6 Control Relays and Timers CA04902001E—March 2011 www.eaton.com
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40.10
Control Relays and Timers
Safety Relays
Safety Relay, continued
Description Unit ESR5-NO-31-230VAC
ESR5-NO-31-24V-
230VAC-DC ESR5-NV3_ ESR5-VE3_ ESR5-NE-51_
General
Standards EN ISO 13849-1, IEC 62061,
IEC 61508, DIN EN 50178,
UL/CUL listed
EN ISO 13849-1, IEC 62061,
IEC 61508, DIN EN 50178,
UL/CUL listed
EN ISO 13849-1, IEC 62061,
IEC 61508, DIN EN 50178,
UL/CUL listed
EN ISO 13849-1, IEC 62061,
IEC 61508, DIN EN 50178,
UL/CUL listed
EN ISO 13849-1, IEC 62061,
IEC 61508, DIN EN 50178,
UL/CUL listed
Type-dependent standards EN 60204
(if applicable)
EN 60204
(if applicable)
EN 60204
(if applicable)
——
Lifespan, mechanical—c (contacts) x 10610 10 10 10 10
Maximum operating frequency Ops/h 3600 3600 3600 900 3600
Climatic proofing Dry heat according to
EN60068-2-2, damp heat
according to EN 60068-2-3
Dry heat according to
EN60068-2-2, damp heat
according to EN 60068-2-3
Cold in accordance with:
EN 60068-2-1, dry heat in
accordance with EN
60068-2-2, humidity
storage test in accordance
with 60068-2-78
Dry heat according to
EN60068-2-2, damp heat
according to EN 60068-2-3
Dry heat according to
EN60068-2-2, damp heat
according to EN 60068-2-3
Ambient temperature °F (°C) –4° to 131° (–20° to 55°) –4° to 131° (–20° to 55°) –4° to 113° (–20° to 45°) –4° to 131° (–20° to 55°) –4° to 131° (–20° to 55°)
Ambient temperature storage °F (°C) –13° to 167° (–25° to 75°) –13° to 167° (–25° to 75°) –13° to 167° (–25° to 75°) –13° to 167° (–25° to 75°) –13° to 167° (–25° to 75°)
Mounting position Any Any Any Any Any
Vibration resistance (IEC/EN 60068-2-6) 2g, frequency: 10–150 Hz,
amplitude: 0.15 mm
2g, frequency: 10–150 Hz,
amplitude: 0.15 mm
2g, frequency: 10–150 Hz,
amplitude: 0.15 mm
2g, frequency: 10–150 Hz,
amplitude: 0.15 mm
2g, frequency: 10–150 Hz,
amplitude: 0.15 mm
Shock resistance (IEC 60068-2-27) —————
Protection type
Housing IP40 IP40 IP20 IP20 IP20
Terminals IP20 IP20 IP20 IP20 IP20
Protection against direct contact when
actuated from front (IEC 0106 Part 100)
Finger- and back-of-hand
proof
Finger- and back-of-hand
proof
Finger- and back-of-hand
proof
Finger- and back-of-hand
proof
Finger- and back-of-hand
proof
Weight kg 0.3 0.3 0.17 0.17 0.22
Terminal capacity
Solid or flexible mm21 x (0.2–2.5)
2 x (0.2–1)
1 x (0.2–2.5)
2 x (0.2–1)
1 x (0.2–2.5)
2 x (0.2–1)
1 x (0.2–2.5)
2 x (0.2–1)
1 x (0.2–2.5)
2 x (0.2–1)
Flexible with ferrule mm21 x (0.25–2.5)
2 x (0.25–1)
1 x (0.25–2.5)
2 x (0.25–1)
1 x (0.25–2.5)
2 x (0.25–1)
1 x (0.25–2.5)
2 x (0.25–1)
1 x (0.25–2.5)
2 x (0.25–1)
Solid or stranded AWG 24–12 24–12 24–12 24–12 24–12
Terminal screw
Pozidriv screwdriver Size 22222
Flat-blade screwdriver mm 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5 0.6 x 3.5
Max. tightening torque Nm 0.6 0.6 0.6 0.6 0.6
Main Contacts
Rated impulse withstand voltage—Uimp Vac 6000 6000 4000 4000 4000
Overvoltage category/pollution degree
Outside III/2 III/2 III/2 III/2 III/2
Inside —————
Rated insulation voltage—UiVac 250 250 250 250 250
Rated operating voltage—UeVac 230 230 230 230 230
Rated operation current
AC-15
230V (360 ops./h)—IeA44—54
230V (3600 ops./h)—IeA33333
DC-13
24V (360 ops./h)—IeA44—64
24V (3600 ops./h)—IeA 2.5 2.5 3 3 2.5
Max. summation current of all poles
24 Vac/Vdc devices A 50 50 49 50 50
230 Vac devices A 50 50 — — —
Square of the total current
(and total current)
of all current paths
50 A2 (4 + 4 + 4) 50 A2 (4 + 4 + 4) 50 A2 (4 + 4 + 4) 49 A2
(3.5 + 3.5 + 3.5 + 3.5)
50 A2
(3.7 + 3.7 + 3.7 + 3.7
+ 3.7)
Short-circuit protection
Max. fuse A gG/gL 6 6 10 10 6