for Snap-in Receptacle
Order the number of retaining pins for each receptacle shown in the Snap-in Receptacle
Shell ordering information. Pins are also required for the plug side when the Cable Clamp &
Hardware Pak is not ordered.
Description ----- Part Number ------
Minimum Quantity ..... 1,000 100 ...
RetainingPin 110G9-BK 110G9
-25-
All Data Subject To Change Without Notice www.andersonpower.com
[ 102.2 ]
4.03
[ 86.2 ]
3.39
[ 85.8 ]
3.38
[ 53 ]
2.09
[ 43.2 ]
1.70
[ 51.1 ]
2.01
Blindmate Pak Connector
Ideal for panel to panel, bulkhead to bulkhead, or rack mount applications that require the
powerconnectortocompensateforupto0.45in.[11.43mm]ofmisalignmentineitheraxis.
EightpositionscanbelledwithPowerpole® 10-45 connectors. The receptacle side can be
used with wire or PCB contacts. Hardware bag includes retaining pins.
Description ---------- Part Numbers ----------
MinimumQuantity....................................................50 25..........
2x4BlindmatePlugShell,Hardware&Pins - BMPP10-45P
2x4BlindmateReceptacleShell,Hardware&Pins - BMPP10-45R
2x4BlindmatePlugShell BMHSG-P -
2x4BlindmateReceptacleShell BMHSG-R -
Hardware Bag Plug Side - 110G50
Hardware Bag Receptacle Side - 110G51
“T” Pak 2 Way Splitter
The Powerpole®“T”Pakconnectorisa2wayelectricalsplitterthatsplitselectricalcurrentfrom
oneincomingcircuitintotwooutgoingcircuits.Thestandardcongurationispre-wiredforAC
3phase,3wireplusgroundcongurations.The“T”PakcanalsobeusedforACsinglephase
plusgroundorDC2wireplusgroundapplicationsbynotusingeithertheredorwhitepower
positions.“T”Pakispre-wiredfromthefactoryallowingplugandplayfieldinstallation
ofmodularofceandindustrialequipment.ULrecognitionupto20ampsand600voltsis
achieved when mating Powerpole®Pakplugswith#12AWGwire.
ForOEMmanufacturingscaleapplications,the“T”Pakcanbeloadedwithcustom
congurationsofanyofourngerproof,standard,orgroundhousingsandcontacts
in the PP15-45 series. Contact sales or customer service for additional information.
Description - Part Numbers -
Minimum Quantity ............................ 80 ........
Assembled“T”Pak 20-01
MatingPlugShellwithLatch2x2 26-01
MatingPlugShellwithoutLatch2x2 27-01
StandardcongurationforeachsideoftheTincludes(1)eachRed,Black,andWhiteStandard
PP15-45Housings&261G2-LPBKcontactswith(1)45AGreenPremateGroundHousingand
1830G1-LPBKcontact.
Mating plug shells include (1) each Red, Black, and White Standard PP 15-45 Housings &
(3)261G2-LPBKcontactswith(1)45AGreenPremateGroundHousingand1830G1-LPBK
contact. Cable clamp & hardware pak also included.
[ 88.6 ]
3.49
[ 76.4 ]
3.01
[ 5.0 ]
Ø 0.20 4 [ 38.6 ]
1.52
[ 58.93 ]
2.320 [ 24.38 ]
0.960
[ 13.46 ]
0.530
[ 3.05 ]
0.120
[47.24]
1.860
[ 36.7 ]
1.45
[ 50.8 ]
2.00
Plug Outline Receptacle Outline
[ 30.2 ]
1.19
[21.5]
0.85
[4.4]
0.17
[ 29.14 ]
1.147
[ 36.7 ]
1.45
[ 0.64 ]
0.025
[ 0.64 ]
0.025
A
BC
SECTION 2
Powerpole® Pak
Mates With B Mates With A & C
27-0126-01
See our innovative MARC Connector that offers straight-on or rotational blindmate capability. MARC
holds 6 PP15/45 power contacts and 2 PP15/45 premate ground contacts in a high temperature hous-
ing. Visit our website, www.andersonpower.com to learn more.
