Electrical Ratings (Catalog Symbol and Amps) IR 100kA AC
Fast-Acting 13⁄32˝ x 1 1⁄2˝ (10x38mm) Midget Fuses,
600Vac/dc, 1⁄10–30A
DCM Series
Dimensions - in (mm)
DCM-1⁄10
DCM-1⁄8
DCM-2⁄10
DCM-1⁄4
DCM-3⁄10
DCM-1⁄2
DCM-3⁄4
DCM-1
DCM-1-1⁄4
DCM-1-1⁄2
DCM-6
DCM-7
DCM-8
DCM-9
DCM-10
DCM-12
DCM-15
DCM-20
DCM-25
DCM-30
DCM-2
DCM-2-1⁄2
DCM-3
DCM-4
DCM-5
• A full range DC midget fuse.
• Melamine tube.
• Nickel-plated brass endcaps.
Designed To:
Fuses: Designed to:
DCM 1⁄10 thru 30 Carry 110% of rating for 4 hours
AC Opens at 135% of rating within 1 hour
AC Maximum Interrupting Rating of 100kA at 600Vac
DC Maximum Interrupting Rating of 50kA at 600Vdc
DC Minimum Interrupting Rating of 200% rated current
at 600Vdc,
Catalog Symbol: DCM
Fast-Acting 1⁄10-30A
UL Listed: STD. 248-14, (FILE #E19180,
GUIDE #JDYX)
CSA Certified, C22.2 NO. 248. 14 (CLASS #1422-01,
FILE #53787)
Interrupting Ratings: 100kA at 600Vac
50kA at 600Vdc
Carton Quantity and Weight
Ampere Carton Weight
Ratings Qty. Lbs. Kg.
0-30 10 0.187 0.088
Recommended fuse blocks/fuse holders
See Data Sheets listed below
• Open fuse blocks - 1104, 2104
• Finger-safe fuse holders - 1109, 1102, 1103, 2053
• Panel-mount fuse holders - 2114, 2113, 2108,
2112, 2109, 2140
• In-line fuse holders - 2127, 2126
Time-Current Characteristic Curves–Total Clearing
© 2010 Cooper Bussmann
St. Louis, MO 63178
www.cooperbussmann.com
0310 BU-SB091066 Page 1 of 1 Data Sheet 2038
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of
this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical informa-
tion that will help the end user with design applica tions. Cooper Bussmann reser ves the right, without notice, to change design or construction of
any products and to discontinue or limit distribution of any products. Cooper Bussmann also reser ves the right to change or update, without notice,
any technical informa tion contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.