18
Eaton’s Cutler-Hammer
Series G Moulded Case Circuit Breakers, 15 - 630 A
www.chscontrols.se
Earth Leakage Modules for LG Frame MCCBs, bottom mounted
Rated Rated
current voltage Pickup Time Alarm contacts
In, A Un, VAC Poles Standard setting, A Delay, s Earth fault levels Catalogue numbers
400 230-415 3 IEC 0,03-10 Inst.-1 50/100% ELLBE3400W
400 230-415 4 IEC 0,03-10 Inst.-1 50/100% ELLBE4400W
630 230-415 3 IEC 0,03-10 Inst.-1 50/100% ELLBE3630W
630 230-415 4 IEC 0,03-10 Inst.-1 50/100% ELLBE4630W
400 120-480 3 UL/CSA 0,03-10 Inst.-1 50/100% ELLBN3400W
400 120-480 4 UL/CSA 0,03-10 Inst.-1 50/100% ELLBN4400W
600 120-480 3 UL/CSA 0,03-10 Inst.-1 50/100% ELLBN3600W
600 120-480 4 UL/CSA 0,03-10 Inst.-1 50/100% ELLBN4600W
Terminals, Installation Accessories for LG Frame MCCBs see note 40, 41
Description Catalogue numbers
Terminal for Cu/Al cond., pressure type, 400 A, 35-240 mm2/AWG 2-500 TA350LK, included
Terminal for Cu cond., pressure type, 400 A, 35-240 mm2/AWG 2-500 T350LK
Terminals for Cu/Al cond., pressure type, 400 A, 240-380 mm2/kcmil 500-750, kit of 3 3TA631LK
Terminals for Cu cond., pressure type, 400 A, 240-380 mm2/kcmil 500-750, kit of 3 3T631LK
Terminals for Cu/Al cond., pressure type, 400 A, 240-380 mm2/kcmil 500-750, kit of 4 4TA631LK
Terminals for Cu cond., pressure type, 400 A, 240-380 mm2/kcmil 500-750, kit of 4 4T631LK
Terminals for Cu/Al cond., pressure type, 630 A, 2*35-240 mm2/AWG 2*2-500, kit of 3 3TA632LK, included
Terminals for Cu cond., pressure type, 630 A, 2*35-240 mm2/AWG 2*2-500, kit of 3 3T632LK
Terminals for Cu/Al cond., pressure type, 630 A, 2*35-240 mm2/AWG 2*2-500, kit of 4 4TA632LK, included
Terminals for Cu cond., pressure type, 630 A, 2*35-240 mm2/AWG 2*2-500, kit of 4 4T632LK
Endcap kit for busbar/cable lugs, 3 pole, metric hardware L3RTWK
Endcap kit for busbar/cable lugs, 4 pole, metric hardware L4RTWK
Endcap kit for busbar/cable lugs, 3 pole, imperial hardware L3RTDK
Endcap kit for busbar/cable lugs, 4 pole, imperial hardware L4RTDK
Spreader, pole cc=54 mm, 3 pole, hardware not included, use endcap kit LGTEW3
Spreader, pole cc=54 mm, 4 pole, hardware not included, use endcap kit LGTEW4
Terminal shields, ingress protection IP 30, 3 pole LTS3K
Terminal shields, ingress protection IP 30, 4 pole LTS4K
Interphase barriers, 2 pcs per package IPB3
Plug-in Blocks for LG Frame MCCBs see note 22
Plug-in block for 3 pole breaker, including breaker terminals and trip-on drawout interlock PAD3L
Plug-in block for 4 pole breaker, including breaker terminals and trip-on drawout interlock PAD4L
Notes
22 Plug-in block can be installed either on or partly behind mounting plate. Rear terminal stabs are included. Stabs can be converted to front terminals.
23 See page 7 for possible installation combinations.
24 Rotary through-the-door handle, see page 24 for min and max enclosure depth.
25 Flexshaft mechanism, additional hardware may be required depending on enclosure type. Contact CHS Controls for more information.
26 Contact CHS Controls for breaker interlock kits and cylinder locks.
40 Terminal cover is included for terminals 3TA631LK, 3T631LK, 4TA631LK, 4T631LK, 3TA632LK, 3T632LK, 4TA632LK and 4T632LK.
41 Terminals TA350LK, 3TA631LK, 4TA631LK, 3TA632LK and 4TA632LK are made of aluminium. Terminals T350LK, 3T631LK, 4T631LK, 3T632LK and 4T632LK are
made of copper.
test
reset
WAR NIN G
TA632LK TA631LK TA350LK
T632LK T631LK T350LK
Endcap kit
Spreader Interphase barrier
Terminal shield