-26- All Data Subject To Change Without Notice
www.andersonpower.com
| PP15-45 & POWERPOLE® PAK SPECIFICATIONS |
SECTION 2
Powerpole® PP15 to 45
Electrical
Current Rating Amperes ¹ UL 1977 CSA/TUV
Singlepole Wire to Wire (10 AWG) 55 40
SinglepoleGroundWiretoWireorPCB(10AWG)45 35
3x3BlockWiretoWire(10AWG) 40 27
Singlepole25APCBtoWire(12AWG) 25 -
2x3Block25APCBtoWire(12AWG) 25 22*
Singlepole 45A PCB to Wire (10 AWG) 45 40 *
2x3Block45APCBtoWire(10AWG) 45 25*
Voltage Rating AC/DC
UL1977 600
Dielectric Withstanding Voltage
VoltsAC 2,200
Avg. Mated Contact Resistance Milliohms ¹
15AWireContactwith5/8”of#16AWG 0.875
30AWireContactwith5/8”of#12AWG 0.600
45AWireContactwith5/8”of#10AWG 0.525
45A PCB Contact to Contact 0.500
25APCBContacttoContact 0.600
UL Hot Plug Current Rating Amperes 5
250cyclesat72VDC 45A
250cyclesat120VDC 30A
UL Ground Short Time Current Test - 45A Premate Ground
750 Amps, #10 AWG Wire 4 Seconds
470Amps,#12AWGWire 4Seconds
Mechanical
Wire Size Range AWG mm²
20to10 0.75to6.0
Max. Wire Insulation Diameter in. mm
0.175 4.450
Operating Temperature ² °F °C
Powerpole® Housings & Powerpole®PakShells -4°to221° -20°to105°
Mating Cycles No Load by Plating Silver (Ag) Tin (Sn)
PCB to Wire - 1,500
Wire to Wire 10,000 1,500
Avg. Mating / Unmating Force Lbf. N
LowForceWire,HighForcePCB,&Ground 3 13
HighForceWire 5 22
LowForcePCB 2 9
Min. Contact / Spring Retention Force Lbf. N
20 90
Powerpole® Pak Latch Avg. Defeat Force Lbf. N
150 667
PCB Specications
Mounting Style Plated Through Hole
PCBThickness-in.[mm] 0.090-0.150 (2.3-3.8)
25APCBRecommendedTraces #12AWGCrossSection
45A PCB Recommended Traces #10 AWG Cross Section
Mechanical Shock 4
MIL-STD-202 213ConditionA 50g’s
Vibration High Frequency 4
MIL-STD-202 204ConditionA 10g’s
Materials
Housing
Plastic Resin Polycarbonate
Contact Retention Spring Stainless Steel
Housing Flammability Rating
UL94 V-0
GlowWire 825°C(GWFI)/800°C(GWIT)
Contact
Base Copper Alloy
Plating Tin or Silver
Contact Termination Methods
Crimp ³ Wire Contacts
HandSolder 1331,1332&PCBContacts
Solder Dip PCB Contacts
Wave Solder PCB Contacts
Protection
Touch Safety with Finger Proof Housings & Wire
Contacts or PCB Mating Interface
UL1977Sec.10.2 Pass
IEC60950 Pass
IEC60529 IP20
Touch Safety Standard Housings
IEC60529 IP10
NOTE 1: See IEC 60664-1 for working voltage.
NOTE2:Ampratingsarestatedperpositionandbasedonallpositionsbeingfullyloaded.
* No TUV Recognition
1 Basedon:105°Cratedorbettercableofthelargestsize,ProperlycalibratedAPPrecommendedtooling,anda25°Cambienttemperature.ULratingnot
toexceedthemaximumoperatingtemperature.CSAratingbelowa30°Ctemperaturerise.
2Limitedbythethermalpropertiesoftheconnectorplastichousing.
3UseAPPrecommendedtoolingonly.AlternatetoolsmayadverselyaffecttheperformanceofourconnectorsalongwithULandCSArecognition.
