Compact Circuit Protector (CCP)
UL Class CC, Midget and IEC 10x38 fuses
1212 BU-SB101428 Form No.CCP Page 1 of 12 Data Sheet 1157
Specifications:
• Box lug and spade terminal suitable for line, load or
accessory connection
• Box Lug Connection:
- 18-6 AWG (1 to 16mm2) single or dual rated, solid or
stranded – 75°C or higher - Cu only
- 4 AWG (25mm2) single – 75°C or higher - Cu only
• Spade Terminal Connection:
- Max. 30A with insulated flanged spade terminal wire size
#12 - #10 AWG for stud size #8
• Torque:
- 18-10 AWG 20 Lb-In (1-6mm2/3.4N•m)
- 8-4 AWG 35 Lb-In (10-25mm2/5.8N•m)
• Lockout/tagout: 4mm shank lock or standard pin-out devices
• 35mm DIN-Rail mount
• Dimensionally compliant to DIN 43880
• Local indication minimum operating voltage:
– 90Vac for AC version
– 12Vdc for DC version
Agency Information:
UL Class CC fuse version
• UL 98 Listed, File E302370, Guide WHTY
• cULus to CSA Standard 22.2 No. 4-04, File 302370,
Guide WHTY7
• CE Compliant
UL Midget fuse version
• UL 508 Listed
• cULus Certified 22.2 No. 14-05
• CE Compliant
10X38 IEC Class aM and gG/gL fuse version
• IEC 60947-3 AC23A
• IEC 60947-3 DC23A
• CE Compliant
Shipping Weight:
• 2.84 lbs (1.29kg) per carton
Carton Quantity:
• 12 Poles
Environmental Data
• Storage and operating temperature: -20°C to 75°C**
• Flammability rating: UL 94V0
** For fuse performance under or above 25°C, consult fuse
performance derating charts in the Cooper Bussmann
publication titled Selecting Protective Devices (SPD) reorder #3002.
The revolutionary Cooper Bussmann CCP is 1/3 the
footprint of a molded case circuit breaker. The level of
protection provided by the CCP is up to three times the
Short-Circuit Current Rating (SCCR) at full voltage than a
molded case circuit breaker while providing a disconnecting
means.
Product Features and Benefits
• Extremely compact design at 17.5mm wide per pole
• High Short-Circuit Current Ratings up to 200kA (UL) and
120kA (IEC)
• Disconnect rated to provide means for load isolation
• Full voltage rated up to 600Vac or 80Vdc
• Class CC version is UL 98 Listed and horsepower rated,
and suitable for branch circuit disconnect and branch circuit
protection
• IEC 10x38 version complies with IEC 60947-3 and
suitable for branch circuit disconnect and branch circuit
protection
• Suitable for global installations, the units comply with UL,
cULus, and IEC standards accepting UL Class CC, Midget
or IEC aM and gG/gL fuses
• Open Fuse Indication
- Local fuse indication lights* are standard.
- Optional wired remote open fuse indication can be
utilized to signal a PLC and open a contactor to
de-energize all phases, if required.
• IP20 finger-safe with 10AWG (6mm2) or larger wire
• Built-in switch interlock capability prohibits removing the
fuse under load
• Padlockable handle for lockout/tagout procedures
• Available in 1-, 2- and 3-pole versions
• Spade terminals, rated up to 30A, installed on the line side
of the disconnect, make it easy to add NEC®240.21
compliant taps for loads up to 80% of the spade terminal
amp rating for devices that need to remain energized when
the disconnect is in the OFF position
*Circuit must be closed with 90Vac/115Vdc minimum for indication light to
illuminate