Tightening torque 0.6...1 N.m conforming to IEC 60947-1
Dielectric strength 2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
Housing material Self-extinguishing
Repeat accuracy +/- 0.5 % conforming to IEC 61812-1
Temperature drift +/- 0.05 %/°C
Voltage drift +/- 0.2 %/V
Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Reset time 350 ms on de-energisation typical
On-load factor 100 %
Power consumption in VA 0...3 VA at 240 V AC
Power consumption in W <= 1.5 W at 240 V DC
Breaking capacity 0.5 A AC/DC conforming to UL
0.7 A AC/DC at 20 °C
Operating frequency 10 Hz
Maximum output current 20 A <= 10 ms
Minimum switching current 10 mA
Leakage current < 5 mA
Maximum switching voltage 250 V AC
Voltage drop 4 V 3-wire
8 V 2-wire
Electrical durability 100000000 cycles
Marking CE
Creepage distance 4 kV/3 conforming to IEC 60664-1
Safety reliability data MTTFd = 353.8 years
B10d = 320000
Mounting position Any position in relation to normal vertical mounting plane
Mounting support 35 mm DIN rail conforming to EN/IEC 60715
Product weight 0.068 kg
Environment
Immunity to microbreaks <= 20 ms
Derating factor 5 mA/°C
Standards EN 61000-6-1
EN 61000-6-2
2004/108/EC
EN 61000-6-3
2006/95/EC
IEC 61812-1
EN 61000-6-4
Product certifications CSA
GL
cULus
Ambient air temperature for storage -30...60 °C
Ambient air temperature for operation -20...60 °C
IP degree of protection IP20 (terminal block) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529
Vibration resistance 20 m/s² (f = 10...150 Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn (duration = 11 ms) conforming to IEC 60068-2-27
Relative humidity 93 % without condensation conforming to IEC 60068-2-30
Electromagnetic compatibility Electrostatic discharge immunity test, in contact at 6 kV conforming to IEC 61000-4-2 level 3
Electrostatic discharge immunity test, in air at 8 kV conforming to IEC 61000-4-2 level 3
Susceptibility to electromagnetic fields, 80 MHz to 1 GHz at 10 V/m conforming to IEC 61000-4-3
level 3
Electrical fast transient/burst immunity test, capacitive connecting clip at 1 kV conforming to IEC
61000-4-4 level 3
Electrical fast transient/burst immunity test, direct at 2 kV conforming to IEC 61000-4-4 level 3
1.2/50 µs shock waves immunity test, differential mode at 1 kV conforming to IEC 61000-4-5 level 3
1.2/50 µs shock waves immunity test, common mode at 2 kV conforming to IEC 61000-4-5 level 3
2