4Testedwithcontactpartnumber261G2.
5Basedon2housingsblockedtogether.
Unmated 1.64 mm
Mated 1.64 mm
Unmated 1.64 mm
Mated 1.64 mm
Unmated 1.64 mm
Mated 1.64 mm
Unmated 1.39 mm
Mated 1.39 mm
Connector
Series Configurations
PP15/45
Standard
IIIa
Stacked Powerpole
PCB - 45A
PCB - 25A
Single Pole
Material
Group
Unmated
1.64 mm
Mated
4.20 mm
Unmated
1.64 mm
Mated
4.20 mm
Unmated
1.64 mm
Mated
2.90 mm
Unmated
1.39 mm
Mated
1.39 mm
Connector
Series Configurations
PP15/45
Finger Proof
IIIa
Stacked Powerpole
PCB - 45A
PCB - 25A
Single Pole
Material
Group
Creepage /
Clearance
per IEC 60950-1
Creepage /
Clearance
per IEC 60950-1
®
®
-27-
All Data Subject To Change Without Notice www.andersonpower.com
| PP15-45 TEMPERATURE CHARTS |
25
50
75
100
125
0 5 10 15 20 25 30 35 40
PP25 PCB
Derating vs. Ambient Temperature
Ambient Temperature (°C)
Amperes Applied
Singlepole 2-Pole Multipole
PP45 PCB
Derating vs. Ambient Temperature
25
50
75
100
125
0 10 20 30 40 50 60 70
Amperes Applied
Singlepole 2-Pole Multipole
Ambient Temperature (°C)
PP15-45 Singlepole
Derating vs. Ambient Temperature
25
50
75
100
125
0 10 20 30 40 50 60 70
Amperes Applied
10 AWG 12 AWG 14 AWG
16 AWG 18 AWG 20 AWG
Ambient Temperature (°C)
25
50
75
100
125
0 10 20 30 40 50
PP15-45 Multipole
Derating vs. Ambient Temperature
Amperes Applied
10 AWG 12 AWG 14 AWG
16 AWG 18 AWG 20 AWG
Ambient Temperature (°C)
SECTION 2
Powerpole® PP15 to 45
0
10
20
30
40
50
60
0 10 20 30 40 50 60
PP15-45 Singlepole
Temperature Rise at Constant Current
Amperes Applied
10 AWG 12 AWG 14 AWG
16 AWG 18 AWG 20 AWG
Temperature Rise
Above Ambient (°C)
PP15-45 Multipole
Temperature Rise at Constant Current
Amperes Applied
10 AWG 12 AWG 14 AWG
16 AWG 18 AWG 20 AWG
10
20
30
40
50
60
0
0
10 20 30 40
Temperature Rise
Above Ambient (°C)
0
10
20
30
40
50
60
0 5 10 15 20 25 30 35 40
PP25 PCB
Temperature Rise at Constant Current
Amperes Applied
Singlepole 2-Pole Multipole
Temperature Rise
Above Ambient (°C)
0
10
20
30
40
50
60
0 10 20 30 40 50 60
PP45 PCB
Temperature Rise at Constant Current
Amperes Applied
Singlepole 2-Pole Multipole
Temperature Rise
Above Ambient (°C)
NOTE:PP25PCBchartsbasedon0.002in²foilonboardside,matedto#12AWGconductoronwireside.PP45PCBchartsbasedon#10AWGequivalentcopper
foil on board side, mated to #10 AWG conductor on wire side.
ForTemperatureRiseAbove60°C,ConsulttheExtendedTemperatureRiseChartsintheAppropriateProductSectionontheWebsite.
Current-TemperatureDeratingperIEC60512-5-2Test5B
ForTemperatureRiseAbove60°C,ConsulttheExtendedTemperatureRiseChartsintheAppropriateProductSectionontheWebsite.
Current-TemperatureDeratingperIEC60512-5-2Test5B
Temperaturerisechartsarebasedona25°Cambienttemperature.
-28- All Data Subject To Change Without Notice
www.andersonpower.com
| Powerpole® 15-45 Accessories |
[ 16.6 ]
0.655
[ 7.9 ]
0.312
[ 24.6 ]
0.968
[ 7.9 ]
0.312
[ 16.6 ]
0.655
[ 7.9 ]
0.312
ShortwithHoleShortwithoutHoleLong
2or4Pole3or6Pole4or8Pole
A
B
SECTION 2
Powerpole® PP15 to 45
Mounting Wing
Secure dovetailed Powerpole® 15-45 series housings by passing fasteners through the wings
in either a horizontal or vertical orientation. Useful for sheet metal panels, printed circuit boards,
and many other mounting surfaces. Fasteners not included.
Description ------- Part Numbers -------
MinimumQuantity...2,500 100....
Red 1399G9-BK 1399G9
Blue 1399G8-BK 1399G8
Spacer
Used to separate housings under high power to minimize derating. They are
recommended for squaring off a block of Powerpole® 15-45 housings for use in connector shells
and mounting clamps. Use a combination of long and short spacers opposite each other in a
mated block to add keying features or use two short spacers to avoid interference. Spacers with
holes can also be used to fasten the blocked housings to a surface with a fastener.
Description ------ Part Numbers -------
MinimumQuantity.....2,500 100 .....
Red,Shortw/Hole 1399G1-BK 1399G1
Red,Long 1399G2-BK 1399G2
Red,Short 1399G6-BK 1399G6
Black,Long 1399G10-BK 1399G10
Blue,Short 1399G13-BK 1399G13
White,Shortw/Hole 1399G14-BK 1399G14
White,Long 1399G17-BK 1399G17
Retaining Pins
Keep stacked Powerpole® 15-45 series housings from separating. Retaining pins are inserted in
the circular opening between two housings stacked side by side.
Dimensions
- A - - B -
Description ----- Part Numbers ----- inches mm inches mm
Minimum Quantity ... 1,000 100 ............................................................................
1BlockHigh H1507P38 110G16 0.093/0.103 2.360/2.62 0.250 6.350
2BlockHigh 111812P5 110G17 0.093/0.103 2.360/2.62 0.440 11.180
Mounting Clamp
Mounting clamps can be used for fastening a block of Powerpole® 15-45 series
housings to a panel. Connector blocks must be a complete square for the clamps
to work properly. Fastening hardware not included.
Description -- Part Numbers --
MinimumQuantity...100setsof2.....
2or4Pole 1462G1
3or6Pole 1462G2
4or8Pole 1462G3
Mounting Wings
[ 16.7 ]
0.66
[ 7.9 ]
0.31
[ 4.6 ]
0.18 SQ
-29-
All Data Subject To Change Without Notice www.andersonpower.com
A
B
SECTION 2
Powerpole® PP15 to 45
For environmentally sealed connector shells to hold Powerpole®
15-180 connectors, see SPEC Pak® product series on our
website, www.andersonpower.com
PCB Mounting Staples
PCB staples are soldered into place to secure Powerpole® 15-45 series housings
ina horizontal congurationtotheboard.Reducestrain on solderingjointsduring
mating and unmating.
Dimensions
Part - A - - B -
Numbers HxW Lengthinches mm inches mm
Minimum Quantity 100 ................................................................................
114555P1 1x1 Short 0.47 12.0 0.28 7.0
114555P2 1x2 Short 0.47 12.0 0.57 14.5
114555P3 1x3 Short 0.47 12.0 0.89 22.5
114555P7 1x4 Short 0.47 12.0 1.20 30.5
114555P10 2x1 Short 0.79 20.0 0.28 7.0
114555P6 2x2 Short 0.79 20.0 0.57 14.5
114555P9 2x2 Long 0.91 23.0 0.57 14.5
Retention Clip
Retention clips prevent Powerpole® 15-45 blocks from unintended disconnects.
They feature a tab for easy insertion and removal.
Description -- Part Number --
Minimum Quantity ........ 100 .........
1 Block High 110G68
Block Lok
Block locks secure mated Powerpole® 15-45 series housings together. For use in
high vibration or shock applications where connectors are unmated infrequently.
Description - Part Numbers -
Minimum Quantity .......... 100 .........
2Pole,Black 110G21
4Pole,Black 110G12
Splash Boot
Splashbootsprotecta2x2blockofanycombinationofPowerpole® 15-45 series
housingsandfeaturesnipoffsealedendsforexibilityinwireO.D.Designedfor
through panel or inline applications. Not a hermetic seal.
Description - Part Numbers -
MinimumQuantity........25...........
Female, Black 1441G1
Male,Black 1442G1
2Pole4Pole
Shown without Powerpoles® Shown with Powerpoles®
2017-0041 DS-PP1545 REV C5
-43-
All Data Subject To Change Without Notice www.andersonpower.com
Powerpole®
- Tooling Information
SECTION 2
Powerpole® Tooling
AWG mm²
Loose Piece Part Numbers
Tin
Plating
Silver
Plating
Hand
Tool Die Locator
Number
of Crimps
Wire Size
or
Pneumatic
Bench
Tool
Loose Piece Contact Crimp Tool
#16 / 20
#12 / 16
#16 / 20
#16 / 20
#12 / 16
#10 / 14
#12 / 16
#10 / 14
#10 / 14
#10 / 14
310 / 14
1.3 / 0.52 N/A 1332
3.3 / 1.3 N/A 1331
1.3 / 0.52 262G1-LPBK 262G2-LPBK
1.3 / 0.52 269G2-LPBK N/A
3.3 / 1.3 261G1-LPBK N/A
5.3 / 2.1 261G2-LPBK 261G3-LPBK
3.3 / 1.3 269G1-LPBK N/A
5.3 / 2.1 269G3-LPBK N/A
5.3 / 2.1 200G1L-LPBK 200G3L-LPBK
5.3 / 2.1 201G1H-LPBK N/A
5.3 / 2.1 1830G1-LPBK 1830G2-LPBK
#8 8.4
1/0 53.5 1323G2
#1 42.4 1323G1
#2 33.6 1319
#4 21.2 1319G4
#6 13.3 1319G6
3/0 85 1328G2 1303G12
2/0 53.5 1328G1
1303G13
#1 42.4 1347
#6 13.3 1348 1387G1 1388G4 1389G3 Single
1. NOTE: See website for the most current information.
2. NOTE: Insertion / Extraction fool for PP15/45 contacts = 111038G2
Double
1309G2
or
1309G8
1367G1
N/A
1309G3
or
1309G8
1309G6
or
1309G8
Single
1387G1
1388G6
N/A SingleN/A
#6 13.3
1309G4
#10 / 12 5.3 / 3.3
N/A
N/A 1368
Series
1387G1
1387G2
1388G4
1389G4
1388G3
1304G32
1/0 53.5 1382
#2
N/A 1368
Series
Single
1388G7
33.6 1383
#4 21.1 1384
or
++
* APP applicators are mechanical feed style and do not require an air feed kit.
PP180
PP120
PP75
PP15 / 45 Flat Wiping Power & Ground
1307
5900
1875G1
5952
1875G2
5953
5915
1875G3
1389G21
1389G6
1389G21
1389G6
1389G21
1389G6
#16 / 20 1.3 / 0.52 262G1 262G2
#16 / 20 1.3 / 0.52 269G2 N/A
#12 / 16 3.3 / 1.3 261G1 N/A
#10 / 14 5.3 / 2.1 261G2 261G3
#12 / 16 3.3 / 1.3 269G1 N/A
#10 / 14 5.3 / 2.1 269G3 N/A
#10 / 14 5.3 / 2.1 200G1L 200G3L
#10 / 14 5.3 / 2.1 201G1H N/A
#10 / 14 5.3 / 2.1 1830G1 1830G2
TD0101
115V= TE0101
230V = TE0102
TD0102
AWG mm²
Reeled Part Numbers
Tin
Plating
Silver
Plating
APP
Applicator
Wire Size Reeled Contact Crimp Tool
PP15 / 45 Flat Wiping Power & Ground
APP Press
NOTE: Insertion / Extraction tool for PP15/45 contacts = 111038G2